Industrial Automation Parts. Prompt replies from real people.

Schneider LC1F1504G6 TeSys F Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the Schneider LC1F1504G6?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1F1504G6 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1F1504G6
Material Number
—
Manufacturer
Schneider
Product ID
33046

Get a Free Quote

Request pricing and availability for LC1F1504G6.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current
250 A (at <104 °F (40 °C)) at <= 440 V AC AC-1
[Uc] control circuit voltage
120 V AC 60 Hz
IP degree of protection
IP2X front face with shrouds IEC 60529 / IP2X front face with shrouds VDE 0106
See all specifications

Product Highlights

  1. Contactor Configuration: 4-pole (4 NO) AC-1 resistive-load contactor in the TeSys F range
  2. Rated Operational Current: 250 A at up to 440 V AC and 40 °C, with 250 A conventional free-air thermal current at 40 °C
  3. Rated Operational Voltage: up to 1000 V AC 50/60 Hz or 460 V DC, with 8 kV rated impulse withstand voltage and 1000 V rated insulation voltage
  4. Control Circuit: 120 V AC 60 Hz coil with operational limits of 0.85 to 1.1 Uc and drop-out limits of 0.35 to 0.55 Uc
  5. Motor Power Ratings: 40 hp at 200 V AC, 50 hp at 230 V AC, 100 hp at 460 V AC, and 125 hp at 575 V AC
  6. Short-Time Withstand Current: 1200 A for 10 s, 700 A for 30 s, 600 A for 1 min, 450 A for 3 min, and 350 A for 10 min at 40 °C
  7. Connections: Bolted power connections for bars, lugs-ring terminals, or 120 mm² connectors, with control circuit screw clamp terminals accepting 1 to 4 mm² flexible or solid conductors
  8. Mechanical Durability: 10 million operating cycles with a maximum operating rate of 2400 cycles per hour at 55 °C
  9. Operating Temperature Range: -40 to 60 °C, with storage from -60 to 80 °C and operation up to 3000 m without derating
LC1F1504G6

Product Information

Technical Specifications

Specifications for LC1F1504G6

ParameterValue
Product or Component TypeContactor
Range of ProductTeSys F
[Ue] rated operational voltage<= 1000 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current250 A (at <104 °F (40 °C)) at <= 440 V AC AC-1
[Uc] control circuit voltage120 V AC 60 Hz
Control circuit voltage limitsOperational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) / Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))
Power dissipation per pole22 W AC-1
Device short nameLC1F
Connections - terminalsControl circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable endControl circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable endControl circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable endControl circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable endControl circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable endControl circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable endPower circuit bolted connectionPower circuit 2 bars 25 x 3 mmPower circuit lugs-ring terminals 1 0.2 in² (120 mm²)Power circuit connector 1 0.2 in² (120 mm²)
ParameterValue
Height6.7 in (170 mm)
Width7.9 in (200.5 mm)
Depth6.7 in (171 mm)
IP degree of protectionIP2X front face with shrouds IEC 60529 / IP2X front face with shrouds VDE 0106
Ambient Air Temperature for Operation-40…140 °F (-40…60 °C)
Product CertificationsDNVCBLROS (Lloyds register of shipping)RMRoSABSULRINACCCBV

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp