Q1Can you supply the Schneider LC1F1504GD?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1F1504GD cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1F1504GD
Material Number
—
Manufacturer
Schneider
Product ID
33086

Get a Free Quote

Request pricing and availability for LC1F1504GD.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
<= 690 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current
250 A (at <40 °C) at <= 440 V AC-1
[Uc] control circuit voltage
125 V DC
IP degree of protection
IP2X front face with shrouds conforming to IEC 60529 / IP2X front face with shrouds conforming to VDE 0106
See all specifications

Product Highlights

  1. Product Type: TeSys F (LC1F) 4-pole contactor for resistive loads, utilisation category AC-1
  2. Rated Operational Voltage: <= 690 V AC 50/60 Hz or <= 460 V DC
  3. Rated Operational Current: 250 A at <= 440 V AC-1 and 40 °C, matching the 250 A conventional free air thermal current at 40 °C
  4. Control Circuit: 125 V DC standard control, with operational limits 0.85 to 1.1 Uc and drop-out 0.15 to 0.2 Uc at 55 °C
  5. Short-Time Withstand Current: 1200 A for 10 s, 700 A for 30 s, 600 A for 1 min, 450 A for 3 min, 350 A for 10 min at 40 °C
  6. Associated Fuse Rating: 160 A aM or 250 A gG at <= 440 V
  7. Rated Insulation and Impulse Withstand: 1000 V per IEC 60947-4-1, 1500 V per VDE 0110 group C, and 8 kV impulse withstand
  8. Mechanical Durability and Operating Rate: 10 million cycles and up to 2400 cycles per hour at 55 °C
  9. Ambient Air Temperature for Operation: -40 to 60 °C, with permissible 60 to 70 °C around the device at Uc
LC1F1504GD

Product Information

Technical Specifications

Specifications for LC1F1504GD
ParameterValue
Product or component typeContactor
Range of productTeSys F
[Ue] rated operational voltage<= 690 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current250 A (at <40 °C) at <= 440 V AC-1
[Uc] control circuit voltage125 V DC
Control circuit voltage limitsOperational: 0.85...1.1 Uc (at 55 °C) / Drop-out: 0.15...0.2 Uc (at 55 °C)
Power dissipation per pole22 W AC-1
RangeTeSys
Connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable endControl circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable endControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable endControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable endControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable endControl circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable endPower circuit: bar 2 cable(s) - busbar cross section: 25 x 3 mmPower circuit: lugs-ring terminals 1 cable(s) 120 mm²Power circuit: connector 1 cable(s) 120 mm²Power circuit: bolted connection
Height170 mm
Width200.5 mm
Depth171 mm
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529 / IP2X front face with shrouds conforming to VDE 0106
Ambient air temperature for operation-40…60 °C
Product certificationsABSULLROS (Lloyds register of shipping)CBDNVCCCBVRMRoSRINA