- ESB40-40N-14
ABB ESB40-40N-14 building contactor, 4-pole with four normally open main contacts and no auxiliary contacts. Rated operational voltage is 220 V DC and 400 V AC on the main circuit; rated control circuit voltage is 12 V. Rated operational current is 40 A at AC-1 and AC-7a, and 22 A at AC-3 (230 V single phase, 400 V three phase) and AC-7b. Rated impulse withstand voltage is 6 kV, rated insulation voltage 500 V, degree of protection IP20. Dimensions are 54 mm wide, 85 mm high, 65 mm deep; net weight 0.405 kg. Standards: IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 61095, UL 60947-1, UL 60947-4-1, IEC 60335-2-40 A2L.
- ESB63-20N-06
ABB ESB63-20N-06 building contactor, manufacturer ID 1SAE351111R0620. Two-pole (2 NO main contacts, no auxiliary contacts), rated operational current 63 A at AC-1 and AC-7a, 30 A at AC-3 and AC-7b (230 V single phase). Rated operational voltage: main circuit 220 V DC and 400 V AC; rated control circuit voltage 230 V. Rated operational power at 230 V single phase: 14.5 kW (AC-1, AC-7a) and 5 kW (AC-3, AC-7b). Rated insulation voltage 500 V, rated impulse withstand voltage 6 kV, pollution degree 3. Dimensions 54 x 85 x 65 mm, weight 0.37 kg, 3.0 modular spacings, IP20. Ambient air temperature: operation -25 to +55 °C, storage -40 to +80 °C. Standards: IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 61095, UL 60947-1, UL 60947-4-1, IEC 60335-2-40 A2L.
- ESB63-22N-06
The ABB ESB63-22N-06 is a 4-pole building contactor with 2 main NC contacts and 2 main NO contacts. It measures 54 mm wide, 85 mm high, and 65 mm deep, weighs 0.4 kg, and occupies 3.0 modular spacings. Main circuit rated operational voltage is 220 V DC and 400 V AC; rated control circuit voltage is 230 V. Rated operational current is 30 A for NC and 63 A for NO at AC-1, and 30 A single-phase NO at AC-3 (230 V). Rated impulse withstand voltage is 6 kV and rated insulation voltage is 500 V. Degree of protection is IP20, pollution degree 3, operating ambient temperature -25 to +55 °C, maximum operating altitude 2000 m. Standards include IEC/EN 60947-1, IEC/EN 60947-4-1, and IEC/EN 61095.
- ESB63-22N-07
The ABB ESB63-22N-07 is a 4-pole building contactor with 2 NO and 2 NC main contacts. It measures 54 mm wide, 85 mm high, and 65 mm deep, and weighs 0.405 kg. Rated operational voltage is 400 V AC for the main circuit and 220 V DC for the main circuit; rated control circuit voltage is 400 V. Rated operational current is 63 A (NO) and 30 A (NC) at AC-1, and 30 A (NO) at AC-3 (230 V, single phase). Rated operational power at AC-1 is 14.5 kW (NO) and 6.9 kW (NC) at 230 V single phase. Degree of protection is IP20. Standards include IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 61095, UL 60947-1, UL 60947-4-1, and IEC 60335-2-40 A2L.
- ESB63-30N-06
ABB building contactor ESB63-30N-06, manufacturer ID 1SAE351111M0630. Three-pole installation contactor with three normally open main contacts and no auxiliary contacts. Rated operational current AC-1 (NO) 63 A; AC-3 (NO) 30 A at 230 V single phase and 30 A at 400 V three phase. Rated operational voltage: main circuit 220 V DC and 400 V AC. Rated control circuit voltage 230 V, with control circuit frequencies of 50 Hz, 60 Hz, 400 Hz, and DC. Rated insulation voltage 500 V; rated impulse withstand voltage 6 kV. Dimensions 54 mm wide, 85 mm high, 65 mm deep; net weight 0.385 kg. IP20. Standards: IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 61095, UL 60947-1, UL 60947-4-1, IEC 60335-2-40 A2L.
- ESB63-30N-07
The ABB ESB63-30N-07 is a three-pole building contactor with three normally open main contacts and no auxiliary contacts. It is rated 63 A at AC-1 and 30 A at AC-3 for single-phase 230 V and three-phase 400 V, corresponding to 14.5 kW and 43.6 kW at AC-1, and 5 kW and 15 kW at AC-3. Main circuit rated operational voltage is 220 V DC or 400 V AC; rated insulation voltage is 500 V and rated impulse withstand voltage is 6 kV. Dimensions are 54 mm wide, 85 mm high, and 65 mm deep, weighing 0.385 kg. Degree of protection is IP20, with a mechanical durability of 1,000,000 cycles. Standards include IEC/EN 60947-1, IEC/EN 60947-4-1, and IEC/EN 61095.
- ESB63-31N-04
The ABB ESB63-31N-04 is a four-pole building contactor with three normally open main contacts and one normally closed main contact. It is rated 63 A AC-1 (NO) and 30 A AC-1 (NC), with AC-3 ratings of 30 A at 230 V single phase and 400 V three phase. Rated operational voltage is 220 V DC or 400 V AC main circuit, with a 110 V control circuit voltage. Dimensions are 54 mm wide, 85 mm high, and 65 mm deep, weighing 0.405 kg. It offers IP20 protection, 6 kV impulse withstand, 500 V insulation voltage, and operates from -25 to +55 °C. Standards include IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 61095, UL 60947-1, and UL 60947-4-1.
- ESB63-31N-06
ABB ESB63-31N-06 building contactor, manufacturer ID 1SAE351111R0631. Four poles with three normally open main contacts and one normally closed main contact. Rated operational voltage: main circuit 220 V DC and 400 V AC. Rated control circuit voltage 230 V. Rated operational current: AC-1 63 A (NO) and 30 A (NC); AC-3 30 A at 230 V single phase and 400 V three phase. Rated operational power AC-3: 5 kW at 230 V single phase and 15 kW at 400 V three phase. Dimensions 54 mm wide, 85 mm high, 65 mm deep; net weight 0.405 kg. IP20, rated insulation voltage 500 V, impulse withstand 6 kV, pollution degree 3. Ambient operating temperature -25 to +55 °C. Standards: IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 61095, UL 60947-1, UL 60947-4-1.