| Protocols > Open IE communication > IPv6 | No |
|---|
| Interrupts/diagnostics/status information > Status indicator | Yes |
|---|
| Interrupts/diagnostics/status information > Alarms | Yes |
|---|
| Interrupts/diagnostics/status information > Diagnostics function | Yes |
|---|
| Interrupts/diagnostics/status information > Diagnostics indication LED > RUN LED | Yes; green LED |
|---|
| Interrupts/diagnostics/status information > Diagnostics indication LED > ERROR LED | Yes; red LED |
|---|
| Interrupts/diagnostics/status information > Diagnostics indication LED > MAINT LED | Yes; Yellow LED |
|---|
| Interrupts/diagnostics/status information > Diagnostics indication LED > Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
|---|
| Interrupts/diagnostics/status information > Diagnostics indication LED > Connection display LINK TX/RX | Yes; 2x green link LEDs on BusAdapter |
|---|
| Potential separation > between backplane bus and electronics | No |
|---|
| Potential separation > between PROFINET and all other circuits | Yes; 1500 V AC (type test) |
|---|
| Potential separation > between supply and all other circuits | No |
|---|
| Permissible potential difference > between different circuits | Safety extra low voltage SELV |
|---|
| Isolation > Isolation tested with | 750 V DC (type test) and according to EN 50155 (routine test) |
|---|
| Standards, approvals, certificates > Network loading class | 3 |
|---|
| Standards, approvals, certificates > Railway application > EN 50121-3-2 | Yes; EMC for rail vehicles |
|---|
| Standards, approvals, certificates > Railway application > EN 50121-4 | Yes; EMC for signal and telecommunications systems |
|---|
| Standards, approvals, certificates > Railway application > EN 50121-5 | Yes; EMC for fixed installations and railway power supply equipment |
|---|
| Standards, approvals, certificates > Railway application > EN 50124-1 | Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV |
|---|
| Standards, approvals, certificates > Railway application > EN 50125-1 | Yes; Rail vehicles - see ambient conditions |
|---|
| Standards, approvals, certificates > Railway application > EN 50125-2 | Yes; Stationary electrical equipment - see ambient conditions |
|---|
| Standards, approvals, certificates > Railway application > EN 50125-3 | Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) |
|---|
| Standards, approvals, certificates > Railway application > EN 50155 | Yes; Rail vehicles - temperature class OT4, ST1/ST2, horizontal mounting position |
|---|
| Standards, approvals, certificates > Railway application > EN 61373 | Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B |
|---|
| Standards, approvals, certificates > Railway application > Fire protection acc. to EN 45545-2 | Yes; For proof of conformity, see Service & Support |
|---|
| Security > PROFINET Security Class | 1 |
|---|
| Security > signed firmware update | Yes |
|---|
| Security > safely removing data | Yes |
|---|
| Security > data integrity | Yes |
|---|
| Ambient conditions > Ambient temperature during operation > horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost) |
|---|
| Ambient conditions > Ambient temperature during operation > horizontal installation, max. | 70 °C; = Tmax; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155) |
|---|
| Ambient conditions > Ambient temperature during operation > vertical installation, min. | -40 °C; = Tmin |
|---|
| Ambient conditions > Ambient temperature during operation > vertical installation, max. | 50 °C; = Tmax |
|---|
| Ambient conditions > Altitude during operation relating to sea level > Installation altitude above sea level, max. | 2 000 m |
|---|
| Ambient conditions > Altitude during operation relating to sea level > Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) |
|---|
| Ambient conditions > Relative humidity > With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation |
|---|
| Ambient conditions > Resistance > Coolants and lubricants > Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air |
|---|
| Ambient conditions > Resistance > Use in stationary industrial systems > to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
|---|
| Ambient conditions > Resistance > Use in stationary industrial systems > to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
|---|
| Ambient conditions > Resistance > Use in stationary industrial systems > to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
|---|
| Ambient conditions > Resistance > Use in stationary industrial systems > Against mechanical environmental conditions acc. to EN 60721-3-3 | Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0//6AG1193-6AB00-0AA0) |
|---|
| Ambient conditions > Resistance > Use on land craft, rail vehicles and special-purpose vehicles > to biologically active substances according to EN 60721-3-5 | Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request |
|---|
| Ambient conditions > Resistance > Use on land craft, rail vehicles and special-purpose vehicles > to chemically active substances according to EN 60721-3-5 | Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
|---|
| Ambient conditions > Resistance > Use on land craft, rail vehicles and special-purpose vehicles > to mechanically active substances according to EN 60721-3-5 | Yes; Class 5S3 incl. sand, dust; * |
|---|
| Ambient conditions > Resistance > Use on land craft, rail vehicles and special-purpose vehicles > Against mechanical environmental conditions acc. to EN 60721-3-5 | Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) |
|---|
| Ambient conditions > Resistance > Use on land craft, rail vehicles and special-purpose vehicles > against mechanical environmental conditions in agriculture acc. to ISO 15003 | Yes; Level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0/6AG1193-6AB00-0AA0) |
|---|
| Ambient conditions > Resistance > Use on ships/at sea > to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold, fungal and dry rot spores (excluding fauna) |
|---|
| Ambient conditions > Resistance > Use on ships/at sea > to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
|---|
| Ambient conditions > Resistance > Use on ships/at sea > to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
|---|
| Ambient conditions > Resistance > Use on ships/at sea > Against mechanical environmental conditions acc. to EN 60721-3-6 | Yes; class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0/6AG1193-6AB00-0AA0) |
|---|
| Ambient conditions > Resistance > Usage in industrial process technology > Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) |
|---|
| Ambient conditions > Resistance > Usage in industrial process technology > Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
|---|
| Ambient conditions > Resistance > Remark > Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
|---|
| Ambient conditions > Conformal coating > Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high reliability |
|---|
| Ambient conditions > Conformal coating > Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
|---|
| Ambient conditions > Conformal coating > Electronic equipment on rolling stock acc. to EN 50155 | Yes; class PC2 protective coating acc. to EN 50155 |
|---|
| Ambient conditions > Conformal coating > Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
|---|
| Ambient conditions > Conformal coating > Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A | Yes; Conformal coating, Class A |
|---|
| Connection method > ET-Connection > via BU/BA Send | Yes; + 16 ET 200AL modules |
|---|
| Mechanics/material > Strain relief | Yes; Optional |
|---|
| Dimensions > Width | 50 mm |
|---|
| Dimensions > Height | 117 mm |
|---|
| Dimensions > Depth | 74 mm |
|---|
| Weights > Weight, approx. | 125 g; without BusAdapter |
|---|