Product Model
6AG2136-6AB00-1CA1
Material Number
6ag21366ab001ca1
Manufacturer
SIEMENS
Product ID
1242767

Get a Free Quote

Request pricing and availability for 6AG2136-6AB00-1CA1.

More parts to source? Send your whole list in one enquiry

Key specifications

General information > Product type designation
F-AI 4XU 0..10V HF
Supply voltage > Rated value (DC)
24 V
Supply voltage > permissible range, lower limit (DC)
19.2 V
Encoder supply > 24 V encoder supply > Output current, max.
300 mA; total current of all encoders/channels
Power > Power consumption from the backplane bus
70 mW
Errors/accuracies > Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency > Series mode interference (peak value of interference < rated value of input range), min.
40 dB
See all specifications
6AG2136-6AB00-1CA1

Product Information

Technical Specifications

Specifications for 6AG2136-6AB00-1CA1

ParameterValue
General information > Product type designationF-AI 4XU 0..10V HF
General information > Firmware version > FW update possibleYes
General information > based on6ES7136-6AB00-0CA1
General information > usable BaseUnitsBU type A0, A1
General information > Color code for module-specific color-coded labelCC00
General information > Product function > I&M dataYes; I&M0 to I&M3
General information > Engineering with > STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
General information > Operating mode > cyclic measurementYes
General information > Operating mode > OversamplingNo
General information > Operating mode > MSINo
CiR - Configuration in RUN > Reparameterization possible in RUNNo
CiR - Configuration in RUN > Calibration possible in RUNNo
Supply voltage > Rated value (DC)24 V
Supply voltage > permissible range, lower limit (DC)19.2 V
Supply voltage > permissible range, upper limit (DC)28.8 V
Supply voltage > Reverse polarity protectionYes
Supply voltage > power supply according to NEC Class 2 requiredNo
Input current > Current consumption (rated value)0.38 A
Input current > Current consumption, max.0.4 A
Encoder supply > 24 V encoder supply > 24 VYes; min. L+ (-1.5 V)
Encoder supply > 24 V encoder supply > Short-circuit protectionYes
Encoder supply > 24 V encoder supply > Output current, max.300 mA; total current of all encoders/channels
Power > Power consumption from the backplane bus70 mW
Power loss > Power loss, typ.2 W
Address area > Address space per module > Inputs14 byte; S7-300/400F CPU, 13 byte
Address area > Address space per module > Outputs5 byte; S7-300/400F CPU, 4 byte
Hardware configuration > Automatic encodingYes
Hardware configuration > Electronic coding element type HYes
Analog inputs > Number of analog inputs4
Analog inputs > For voltage measurement4
Analog inputs > permissible input voltage for voltage input (destruction limit), max.36 V
Analog inputs > Input ranges (rated values), voltages > 0 to +10 VYes
Analog inputs > Input ranges (rated values), voltages > Input resistance (0 to 10 V)16 kΩ
Analog inputs > Cable length > shielded, max.200 m
Analog value generation for the inputs > Measurement principleSigma Delta
Analog value generation for the inputs > Integration and conversion time/resolution per channel > Resolution with overrange (bit including sign), max.16 bit
Analog value generation for the inputs > Integration and conversion time/resolution per channel > Integration time, parameterizableYes
Analog value generation for the inputs > Integration and conversion time/resolution per channel > Integration time (ms)20 / 16,667
Analog value generation for the inputs > Integration and conversion time/resolution per channel > Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Analog value generation for the inputs > Smoothing of measured values > Number of smoothing levels7
Analog value generation for the inputs > Smoothing of measured values > parameterizableYes
Analog value generation for the inputs > Smoothing of measured values > Step: NoneYes; 1x conversion cycle time
Analog value generation for the inputs > Smoothing of measured values > Step: lowYes; 2x / 4x conversion cycle time
Analog value generation for the inputs > Smoothing of measured values > Step: MediumYes; 8x / 16x conversion cycle time
Analog value generation for the inputs > Smoothing of measured values > Step: HighYes; 32x / 64x conversion cycle time
Analog value generation for the inputs > Smoothing of measured values > Average value filterYes
Encoder > Connection of signal encoders > for voltage measurementYes
Errors/accuracies > Linearity error (relative to input range), (+/-)0.1 %
Errors/accuracies > Temperature error (relative to input range), (+/-)0.023 %/K
Errors/accuracies > Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.1 %
Errors/accuracies > Operational error limit in overall temperature range > Voltage, relative to input range, (+/-)2.6 %
Errors/accuracies > Basic error limit (operational limit at 25 °C) > Voltage, relative to input range, (+/-)0.1 %
Errors/accuracies > Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency > Series mode interference (peak value of interference < rated value of input range), min.40 dB
Errors/accuracies > Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency > Common mode voltage, max.10 V
Errors/accuracies > Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency > Common mode interference, min.70 dB
Interrupts/diagnostics/status information > Diagnostics functionYes
Interrupts/diagnostics/status information > Alarms > Diagnostic alarmYes
Interrupts/diagnostics/status information > Alarms > Limit value alarmNo
Interrupts/diagnostics/status information > Diagnoses > Monitoring the supply voltageYes
Interrupts/diagnostics/status information > Diagnoses > Wire breakYes
Interrupts/diagnostics/status information > Diagnostics indication LED > RUN LEDYes; green LED
Interrupts/diagnostics/status information > Diagnostics indication LED > ERROR LEDYes; red LED
ParameterValue
Interrupts/diagnostics/status information > Diagnostics indication LED > Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Interrupts/diagnostics/status information > Diagnostics indication LED > Channel status displayYes; green LED
Interrupts/diagnostics/status information > Diagnostics indication LED > for channel diagnosticsYes; red LED
Interrupts/diagnostics/status information > Diagnostics indication LED > for module diagnosticsYes; green/red DIAG LED
Potential separation > Potential separation channels > between the channelsNo
Potential separation > Potential separation channels > between the channels and backplane busYes
Potential separation > Potential separation channels > between the channels and the power supply of the electronicsYes
Permissible potential difference > between the inputs (UCM)10 Vpp
Isolation > Isolation tested with750 V DC (type test) and according to EN 50155 (routine test)
Standards, approvals, certificates > Ecological footprint > environmental product declarationYes
Standards, approvals, certificates > Ecological footprint > Global warming potential > global warming potential, (total) [CO2 eq]88.3 kg
Standards, approvals, certificates > Ecological footprint > Global warming potential > global warming potential, (during production) [CO2 eq]13.1 kg
Standards, approvals, certificates > Ecological footprint > Global warming potential > global warming potential, (during operation) [CO2 eq]76.6 kg
Standards, approvals, certificates > Ecological footprint > Global warming potential > global warming potential, (after end of life cycle) [CO2 eq]-1.37 kg
Standards, approvals, certificates > Highest safety class achievable in safety mode > Performance level according to ISO 13849-1PLe
Standards, approvals, certificates > Highest safety class achievable in safety mode > Category according to ISO 13849-1Cat. 4
Standards, approvals, certificates > Highest safety class achievable in safety mode > SIL acc. to IEC 61508SIL 3
Standards, approvals, certificates > Highest safety class achievable in safety mode > SIL in accordance with EN 50126-1, 50129, 50159, 50716SIL 2; a higher safety integrity level is possible if tested and approved for the specific application under consideration of all local regulations.
Standards, approvals, certificates > Highest safety class achievable in safety mode > Probability of failure (for service life of 20 years and repair time of 100 hours) > Low demand mode: PFDavg in accordance with SIL3< 5.00E-05
Standards, approvals, certificates > Highest safety class achievable in safety mode > Probability of failure (for service life of 20 years and repair time of 100 hours) > High demand/continuous mode: PFH in accordance with SIL3< 1.00E-09 1/h
Standards, approvals, certificates > Railway application > EN 50121-3-2Yes; EMC for rail vehicles
Standards, approvals, certificates > Railway application > EN 50121-4Yes; EMC for signal and telecommunications systems
Standards, approvals, certificates > Railway application > EN 50121-5Yes; EMC for fixed installations and railway power supply equipment
Standards, approvals, certificates > Railway application > EN 50124-1Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC
Standards, approvals, certificates > Railway application > EN 50125-1Yes; Rail vehicles - see ambient conditions
Standards, approvals, certificates > Railway application > EN 50125-2Yes; Stationary electrical equipment - see ambient conditions
Standards, approvals, certificates > Railway application > EN 50125-3Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)
Standards, approvals, certificates > Railway application > EN 50155Yes; Rail vehicles - temperature class OT1, ST1/ST2, horizontal mounting position
Standards, approvals, certificates > Railway application > EN 61373Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B
Standards, approvals, certificates > Railway application > Fire protection acc. to EN 45545-2Yes; For proof of conformity, see Service & Support
Ambient conditions > Ambient temperature during operation > horizontal installation, min.-30 °C; = Tmin (incl. condensation/frost)
Ambient conditions > Ambient temperature during operation > horizontal installation, max.60 °C; = Tmax; +70 °C for 10 min (OT1, ST1/ST2 acc. to EN 50155); +70 °C continuously with spacing modules (6AG2193-6BN00-4BA0) or configured empty slots to the left and right of the module (OT3, ST1/ST2 acc. to EN 50155)
Ambient conditions > Ambient temperature during operation > vertical installation, min.-30 °C; = Tmin
Ambient conditions > Ambient temperature during operation > vertical installation, max.50 °C; = Tmax
Ambient conditions > Altitude during operation relating to sea level > Installation altitude above sea level, max.2 000 m
Ambient conditions > Altitude during operation relating to sea level > Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Ambient conditions > Relative humidity > With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Ambient conditions > Resistance > Coolants and lubricants > Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Ambient conditions > Resistance > Use in stationary industrial systems > to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
Ambient conditions > Resistance > Use in stationary industrial systems > to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
Ambient conditions > Resistance > Use in stationary industrial systems > to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Ambient conditions > Resistance > Use in stationary industrial systems > Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Ambient conditions > Resistance > Use on land craft, rail vehicles and special-purpose vehicles > to biologically active substances according to EN 60721-3-5Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
Ambient conditions > Resistance > Use on land craft, rail vehicles and special-purpose vehicles > to chemically active substances according to EN 60721-3-5Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
Ambient conditions > Resistance > Use on land craft, rail vehicles and special-purpose vehicles > to mechanically active substances according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust; *
Ambient conditions > Resistance > Use on land craft, rail vehicles and special-purpose vehicles > Against mechanical environmental conditions acc. to EN 60721-3-5Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Ambient conditions > Resistance > Use on land craft, rail vehicles and special-purpose vehicles > against mechanical environmental conditions in agriculture acc. to ISO 15003Yes; level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Ambient conditions > Resistance > Usage in industrial process technology > Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
Ambient conditions > Resistance > Usage in industrial process technology > Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Ambient conditions > Resistance > Remark > Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Ambient conditions > Conformal coating > Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Ambient conditions > Conformal coating > Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Ambient conditions > Conformal coating > Electronic equipment on rolling stock acc. to EN 50155Yes; Class PC2 protective coating acc. to EN 50155:2017
Ambient conditions > Conformal coating > Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Ambient conditions > Conformal coating > Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions > Width15 mm
Dimensions > Height73 mm
Dimensions > Depth58 mm
Weights > Weight, approx.48 g
Other > Note:for use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A, Online Support article 109736776

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.