| Analog inputs > Input ranges (rated values), resistors > Input resistance (0 to 6000 ohms) | 1 MΩ |
|---|
| Analog inputs > Input ranges (rated values), resistors > PTC | Yes; 15 bit |
|---|
| Analog inputs > Input ranges (rated values), resistors > Input resistance (PTC) | 1 MΩ |
|---|
| Analog inputs > Thermocouple (TC) > Temperature compensation > Parameterizable | Yes |
|---|
| Analog inputs > Thermocouple (TC) > Temperature compensation > Reference channel of the module | Yes |
|---|
| Analog inputs > Thermocouple (TC) > Temperature compensation > internal comparison point | Yes; with BaseUnit type A1 |
|---|
| Analog inputs > Thermocouple (TC) > Temperature compensation > Reference channel of the group | Yes |
|---|
| Analog inputs > Thermocouple (TC) > Temperature compensation > Number of reference channel groups | 4; Group 0 to 3 |
|---|
| Analog inputs > Thermocouple (TC) > Temperature compensation > fixed reference temperature | Yes |
|---|
| Analog inputs > Cable length > shielded, max. | 200 m; 50 m with thermocouples |
|---|
| Analog value generation for the inputs > Measurement principle | integrating (Sigma-Delta) |
|---|
| Analog value generation for the inputs > Integration and conversion time/resolution per channel > Resolution with overrange (bit including sign), max. | 16 bit |
|---|
| Analog value generation for the inputs > Integration and conversion time/resolution per channel > Integration time, parameterizable | Yes |
|---|
| Analog value generation for the inputs > Integration and conversion time/resolution per channel > Basic conversion time, including integration time (ms) > additional processing time for wire-break check | 2 ms; In the ranges resistance thermometers, resistors and thermocouples |
|---|
| Analog value generation for the inputs > Integration and conversion time/resolution per channel > Basic conversion time, including integration time (ms) > additional power line wire-break check | 2 ms; for 3/4 wire transducer (resistance thermometer and resistor) |
|---|
| Analog value generation for the inputs > Integration and conversion time/resolution per channel > Interference voltage suppression for interference frequency f1 in Hz | 16.65060 Hz |
|---|
| Analog value generation for the inputs > Integration and conversion time/resolution per channel > Conversion time (per channel) | 1806050(67.522.518.75) ms |
|---|
| Analog value generation for the inputs > Smoothing of measured values > Number of smoothing levels | 4; None; 4/8/16 times |
|---|
| Analog value generation for the inputs > Smoothing of measured values > parameterizable | Yes |
|---|
| Encoder > Connection of signal encoders > for voltage measurement | Yes |
|---|
| Encoder > Connection of signal encoders > for resistance measurement with two-wire connection | Yes |
|---|
| Encoder > Connection of signal encoders > for resistance measurement with three-wire connection | Yes |
|---|
| Encoder > Connection of signal encoders > for resistance measurement with four-wire connection | Yes |
|---|
| Errors/accuracies > Linearity error (relative to input range), (+/-) | 0.01 %; ±0.1 % for resistance thermometers and resistance |
|---|
| Errors/accuracies > Temperature error (relative to input range), (+/-) | 0.0009 %/K; ±0.005 % / K at thermocouple |
|---|
| Errors/accuracies > Crosstalk between the inputs, min. | -50 dB |
|---|
| Errors/accuracies > Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
|---|
| Errors/accuracies > Operational error limit in overall temperature range > Voltage, relative to input range, (+/-) | 0.2 % |
|---|
| Errors/accuracies > Operational error limit in overall temperature range > Resistance, relative to input range, (+/-) | 0.2 % |
|---|
| Errors/accuracies > Basic error limit (operational limit at 25 °C) > Voltage, relative to input range, (+/-) | 0.05 % |
|---|
| Errors/accuracies > Basic error limit (operational limit at 25 °C) > Resistance, relative to input range, (+/-) | 0.05 % |
|---|
| Errors/accuracies > Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency > Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
|---|
| Errors/accuracies > Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency > Common mode voltage, max. | 10 V |
|---|
| Errors/accuracies > Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency > Common mode interference, min. | 90 dB |
|---|
| Interrupts/diagnostics/status information > Diagnostics function | Yes |
|---|
| Interrupts/diagnostics/status information > Alarms > Diagnostic alarm | Yes |
|---|
| Interrupts/diagnostics/status information > Alarms > Limit value alarm | Yes; two upper and two lower limit values in each case |
|---|
| Interrupts/diagnostics/status information > Diagnoses > Monitoring the supply voltage | Yes |
|---|
| Interrupts/diagnostics/status information > Diagnoses > Wire break | Yes; channel by channel |
|---|
| Interrupts/diagnostics/status information > Diagnoses > Group error | Yes |
|---|
| Interrupts/diagnostics/status information > Diagnoses > Overflow/Underflow | Yes; channel by channel |
|---|
| Interrupts/diagnostics/status information > Diagnostics indication LED > Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
|---|
| Interrupts/diagnostics/status information > Diagnostics indication LED > Channel status display | Yes; green LED |
|---|
| Interrupts/diagnostics/status information > Diagnostics indication LED > for channel diagnostics | Yes; red LED |
|---|
| Interrupts/diagnostics/status information > Diagnostics indication LED > for module diagnostics | Yes; green/red DIAG LED |
|---|
| Potential separation > Potential separation channels > between the channels | No |
|---|
| Potential separation > Potential separation channels > between the channels and backplane bus | Yes |
|---|
| Potential separation > Potential separation channels > between the channels and the power supply of the electronics | Yes |
|---|
| Permissible potential difference > between the inputs (UCM) | 10 V DC |
|---|
| Isolation > Isolation tested with | 750 V DC (type test) and according to EN 50155 (routine test) |
|---|
| Standards, approvals, certificates > Railway application > EN 50121-3-2 | Yes; EMC for rail vehicles |
|---|
| Standards, approvals, certificates > Railway application > EN 50121-4 | Yes; EMC for signal and telecommunications systems |
|---|
| Standards, approvals, certificates > Railway application > EN 50121-5 | Yes; EMC for fixed installations and railway power supply equipment |
|---|
| Standards, approvals, certificates > Railway application > EN 50124-1 | Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC |
|---|
| Standards, approvals, certificates > Railway application > EN 50125-1 | Yes; Rail vehicles - see ambient conditions |
|---|
| Standards, approvals, certificates > Railway application > EN 50125-2 | Yes; Stationary electrical equipment - see ambient conditions |
|---|
| Standards, approvals, certificates > Railway application > EN 50125-3 | Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) |
|---|
| Standards, approvals, certificates > Railway application > EN 50155 | Yes; Rail vehicles - temperature class OT2, ST1/ST2, horizontal mounting position |
|---|
| Standards, approvals, certificates > Railway application > EN 61373 | Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B |
|---|
| Standards, approvals, certificates > Railway application > Fire protection acc. to EN 45545-2 | Yes; Rail vehicles - verification on request |
|---|
| Ambient conditions > Ambient temperature during operation > horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost) |
|---|
| Ambient conditions > Ambient temperature during operation > horizontal installation, max. | 60 °C; = Tmax; +70 °C for 10 min (OT2, ST1/ST2 acc. to EN 50155); +70 °C continuously with spacing modules (6AG2193-6BN00-4BA0) or configured slots to the left and right of the module (OT4, ST0 acc. to EN 50155) |
|---|
| Ambient conditions > Ambient temperature during operation > vertical installation, min. | -40 °C; = Tmin |
|---|
| Ambient conditions > Ambient temperature during operation > vertical installation, max. | 50 °C; = Tmax |
|---|
| Ambient conditions > Altitude during operation relating to sea level > Installation altitude above sea level, max. | 2 000 m |
|---|
| Ambient conditions > Altitude during operation relating to sea level > Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) |
|---|
| Ambient conditions > Relative humidity > With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation |
|---|
| Ambient conditions > Resistance > Coolants and lubricants > Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air |
|---|
| Ambient conditions > Resistance > Use in stationary industrial systems > to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
|---|
| Ambient conditions > Resistance > Use in stationary industrial systems > to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
|---|
| Ambient conditions > Resistance > Use in stationary industrial systems > to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
|---|
| Ambient conditions > Resistance > Use in stationary industrial systems > Against mechanical environmental conditions acc. to EN 60721-3-3 | Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) |
|---|
| Ambient conditions > Resistance > Use on land craft, rail vehicles and special-purpose vehicles > to biologically active substances according to EN 60721-3-5 | Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request |
|---|
| Ambient conditions > Resistance > Use on land craft, rail vehicles and special-purpose vehicles > to chemically active substances according to EN 60721-3-5 | Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
|---|
| Ambient conditions > Resistance > Use on land craft, rail vehicles and special-purpose vehicles > to mechanically active substances according to EN 60721-3-5 | Yes; Class 5S3 incl. sand, dust; * |
|---|
| Ambient conditions > Resistance > Use on land craft, rail vehicles and special-purpose vehicles > Against mechanical environmental conditions acc. to EN 60721-3-5 | Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) |
|---|
| Ambient conditions > Resistance > Usage in industrial process technology > Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) |
|---|
| Ambient conditions > Resistance > Usage in industrial process technology > Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
|---|
| Ambient conditions > Resistance > Remark > Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
|---|
| Ambient conditions > Conformal coating > Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high reliability |
|---|
| Ambient conditions > Conformal coating > Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
|---|
| Ambient conditions > Conformal coating > Electronic equipment on rolling stock acc. to EN 50155 | Yes; Class PC2 protective coating acc. to EN 50155:2017 |
|---|
| Ambient conditions > Conformal coating > Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
|---|
| Ambient conditions > Conformal coating > Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A | Yes; Conformal coating, Class A |
|---|
| Dimensions > Width | 15 mm |
|---|
| Dimensions > Height | 73 mm |
|---|
| Dimensions > Depth | 58 mm |
|---|
| Other > Note: | for use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A, Online Support article 109736776 |
|---|