Product Model
750-8216
Material Number
—
Manufacturer
WAGO
Product ID
50297

Get a Free Quote

Request pricing and availability for 750-8216.

More parts to source? Send your whole list in one enquiry

Key specifications

Communications
PROFIBUS
Supply voltage (system)
24 VDC (-25 +30 %); Via pluggable connector (CAGE CLAMP®connection)
Supply voltage (field)
24 VDC (-25 +30 %); Via power jumper contacts
Weight
260.7g
Ambient temperature (operation)
0 … +55 °C
Protection type
IP20
See all specifications

Product Highlights

  1. Processor and operating system: ARM Cortex-A8 at 1 GHz running real-time Linux with PREEMPT_RT patch
  2. Programming: CODESYS V3.5 with firmware release 23 or higher, supporting IEC 61131-3 Instruction List (IL)
  3. Memory: 512 MB RAM, 4096 MB internal flash, 128 KB non-volatile hardware memory, 128 KB non-volatile software memory, and program/data memory of 16 MB/64 MB for CODESYS V2 and 32 MB/128 MB for CODESYS V3
  4. Communications: PROFIBUS, CANopen, Modbus (TCP, UDP, RTU), RS-232, RS-485, DHCP, and IEC 60870 telecontrol protocols (additional license required for slave or master)
  5. Node capacity: up to 250 modules per node and 64 modules without a bus extension
  6. Memory card: SD card slot with push-push mechanism and sealable cover lid
  7. Ethernet: 10/100 Mbit/s over twisted pair S-UTP, 100 Ω, Cat. 5, maximum cable length 100 m
  8. Environmental rating: IP20, operating temperature 0 °C to +55 °C, storage temperature -25 °C to +85 °C
750-8216

Product Information

Technical Specifications

Specifications for 750-8216

ParameterValue
CommunicationsPROFIBUS
ETHERNET protocolsDHCP
Telecontrol protocolsIEC 60870 (additional license as slave or master)
VisualizationWeb-Visu
Operating systemReal-time Linux (with PREEMPT_RT patch)
CPUCortex A8; 1 GHz
Programming languages per IEC 61131-3Instruction List (IL)
Programming environmentCODESYS V3.5, Firmware Release 23 or higher
Configuration optionsCODESYS V3
Transmission rateETHERNET: 10/100 mbit/s
Transmission medium (communication/fieldbus)ETHERNET: Twisted Pair S-UTP; 100 Ω; Cat. 5; 100 m maximum cable length
Main memory (RAM)512MB
Internal memory (flash)4096MB
Non-volatile hardware memory128Kbytes
Program memoryCODESYS V2: 16 mB; CODESYS V3: 32 mB
Data memoryCODESYS V2: 64 mB; CODESYS V3: 128 mB
Non-volatile software memory128.Kbytes
Type of memory cardSD card
Memory card slotPush-push mechanism; Cover lid (sealable)
Number of modules per node (max.)250
Number of modules without a bus extension (max.)64
Input and output process image (internal) max.1000 Words/1000 Words
Input and output process image (Modbus®) max.CODESYS V2: 1000 Words/1000 Words; CODESYS V3: 32000 Words/32000 Words
Input and output process image (PROFIBUS) max.244 bytes/244 bytes
Input and output process image (CAN) max.2000 Words/2000 Words
IndicatorsLED (SYS, RUN, I/O, CAN, BF, DIA, U1 U4) red/green/orange: Status system, program, internal data bus, CANopen, PROFIBUS, PROFIBUS diagnostics, status programmable by user (can be used via CODESYS library); LED (A, B) green: System power supply status, field supply
Supply voltage (system)24 VDC (-25 +30 %); Via pluggable connector (CAGE CLAMP®connection)
Input current (typ.) at nominal load (24 V)550mA
Total current (system supply)1,700mA
Supply voltage (field)24 VDC (-25 +30 %); Via power jumper contacts
Current carrying capacity (power jumper contacts)10A
Number of outgoing power jumper contacts3
Isolation500 V system/field
Connection technology: communication/fieldbusPROFIBUS: 1 x D-sub 9 socket; CANopen: 1 x D-sub 9 plug; modbus (TCP, UDP): 2 x RJ-45; modbus RTU: 1 x D-sub 9 socket; RS-232 serial interface: 1 x D-sub 9 socket; RS-4852 interface: 1 x D-sub 9 socket
Connection technology: system supply2 x CAGE CLAMP®
Connection technology: field supply6 x CAGE CLAMP®
Connection type 1System/field supply
Solid conductor0.08 … 2.5 mm2 / 28 14 AWG
Fine-stranded conductor0.08 … 2.5 mm2 / 28 14 AWG
Strip length8 9 mm / 0.31 0.35 inches
Connection technology: device configuration1 x Male connector; 4-pole
Width112 mm / 4.409 inches
Height100 mm / 3.937 inches
Depth71.9 mm / 2.831 inches
Depth from upper-edge of DIN-rail64.7 mm / 2.547 inches
ParameterValue
Weight260.7g
Colorlight gray
Housing materialPolycarbonate; polyamide 6.6
Conformity markingCE
Ambient temperature (operation)0 … +55 °C
Ambient temperature (storage)-25 … +85 °C
Protection typeIP20
Pollution degree2 per IEC 61131-2
Operating altitudewithout temperature derating: 0 2000 m; with temperature derating: 2000 5000 m (0.5 K/100 m); 5000 m (max.)
Relative humidity (without condensation)95%
Mounting positionHorizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Mounting typeDIN-35 rail
Vibration resistance4g per IEC 60068-2-6
Shock resistance15g per IEC 60068-2-27
EMC immunity to interferenceper EN 61000-6-2, marine applications
EMC emission of interferenceper EN 61000-6-3, marine applications
Exposure to pollutantsPer IEC 60068-2-42 and IEC 60068-2-43
Fire load2.883MJ
Permissible pollutant concentration H2S at a relative humidity < 75%10ppm
Permissible pollutant concentration SO 2 at a relative humidity < 75%25ppm
eCl@ss 10.027-24-26-07
eCl@ss 9.027-24-26-07
ETIM 9.0EC000236
ETIM 8.0EC000236
ECCNNO US CLASSIFICATION
PU (SPU)1 pcs
Packaging typebox
Country of originDE
GTIN4055143759809
Customs tariff number8537109160
CAS-No.1303-86-2
REACH Candidate List Substance2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol
RoHS Compliance StatusCompliant,With Exemption
RoHS Exemption6(c)
SCIP notification number (Austria)b9fd5afa-0337-4021-8eca-e378fe47c970
SCIP notification number (Belgium)2435620a-a05f-4cb8-ae93-324c3122fc51
SCIP notification number (Bulgaria)d83ad98d-22ad-40fe-b550-71778e46eb23
SCIP notification number (Czech Republic)cffe418e-2e41-436f-80a1-73ddc85fc981
SCIP notification number (Denmark)cbd8f492-fdb2-43a9-ac34-10ffd93b9a2e
SCIP notification number (Finland)0844fb3c-422c-401b-bf0a-d0436d8fe674
SCIP notification number (France)7d18f8be-67fb-4ed0-b2a8-3275d95ad5ed
SCIP notification number (Germany)1b0e5cda-b6c2-412b-bf8b-3622deefbcf2
SCIP notification number (Hungary)df082563-983b-46d4-be43-fb5a224b3be8
SCIP notification number (Italy)dbf0ec57-3037-41f7-9f30-931b065c9635
SCIP notification number (Netherlands)84b1c473-df7f-4830-a056-d4f123ba8175
SCIP notification number (Poland)a3c3560c-ad82-401a-b6cc-ebb7c853989e
SCIP notification number (Romania)5b20b554-a0b6-441d-8c14-f084d53e9f8d
SCIP notification number (Sweden)f7d11444-434f-4f38-86f1-7994bdaa17bc