Industrial Automation Parts. Prompt replies from real people.

Schneider LC1F1504FD TeSys F Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the Schneider LC1F1504FD?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1F1504FD cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1F1504FD
Material Number
—
Manufacturer
Schneider
Product ID
33044

Get a Free Quote

Request pricing and availability for LC1F1504FD.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
<= 690 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current
250 A (at <40 °C) at <= 440 V AC-1
[Uc] control circuit voltage
110 V DC
IP degree of protection
IP2X front face with shrouds conforming to IEC 60529 / IP2X front face with shrouds conforming to VDE 0106
See all specifications

Product Highlights

  1. 4-Pole Contactor: TeSys F LC1F contactor with 4 NO power poles for resistive load AC-1 applications
  2. Rated Operational Current: 250 A at up to 440 V AC and 40 °C, with 250 A conventional free air thermal current at 40 °C
  3. Rated Operational Voltage: Up to 690 V AC 50/60 Hz or 460 V DC, with 8 kV impulse withstand and 1000 V insulation rating
  4. 110 V DC Control Circuit: DC standard control coil with operational limits 0.85 to 1.1 Uc, 560 W inrush and 4.5 W hold-in power
  5. Durability and Operating Rate: 10 million mechanical cycles and maximum operating rate of 2400 cycles per hour at 55 °C
  6. Short-Time Withstand Current: 1200 A for 10 s, 700 A for 30 s, 600 A for 1 min, 450 A for 3 min, and 350 A for 10 min at 40 °C
  7. Ambient Operating Range: -40 to 60 °C operation and -60 to 80 °C storage, with operating altitude up to 3000 m without derating
LC1F1504FD

Product Information

Technical Specifications

Specifications for LC1F1504FD
ParameterValue
Product or component typeContactor
Range of productTeSys F
[Ue] rated operational voltage<= 690 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current250 A (at <40 °C) at <= 440 V AC-1
[Uc] control circuit voltage110 V DC
Control circuit voltage limitsOperational: 0.85...1.1 Uc (at 55 °C) / Drop-out: 0.15...0.2 Uc (at 55 °C)
Power dissipation per pole22 W AC-1
RangeTeSys
Connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable endControl circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable endControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable endControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable endControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable endControl circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable endPower circuit: bar 2 cable(s) - busbar cross section: 25 x 3 mmPower circuit: lugs-ring terminals 1 cable(s) 120 mm²Power circuit: connector 1 cable(s) 120 mm²Power circuit: bolted connection
Height170 mm
Width200.5 mm
Depth171 mm
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529 / IP2X front face with shrouds conforming to VDE 0106
Ambient air temperature for operation-40…60 °C
Product certificationsABSCCCCBULRMRoSBVDNVLROS (Lloyds register of shipping)RINA

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.