Before You Swap a Failed Drive: The Checks That Prevent a Second Failure

When a drive fails, everyone wants the same thing: the old one out, the spare in, the line running. The swap itself takes twenty minutes. What decides whether production is still running next week is the information captured around the swap — most of it in the hour before the replacement arrives, and some of it in the five minutes before anyone touches the reset button.

This is the checklist we give customers who are buying a replacement drive, because the saddest sentence in this business is "the new one failed the same way." Drives rarely die of old age alone. They are usually killed by something that is still in the cabinet, waiting for the next one.

Step 1: Before you power-cycle — capture the evidence

A drive's fault memory is the black-box recorder of its own death, and the first power-cycle or reset can clear exactly the entries you need.

  1. Photograph the keypad/display — the active fault and any alarm history, with codes, not just "it says F-something".
  2. Open the fault log if the drive supports it — the last several faults with timestamps and the operating state at trip (current, DC-bus voltage, heatsink temperature, run hours). A drive that tripped on overcurrent at 40% load is telling a different story from one that tripped at 140%.
  3. Record the run-hours and start counters if shown. They set honest expectations for the rest of the drivetrain.
  4. Note what the machine was doing when it failed: starting, running steady, braking, sitting powered. Drives that fail at power-up after a weekend stop have usually died of capacitor ageing; drives that fail under braking load point at the braking path.

Only now reset or power-cycle — once, to see whether the fault is permanent. If it clears and runs, you have bought diagnostic time, not a repair; a drive that has faulted hard once will do it again, usually during the shift you can least afford.

Step 2: Back up the parameters before unplugging anything

The hardware is replaceable from stock. The parameter set — ten years of tuning by three different engineers — often exists nowhere else.

Where parameters live, by family:

Drive family Backup routes
ABB ACS880 / ACS580 Keypad (panel backup), memory unit, Drive Composer PC tool
ABB ACS800 (legacy) Keypad copy function, DriveWindow; the application program is a separate concern from parameters
Siemens SINAMICS G120 / S120 Operator panel (IOP/BOP) copy, memory card, STARTER/Startdrive project
Siemens MICROMASTER (legacy) BOP/AOP copy, DriveMonitor — assume no backup exists until you have one
Schneider Altivar (ATV630/930, legacy ATV61/71) Keypad/HMI save, SoMove software, Multiloader
Allen-Bradley PowerFlex HIM copy (HIM CopyCat on older series), Connected Components Workbench, drive's own memory

Rules that hold for every family:

  • A photo of the keypad values beats no backup, but a real file beats photos. If the drive still powers its control side, take the electronic backup even if the power stage is dead — on many drives the control board and its memory survive the failure.
  • Record the motor nameplate too (voltage, current, frequency, speed, cosφ). If the parameter backup fails, the nameplate plus autotune gets you most of the way back — see Step 5.
  • Write down the control wiring logic while it is still connected: which terminals carry start, speed reference, faults, and whether control is 2-wire or 3-wire, PNP or NPN. Photograph the terminal strip before a single wire moves, and label wires that are not numbered.

Step 3: Find out what killed it — before the new one is in the line of fire

Replacing a drive without a cause is scheduling the next failure. The common killers, and their fingerprints:

Suspected cause Evidence to check Fix before the swap
Failed cooling fan / clogged heatsink Fan date label older than ~5 years, dust mats on heatsink fins, overtemp faults in the log Clean cabinet, replace filters, check fan operation on the new setup
Capacitor ageing (shelf or service) Drive sat unpowered for years; fails at power-up; DC-bus undervoltage faults Follow the maker's reforming procedure for any long-stored drive — including the "new" spare
Incoming surge / poor supply Failed input stage, damaged surge protection in the cabinet, trips cluster after storms or switchovers Check surge arresters, line fuses and supply quality first
Motor or cable insulation failure Ground-fault trips, fault follows one motor/cable Insulation-test motor and cable with the drive disconnected — never megger into a connected drive, old or new
Braking overload Overvoltage trips on deceleration, hot or open braking resistor Measure the resistor; check its value against the drive's specification
Loose/overheated terminals Discoloured terminal plastic, heat marks on cable ends Re-terminate properly torqued connections during the swap

That capacitor point deserves emphasis, because it catches people with the replacement part: a drive that has sat unpowered in a warehouse for years — including a genuinely new one — may need its DC-bus capacitors reformed (a controlled, gradual voltage application) before full power. Skipping this is a recognised way to kill a new-old-stock drive on its first energisation. The procedure is in every maker's manual; it takes an hour; it is worth it. DC drives are no exception — for installed DCS800 converters, see what changes as the DCS800 enters its Limited phase before you plan spares around long-stored modules.

Step 4: Match more than the kilowatts

The replacement does not need to be the same catalogue number in every case — migration to a successor is often the better part — but these must match or be consciously re-engineered:

Where the maker publishes a model-by-model path, use it instead of a family-name swap — see the official ACS355-to-ACS380 replacement path for how that check works on ABB's outgoing machinery drives.

  • Rating in the right terms — match current (amps) at the actual switching frequency and duty, not just the kW headline, which assumes a standard motor.
  • Feedback device — encoder or resolver type, voltage and pinout. A drive configured for an encoder it cannot read will not turn the motor, and some feedback cards are family-specific.
  • Option boards — fieldbus adapters (PROFIBUS, PROFINET, EtherNet/IP, DeviceNet), I/O extensions, encoder cards. On some families they transfer to the replacement; on others they must be ordered with it. Check before the swap day, not during it.
  • Firmware and application — if the drive runs an application program (positioning, winding, pump logic) rather than plain speed control, the program is a deliverable of its own. A parameter file does not always contain it.
  • Safety functions — STO wiring and behaviour differ between generations. A successor drive is rarely a pin-for-pin safety equivalent; treat the safety circuit as a small engineering task, not a wire swap.
  • EMC and cabling practice — keep shielded motor cable practice and grounding as installed; do not "improve" the layout mid-repair unless it was the problem.

Step 5: First run of the new drive

  1. Enter or restore motor data first, then run the identification/autotune routine the drive offers — with the motor uncoupled if the procedure or the load requires it.
  2. Restore parameters, then verify the handful that hurt: ramp times, maximum frequency/speed, current limit, control source (keypad vs terminals vs fieldbus), and the speed-reference scaling. A drive that runs but at half speed has a scaling mismatch, not a fault.
  3. Direction check at low speed before coupling the load. Swapped phases are harmless to fix now and expensive after a loaded start.
  4. Loaded run with eyes on current — compare draw against the motor nameplate at the same duty the old drive ran. Substantially higher current means the problem is downstream and the old drive was a victim, not the culprit.
  5. Watch the first stops — braking behaviour is where resistor and parameter problems announce themselves.
  6. Save a fresh backup of the working configuration — to the keypad, to a file, and to wherever your plant keeps such things. The next engineer (possibly you, at 2 a.m., in three years) starts from that file.

The whole job on one list

  • Fault codes and fault log photographed before reset
  • Parameter backup taken (or motor nameplate photographed as fallback)
  • Terminal strip photographed, wires labelled
  • Root cause identified or honestly ruled out — fan, heatsink, surge, motor/cable (drive disconnected for insulation tests), braking resistor
  • Long-stored replacement checked for capacitor reforming requirement
  • Replacement matched on: current rating, feedback, option boards, firmware/application, STO/safety
  • First run: motor data + autotune, key parameters verified, direction checked, loaded current compared to nameplate
  • Working configuration backed up and filed

A replacement drive is the visible cost of a failure. The invisible cost is the second failure — and it is almost always preventable in the hour before the swap, with a phone camera and this list.