- 855-8002
WAGO 855-8002 voltage tap for voltage measurement on insulated round cable. Rated voltage AC 400 V, maximum continuous current 2 A, voltage drop ≤ 0.5 VAC, no fuse in the voltage path. IDC connection accepts solid and fine-stranded conductors of 2.5–6 mm² (14–10 AWG). Secondary side: 1 x 1.0 mm² flexible cable with ferrule, 3 m length. Dimensions 23 x 50 x 23 mm; weight 20 g; PA 66 housing; IP20; mounting on insulated round cable; torque 1.5–2 Nm; reusable up to 24 times. Rated surge voltage 6 kV, overvoltage category III, pollution degree 2. Test voltage AC 3 kV, 50 Hz, 1 min. Operating temperature -5 to +55 °C; storage -20 to +70 °C; relative humidity 5–85% without condensation; maximum operating altitude 2000 m. Conforms to EN 60947-7-1; CE marking.
- 855-8003
WAGO 855-8003 signal conditioner, a voltage tapping terminal with fuse for phase application. It mounts on insulated round cable and uses IDC connection for solid or fine-stranded conductors of 10–16 mm² (8–6 AWG). Rated voltage is AC 400 V; maximum continuous current is 2 A. The voltage-path fuse is 2 A, 450 V, F, 70 kA, 5 x 25 mm (WAGO 855-8020). Voltage drop is ≤ 0.5 VAC. Rated surge voltage is 6 kV, overvoltage category III, pollution degree 2. Test voltage is AC 3 kV, 50 Hz, 1 min. Protection type IP20. Dimensions: 23 mm width, 59 mm height, 23 mm depth; weight 72.6 g. Operating ambient temperature -5 to +55 °C. Standards: EN 60947-7-1; CE marking.
- 855-8004
WAGO 855-8004 voltage tap for voltage measurement, mounted on insulated round cable. Rated voltage AC 400 V; maximum continuous current 2 A; voltage drop ≤ 0.5 VAC. No fuse in the voltage path. Connection technology is IDC; accepts solid and fine-stranded conductors of 10–16 mm² (8–6 AWG). Secondary side: 1 x 1.0 mm² flexible cable with ferrule, 3 m length. Rated surge voltage 6 kV, overvoltage category III, pollution degree 2, protection type IP20. Test voltage AC 3 kV at 50 Hz for 1 min. Dimensions 23 x 50 x 23 mm; PA 66 housing; 21 g. Torque range 1.5–2 Nm. Reusable up to 24 times. Ambient temperature -5 to +55 °C in operation, -20 to +70 °C in storage; relative humidity 5–85 % without condensation; maximum operating altitude 2000 m. Conforms to EN 60947-7-1; CE marking.
- 855-8008
WAGO 855-8008 busbar tap for measuring L- or N-conductors, with an integrated SIBA fuse. It mounts on a busbar and uses Push-in CAGE CLAMP connection technology (WAGO 2624 Series). Dimensions are 61 mm width, 14 mm height, and 48 mm depth; weight is 31 g. The voltage path fuse is 2 A, 450 V, F, 70 kA, 5 x 25 mm (WAGO 855-8020). Rated voltage is AC 400 V; measured variable is voltage. Solid and fine-stranded conductors accept 0.2 to 6 mm2 (24 to 10 AWG), with 10 to 12 mm strip length. Operating ambient temperature is -25 to +70 °C, storage -40 to 85 °C, relative humidity 5 to 85 percent without condensation, and maximum operating altitude 2000 m. Standard: IEC 60947-7-3.
- 855-801/2000-1001
WAGO 855-801/2000-1001 is a closed current transformer with a 2000 A primary rated current and 1 A secondary rated current, rated power 10 VA, accuracy class 1, and rated frequency 50 to 60 Hz. The measurement conductor feedthrough is Ø 55 mm. Rated continuous thermal current is 1.2 x IN; rated short-time thermal current is 60 x IN/1 s (max. 100 kA/1 s). Test voltage is AC 6 kV at 50 Hz for 1 min, and highest voltage for equipment Um is AC 1.2 kVrms. Insulation class E. Dimensions are 120 mm width, 134.4 mm height, and 52 mm depth; weight 396 g. Operation is -5 to +50 °C, storage -25 to +70 °C, maximum operating altitude 1000 m. Connection technology is CAGE CLAMP. Conformity marking CE; standards/specifications EN 61869-1.
- 855-8015
WAGO 855-8015 power tap for busbar installation, with clamping connection and integrated SIBA fuse with indicator for measuring L- or N-conductors. It measures voltage, has a rated voltage of AC 400 V, and uses Push-in CAGE CLAMP connection technology with a WAGO 2624 Series connector. Busbar thickness range is 4 mm to 15 mm. Dimensions are 79 mm width, 15 mm height, and 72 mm depth, weighing 160 g. Operating ambient temperature is -25 to +70 °C; storage temperature is -40 to 85 °C. Relative humidity is 5 to 85 % without condensation. Maximum operating altitude is 2000 m. The voltage path fuse is 2 A; 450 V; F; 70 kA; 5 x 25 mm (WAGO 855-8020). Standards/specifications: IEC 60947-7-3.
- 855-805/2000-1001
WAGO 855-805/2000-1001 is a closed current transformer for current measurement, with a 2000 A / 5 A ratio, 5 A secondary rated current, 10 VA rated power, and accuracy class 1. The feedthrough for the measurement conductor is Ø 55 mm. It measures 120 mm wide, 134.4 mm high, and 52 mm deep, and weighs 396 g. Rated frequency is 50 … 60 Hz. Rated continuous thermal current Icth is 1.2 x IN; rated short-time thermal current Ith is 60 x IN / 1 s (max. 100 kA / 1 s). Test voltage is AC 6 kV; 50 Hz; 1 min. Highest voltage for equipment Um is AC 1.2 kVrms. Insulation class E. Ambient temperature: -5 … +50 °C operation, -25 … +70 °C storage. Maximum operating altitude 1000 m. Connection technology is CAGE CLAMP. Conformity marking CE; standards/specifications EN 61869-1.
- 855-9150/2000-1251
WAGO 855-9150/2000-1251 is a split-core Rogowski coil current transformer for current measurement. It measures 10 A to 10,000 A, or up to 4000 A when combined with recommended WAGO products, with a sensitivity of 22.5 mV/kA at 50 Hz and accuracy class 0.5. Rated frequency is 50 to 60 Hz. The feedthrough for the measurement conductor is 125 mm, cable length is 1.5 m, and weight is 130 g. Rated voltage is 1000 VACrms (Cat. III) or 600 VACrms (Cat. IV). Protection type is IP57. Operating ambient temperature is -40 to +80 °C at up to 90% relative humidity without condensation, maximum operating altitude 2000 m. Conforms to EN 61010-1 and carries the CE marking.