The Rack PC in the Control Room Is on a Clock Too: IPC647E and IPC847E Phase Out
Open the control-room door and look at the 19-inch rack, not the field devices. Somewhere in that cabinet sits the machine the whole line reports to: a SIMATIC IPC647E pulling together visualization and data logging, or its bigger brother, an IPC847E, running a server role with a shelf of expansion cards and a RAID array. These rack PCs rarely appear in spare-parts conversations, because they do not sit on the machine — they sit above it. That is exactly why their phase-out deserves attention. Siemens declared the SIMATIC IPC647E and SIMATIC IPC847E phased out on 1 October 2026, and type cancellation follows on 1 October 2027. [1] After that date, a failed rack PC is no longer a routine reorder. It is a migration project that starts on the worst possible day.
Rack PCs from the same 2019 generation
Siemens launched the IPC647E and IPC847E in February 2019 as the rack members of a new generation of high-end industrial PCs, together with the box PC IPC627E and the panel PC IPC677E. [2] The generation was built around 8th-generation Intel processors, fast onboard graphics and M.2 NVMe storage, and Siemens claimed up to 100 percent more performance than the predecessor D generation while keeping the enclosures installation-compatible with what plants already had. [2]
The two rack machines divide the cabinet by height and expansion room. The IPC647E is the 19-inch 2U unit: a compact rack PC for machine-level and control-room duties where two, or in some boards four, expansion slots are enough. The IPC847E is the 19-inch 4U unit: the same computing platform with up to eleven slots, room for larger drive arrays and the redundant power supplies that server roles in process plants are usually specified with. Both were designed for continuous operation, with temperature and fan monitoring, a watchdog and card retainers as standard parts of the product description. [3][4] In plants running SIMATIC PCS 7 or large WinCC installations, machines like these often carry the operator stations, the historian and the engineering tools in one rack — which is why a single failure can darken more than one screen.

Siemens SIMATIC IPC647E rack PC, 19-inch 2U (Siemens product image, SIOS entry 109763584)
What Siemens has scheduled
The phase-out announcement, SIOS entry 110007134, is short and specific about the two dates that govern ordering: [1]
| Milestone | Date | What it means |
|---|---|---|
| P.M400 — Phase-out announcement | 1 October 2026 | IPC647E (6AG4112-3....-....) and IPC847E (6AG4114-3....-....) remain orderable as new parts; the migration phase begins |
| P.M410 — Type cancellation | 1 October 2027 | The products are removed from active sales; new complete units are no longer the normal route |
Siemens states the reason for acting early in the same announcement: the successor platforms, the SIMATIC IPC Rx-528A and Rx-548A series, are already available — they have been deliverable since September 2025 — and are described as installation-compatible successor platforms. [1] In other words, this is not a phase-out announced ahead of a replacement. The replacement is on the shelf, and the remaining year of new-unit sales is the overlap Siemens intends plants to use.
Two machines, one platform: the numbers
Both rack PCs are configured products — the article number encodes processor, drives, memory, power supply and operating system — but the configuration envelopes come straight from Siemens data sheets. For the IPC647E, the reference is article 6AG4112-3GT12-0DX0: [3]
| IPC647E (Rack PC, 19 in, 2U) | Data sheet values |
|---|---|
| Processors | Xeon E-2278GE (8C/16T, 3.3 (4.7) GHz, 16 MB cache); Xeon E-2176G (6C/12T, 3.7 (4.7) GHz, 12 MB cache); Core i7-8700 (6C/12T, 3.2 (4.6) GHz, 12 MB cache); Core i5-8500 (6C/6T, 3.0 (4.1) GHz, 9 MB cache); Core i3-8100 (4C/4T, 3.6 GHz, 6 MB cache); Intel C246 chipset |
| Memory | 4 GB to 128 GB DDR4-2666 SDRAM DIMM, ECC optional |
| Expansion slots | 2 slots (PCIe x16 configurations) or 4 slots (PCI / PCIe mixes), modules up to 312 mm |
| Interfaces | 3x Gigabit Ethernet (RJ45); 9x USB; 2x DisplayPort, 1x DVI-D; 1x COM; audio |
| Power supply | 100/240 V AC autorange, optional redundant; 20 ms mains buffering |
| Dimensions | 430 x 88 (2U) x 444 mm |
For the IPC847E, the reference is article 6AG4114-3JC03-2FA2: [4]
| IPC847E (Rack PC, 19 in, 4U) | Data sheet values |
|---|---|
| Processors | Same processor envelope as the IPC647E, up to Xeon E-2278GE (8C/16T, 3.3 (4.7) GHz, 16 MB cache); Intel C246 chipset |
| Memory | 4 GB to 128 GB DDR4-2666 SDRAM DIMM, ECC optional |
| Expansion slots | Up to 11 slots (PCI and PCIe mixes, depending on board), modules up to 312 mm |
| Interfaces | 3x Gigabit Ethernet (RJ45); 9x USB; 2x DisplayPort, 1x DVI-D; 1x COM; audio |
| Power supply | 100/240 V AC autorange, optional redundant; 20 ms mains buffering |
| Mounting | Horizontal or vertical installation, prepared for telescopic rails; tower kit optional; approx. 17 kg |

Siemens SIMATIC IPC847E rack PC, 19-inch 4U (Siemens product image, SIOS entry 109763333)
The successors split by role, not just by size
The migration table in the announcement is the part worth reading twice, because Siemens does not map the old machines by height alone. The successor depends on the operating system role the old machine was bought for: [1]
| Installed IPC647E / IPC847E runs | Successor platform | Article number pattern |
|---|---|---|
| Windows Desktop operating system (workstation) | SIMATIC IPC RW-528A (from IPC647E) | 6AG4112-4....-.... |
| Windows Desktop operating system (workstation) | SIMATIC IPC RW-548A (from IPC847E) | 6AG4114-4....-.... |
| Windows Server operating system (server) | SIMATIC IPC RS-528A (from IPC647E) | 6AG4113-4....-.... |
| Windows Server operating system (server) | SIMATIC IPC RS-548A (from IPC847E) | 6AG4115-4....-.... |
Siemens describes the successor products as offering current hardware technology, long-term availability and flexible configuration options for workstation and server applications. [1] That is the manufacturer case. Our judgment is narrower: installation-compatible is a mechanical and platform statement, not a software guarantee. A workstation image carrying visualization projects, and a server image carrying a historian database and license services, fail migration in different places. Test the server first. It holds the most services, the oldest drivers and the cards — a legacy PCI interface card that has no place in a new slot plan ends the discussion faster than any processor comparison.
There is also a simpler option, and it expires on a fixed date: secure a configured spare of the existing machine while it is still a normal order. Downtime economics argue for it. ITIC and its 2024 survey of more than 1,000 organizations found over 90 percent estimating hourly downtime costs above $300,000 — self-reported enterprise figures that exclude litigation and penalties, but a fair indication of what a dark control room costs against the price of one configured rack PC. [5]
Frequently asked questions
Can I still order a new IPC647E or IPC847E? Yes, for now. Phase-out began on 1 October 2026 and the products remain orderable as new parts until type cancellation on 1 October 2027. [1] Record the full article number of the installed unit before ordering, because processor, drives, memory and operating system are all encoded in it.
Which successor replaces my machine? It depends on its role, not only its size. Workstation machines running Windows Desktop operating systems migrate to the RW-528A or RW-548A; server machines running Windows Server operating systems migrate to the RS-528A or RS-548A. Siemens describes the Rx-528A and Rx-548A series as installation-compatible platforms that have been available since September 2025. [1]
Should I migrate now or buy a spare? In our judgment, do both in the right order: test the successor with your most demanding image — the server first — while a spare of the existing machine can still be ordered as insurance. If you are sourcing a configured IPC647E or IPC847E spare, or checking a successor configuration against an existing rack, send us the full article number through our Siemens sourcing page or request a quote. For the box and panel members of the same generation, see our analysis of the IPC627E and IPC677E phase-out, and for what the same announcement season did to the fieldbus side, the PROFIBUS components phase-out.
Sources
[1] Siemens Industry Online Support, entry 110007134: Product phase-out announcement: SIMATIC IPC647E and SIMATIC IPC847E [2] Siemens press release, 18 February 2019: New generation of high-end industrial PCs [3] Siemens data sheet, SIMATIC IPC647E, article 6AG4112-3GT12-0DX0 (Industry Mall): data sheet PDF [4] Siemens data sheet, SIMATIC IPC847E, article 6AG4114-3JC03-2FA2 (Industry Mall): data sheet PDF [5] ITIC 2024 Hourly Cost of Downtime Report: itic-corp.com
Need help finding a part?
Send your model and quantity. Our team aims to reply promptly during office hours.