- 855-5101/1000-000
WAGO 855-5101/1000-000 is a split-core current transformer for current measurement, with a primary rated current of 1000 A and a secondary rated current of 1 A. Rated power is 0.5 VA and accuracy class is 0.5. Rated frequency is 50 to 60 Hz. The feedthrough for the measurement conductor is 2 x ? 42 mm. The connection cable is 5 m long, 2 x 0.5 mm2 fine-stranded, with brown = S1 and blue = S2. Highest voltage for equipment Um is AC 720 Vrms. Test voltage is AC 3 kV, 50 Hz, 1 min. Protection type is IP20. Dimensions are 66.2 mm wide, 139 mm high, and 66 mm deep; weight is 794 g. Operating ambient temperature is -10 to +40 °C. Conformity marking is CE; standards/specifications include EN 61869-1.
- 855-5105/1000-000
WAGO 855-5105/1000-000 is a split-core current transformer for current measurement, with a primary rated current of 1000 A and a secondary rated current of 5 A. Rated power is 0.5 VA and accuracy class is 0.5. Rated frequency is 50 to 60 Hz. The conductor feedthrough accommodates 2 x 42 mm. Connection cable is 2 x 1.5 mm2 fine-stranded, 3 m long, with black = S1 and red = S2. Dimensions are 66.2 mm wide, 139 mm high, and 66 mm deep. Protection type is IP20. Test voltage is AC 3 kV at 50 Hz for 1 min, and highest voltage for equipment Um is AC 720 Vrms. Operating ambient temperature is -10 to +40 °C. Standards/specifications: EN 61869-1. Conformity marking: CE.
- 855-605/1500-501
WAGO 855-605/1500-501 is a closed current transformer for current measurement. Primary rated current is 1500 A with a 5 A secondary, rated power 5 VA, accuracy class 1, and rated frequency 50 to 60 Hz. The feedthrough for the measurement conductor is Ø 44 mm. Rated continuous thermal current is 1.2 x IN; rated short-time thermal current is 60 x IN for 1 s (max. 100 kA for 1 s). Highest voltage for equipment Um is AC 1.2 kVrms, and test voltage is AC 6 kV at 50 Hz for 1 min. Dimensions are 95 mm width, 114.85 mm height, and 52 mm depth; weight is 396 g. Connection uses CAGE CLAMP® with 9 to 10 mm strip length, accepting 0.08 to 4 mm² (28 to 12 AWG) solid and fine-stranded conductors. Operating ambient temperature is -5 to +50 °C. Conforms to EN 61869-1; CE marked.
- 855-8001
WAGO 855-8001 signal conditioner for voltage measurement, mounted on insulated round cable via IDC connection. Accepts solid or fine-stranded conductors from 2.5 to 6 mm² (14 to 10 AWG). Rated voltage AC 400 V; maximum continuous current 2 A; voltage drop ≤ 0.5 VAC. Voltage path fuse: 2 A, 450 V, F, 70 kA, 5 x 25 mm (WAGO 855-8020). Rated surge voltage 6 kV, overvoltage category III, pollution degree 2, protection type IP20. Test voltage AC 3 kV at 50 Hz for 1 min. Secondary side cable: 1 x 1.0 mm² flexible with ferrule, 3 m length. Dimensions 23 x 59 x 23 mm; weight 25.9 g; PA 66 housing. Ambient temperature -5 to +55 °C operation, -20 to +70 °C storage. Conforms to EN 60947-7-1; CE marked.
- 855-8002
WAGO 855-8002 voltage tap for voltage measurement on insulated round cable. Rated voltage AC 400 V, maximum continuous current 2 A, voltage drop ≤ 0.5 VAC, no fuse in the voltage path. IDC connection accepts solid and fine-stranded conductors of 2.5–6 mm² (14–10 AWG). Secondary side: 1 x 1.0 mm² flexible cable with ferrule, 3 m length. Dimensions 23 x 50 x 23 mm; weight 20 g; PA 66 housing; IP20; mounting on insulated round cable; torque 1.5–2 Nm; reusable up to 24 times. Rated surge voltage 6 kV, overvoltage category III, pollution degree 2. Test voltage AC 3 kV, 50 Hz, 1 min. Operating temperature -5 to +55 °C; storage -20 to +70 °C; relative humidity 5–85% without condensation; maximum operating altitude 2000 m. Conforms to EN 60947-7-1; CE marking.
- 855-8003
WAGO 855-8003 signal conditioner, a voltage tapping terminal with fuse for phase application. It mounts on insulated round cable and uses IDC connection for solid or fine-stranded conductors of 10–16 mm² (8–6 AWG). Rated voltage is AC 400 V; maximum continuous current is 2 A. The voltage-path fuse is 2 A, 450 V, F, 70 kA, 5 x 25 mm (WAGO 855-8020). Voltage drop is ≤ 0.5 VAC. Rated surge voltage is 6 kV, overvoltage category III, pollution degree 2. Test voltage is AC 3 kV, 50 Hz, 1 min. Protection type IP20. Dimensions: 23 mm width, 59 mm height, 23 mm depth; weight 72.6 g. Operating ambient temperature -5 to +55 °C. Standards: EN 60947-7-1; CE marking.
- 855-8004
WAGO 855-8004 voltage tap for voltage measurement, mounted on insulated round cable. Rated voltage AC 400 V; maximum continuous current 2 A; voltage drop ≤ 0.5 VAC. No fuse in the voltage path. Connection technology is IDC; accepts solid and fine-stranded conductors of 10–16 mm² (8–6 AWG). Secondary side: 1 x 1.0 mm² flexible cable with ferrule, 3 m length. Rated surge voltage 6 kV, overvoltage category III, pollution degree 2, protection type IP20. Test voltage AC 3 kV at 50 Hz for 1 min. Dimensions 23 x 50 x 23 mm; PA 66 housing; 21 g. Torque range 1.5–2 Nm. Reusable up to 24 times. Ambient temperature -5 to +55 °C in operation, -20 to +70 °C in storage; relative humidity 5–85 % without condensation; maximum operating altitude 2000 m. Conforms to EN 60947-7-1; CE marking.
- 855-8008
WAGO 855-8008 busbar tap for measuring L- or N-conductors, with an integrated SIBA fuse. It mounts on a busbar and uses Push-in CAGE CLAMP connection technology (WAGO 2624 Series). Dimensions are 61 mm width, 14 mm height, and 48 mm depth; weight is 31 g. The voltage path fuse is 2 A, 450 V, F, 70 kA, 5 x 25 mm (WAGO 855-8020). Rated voltage is AC 400 V; measured variable is voltage. Solid and fine-stranded conductors accept 0.2 to 6 mm2 (24 to 10 AWG), with 10 to 12 mm strip length. Operating ambient temperature is -25 to +70 °C, storage -40 to 85 °C, relative humidity 5 to 85 percent without condensation, and maximum operating altitude 2000 m. Standard: IEC 60947-7-3.