| Product or component type | Contactor |
|---|
| [Ue] rated operational voltage | <= 690 V AC 50/60 Hz / <= 460 V DC |
|---|
| [Ie] rated operational current | 250 A (at <40 °C) at <= 440 V AC-1 |
|---|
| [Uc] control circuit voltage | 24...575 V AC 40...400 Hz with LX1/LX9 coil24...460 V DC with LX4 coil100...250 V AC 50/60 Hz with LXE coil100...380 V DC with LXE coil |
|---|
| Control circuit voltage limits | Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coilDrop-out: 0.2...0.55 Uc AC 40...400 Hz with LX1/LX9 coilOperational: 0.85...1.1 Uc DC with LX4 coilDrop-out: 0.15...0.2 Uc DC with LX4 coilOperational: 85...275 V AC 50/60 Hz with LXE coilDrop-out: 0...60 V AC 50/60 Hz with LXE coilOperational: 85...418 V DC with LXE coilDrop-out: 0...45 V DC with LXE coil |
|---|
| power pole contact composition | 4 NO |
|---|
| Range | TeSys |
|---|
| Product name | TeSys F |
|---|
| Connections - terminals | Power circuit: lugs-ring terminals 1 cable(s) 120 mm² - busbar cross section: 25 x 3 mmPower circuit: connector 1 cable(s) 120 mm²Power circuit: bar 2 cable(s)Power circuit: bolted connectionControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable endControl circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable endControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable endControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable endControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²flexible without cable endControl circuit: screw clamp terminals 1.0 cable(s) 0.25…2.5 mm²flexible with cable endControl circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²solid without cable end |
|---|
| Height | 170 mm |
|---|
| Width | 200.5 mm |
|---|
| Depth | 171 mm |
|---|
| IP degree of protection | IP2X front face with shrouds conforming to IEC 60529 / IP2X front face with shrouds conforming to VDE 0106 |
|---|
| Ambient air temperature for operation | -40…60 °C |
|---|
| Product certifications | ABSCSABVCBRINARMRoSDNVLROS (Lloyds register of shipping)ULUKCA |
|---|