PROFIBUS Is Not Ending Tomorrow — But New Parts Have Less Than a Year Left

1 October 2026 has already passed. On that day, Siemens placed a range of PROFIBUS components into phase-out (PM400). That does not mean the bus stops tomorrow — PROFIBUS networks on the plant floor keep running as normal, and spare parts remain available as normal. But the window for new parts has started counting down: from 1 October 2027, these models will be available only through the spare-parts channel, and from 2036 even that channel closes. This article sets out three things clearly: exactly which models this phase-out covers, which components are often assumed to be on the list but are not, and what plants should do between now and 1 October 2027. Every date and model number has been checked line by line against Siemens' SIOS originals; the source links are at the end.

The timeline first

Siemens manages phase-outs with three milestones. According to SIOS entry 109989704, the schedule for this range of PROFIBUS components is:

Milestone Date What happens at this point
PM400 — Phase-out announcement 1 October 2026 Phase-out formally announced; new parts remain orderable through normal channels
PM410 — Product cancellation 1 October 2027 From here on, spare-parts supply only; no more new parts
PM490 — Discontinuation Not before 1 October 2036 No longer orderable, except supply covered by warranty

Our judgment: the date to watch is not 2036 — it is 1 October 2027. Counting from today (24 November 2026), the new-parts window has just over ten months left. Wait until after PM410 to act, and price and lead time are no longer yours to choose. Dutch distributor Batenburg's PROFIBUS phase-out risk check gives the same timeline, with a reminder worth repeating: a stock of spare parts is not a strategy, only a way of buying time.

What PROFIBUS is, and why it is still running

PROFIBUS is one of the earliest fieldbuses to see wide adoption in industrial automation. The PROFIBUS User Organization (PNO) was founded on 11 December 1989, growing out of a German government-led fieldbus project — this history is PI's (PROFIBUS & PROFINET International's) own account. More than three decades on, it is still the backbone of many plants: a single RS-485 bus at up to 12 Mbit/s tying together distributed I/O, drives, instruments and controllers. The SIOS announcement notes that the interface modules covered support up to 244 bytes of input and 244 bytes of output data per station.

Why it is still running is no mystery. In our judgment: first, the installed base is huge — replacing the PROFIBUS cabling and connectors laid through production lines, buildings, water treatment plants and car body shops means downtime. Second, it is good enough — 12 Mbit/s is ample for large volumes of digital and analog signals. Third, the ET 200 distributed I/O stations hanging on it are still very capable, and changing the bus means changing interface modules, redoing the configuration and re-testing. So when phase-out news lands, the first reaction on the plant floor is usually not panic. It is: is my model on the list?

What this phase-out actually covers

This is the section that most needs checking against the original. SIOS 109989704 is the phase-out announcement for PROFIBUS components, covering PROFIBUS interface modules of the ET 200 range and the DP/DP coupler — 13 order numbers in total. Siemens gives the corresponding PROFINET successors:

Series Phased-out model Successor (PROFINET)
ET 200AL IM 157-1 DP 6ES7157-1AA00-0AB0 IM 157-1 PN 6ES7157-1AB00-0AB0
ET 200pro IM 154-1 DP 6ES7154-1AA01-0AB0 IM 154-1 PN 6ES7154-1AB01-0AB0
ET 200pro IM 154-2 DP 6ES7154-2AA01-0AB0 IM 154-2 PN HF 6ES7154-2AB01-0AB0
ET 200SP IM 155-6 DP HF 6ES7155-6BA01-0CN0 IM 155-6 PN HF 6ES7155-6AU01-0CN0
ET 200SP SIPLUS IM 155-6 DP HF 6AG1155-6BA01-7CN0 SIPLUS IM 155-6 PN HF 6AG1155-6AU01-2CN0
ET 200MP IM 155-5 DP ST 6ES7155-5BA00-0AB0 IM 155-5 PN ST 6ES7155-5AA00-0AB0
ET 200MP SIPLUS IM 155-5 DP ST 6AG1155-5BA00-2AB0 SIPLUS IM 155-5 PN ST 6AG1155-5AA00-2AB0
Coupler DP/DP coupler 6ES7158-0AD01-0XA0 DP/PN coupler 6ES7158-3AD01-0XA0

In addition, several ET 200pro connection modules are on the list: CM IM DP ECOFAST Cu 6ES7194-4AA00-0AA0, CM IM DP Direct 6ES7194-4AC00-0AA0, CM IM DP M12 7/8 inch 6ES7194-4AD00-0AA0, CM PM-E ECOFAST 6ES7194-4BA00-0AA0, and the sealing cap 6ES7194-1JB10-0XA0. The PROFINET connection modules Siemens lists in the announcement are CM IM PN M12 7/8 inch 6ES7194-4AF00-0AA0, CM IM PN M12 7/8 inch L-coded 6ES7194-4AG00-0AA0, CM IM PN Direct 6ES7194-4AE00-0AA0 and CM PM-E PN 6ES7194-4BC00-0AA0 — match connection modules by model number against the original one by one; do not pair them by row order in a table.

Two details deserve attention. First, the ET 200AL successor IM 157-1 PN was marked, when the announcement was published, as becoming available only in the first quarter of 2026 — before scheduling a changeover, confirm its current availability. Second, order number 6ES7155-5AA00-0AB0 is the PROFINET successor of the IM 155-5, not a phased-out model — do not write the DP and PN order numbers the wrong way round.

What is not on the list matters just as much

The easiest part of this announcement to misread is its scope. The SIOS original is explicit: this announcement applies only to the PROFIBUS components listed; other PROFIBUS components are not affected.

That means: the 6ES7972 series bus connectors and the RS485 repeaters are not on the 109989704 phase-out list. If your on-site risk concentrates on connectors and repeaters, this announcement has not phased them out. But do not relax on that account — the same announcement contains one more sentence: the phase-out of the remaining PROFIBUS components will be announced separately on 1 October 2026. In other words, the connectors and repeaters have their own announcement, with the same date as this one.

And a follow-up announcement has in fact appeared. SIOS 110002640 announces that the PROFIBUS bus terminal RS485 (6GK1500-0DA00) enters phase-out (PM400) immediately, with product cancellation (PM410) set for 1 October 2026; the successor is the PROFIBUS bus terminal 12M (6GK1500-0AA10). The reason given is that the relevant components are already discontinued, with no remaining stock available. Our judgment: Siemens' PROFIBUS phase-out is not one announcement covering everything, but a main announcement plus follow-ups by product line. Watch only 109989704 and you will miss the models you actually use.

The module in numbers: IM 155-5 DP ST

Take the most representative model on the list as the example. The IM 155-5 DP ST (6ES7155-5BA00-0AB0) is the ET 200MP PROFIBUS interface module: PROFIBUS DP on one side, up to 12 S7-1500/ET 200MP I/O modules on the other. The data below comes from Siemens' official S7-1500/ET 200MP manual collection (March 2026 edition):

Figure 1: Siemens SIMATIC ET 200MP interface module IM 155-5 DP ST (6ES7155-5BA00-0AB0). Illustration from the Siemens manual; not a photograph of an actual unit.

Figure 1: Siemens SIMATIC ET 200MP interface module IM 155-5 DP ST (6ES7155-5BA00-0AB0). Illustration from the Siemens manual; not a photograph of an actual unit.

Item IM 155-5 DP ST 6ES7155-5BA00-0AB0
Interface 1 PROFIBUS DP interface, RS-485, up to 12 Mbit/s; DP slave, DPV1 supported
Address space per station Up to 244 bytes input, 244 bytes output
Modules per station Up to 12 I/O modules
Power supply 24 V DC (20.4–28.8 V), reverse-polarity protection
Current consumption Rated 0.2 A (24 V, no load), max. 1.2 A; inrush current 4 A
Power consumption Typ. 4 W; power supply to backplane bus 14 W
Electrical isolation Isolation between PROFIBUS DP and the other circuits
PROFIBUS address 1–125, set by DIP switch; package includes a 9-pin Sub-D PROFIBUS connector
Operating temperature Horizontal mounting 0–60 °C, vertical mounting 0–40 °C
Dimensions and weight 35 × 147 × 129 mm; approx. 360 g

Data source: Siemens TIA Portal information system, S7-1500/ET 200MP manual collection, IM 155-5 DP ST technical specifications page. The ET 200SP interface module of the same family, the IM 155-6 DP HF (6ES7155-6BA01-0CN0), is also on the phase-out list; its package includes the interface module, a server module and a PROFIBUS FastConnect bus connector (6ES7972-0BB70-0XA0), with the same 244-byte I/O per station.

Figure 2: Siemens SIMATIC ET 200SP interface module IM 155-6 DP HF (6ES7155-6BA01-0CN0) and server module. Illustration from the Siemens manual; not a photograph of an actual unit.

Figure 2: Siemens SIMATIC ET 200SP interface module IM 155-6 DP HF (6ES7155-6BA01-0CN0) and server module. Illustration from the Siemens manual; not a photograph of an actual unit.

What this means on the plant floor

Translating the timeline into plant-floor language:

  • Before 1 October 2027, these models remain orderable as new parts through the normal channels. Expansions, new stations and fault replacements go ahead as usual.
  • After 1 October 2027, new parts are gone; only the spare-parts channel remains. Spare-parts pricing, lead times and minimum order quantities differ from new parts — and the spare stock itself keeps shrinking as it sells.
  • After 1 October 2036 (and not before that date), even the spare-parts channel closes, with only warranty-covered supply excepted.

Our judgment: the danger point is not 2036 — it is September 2027. Many plants plan spares on an annual cycle; if the 2027 budget has no line for this, then once PM410 passes, restocking means taking your chances on the spot market. Batenburg's risk check has a line whose spirit is worth passing on: a stock of spare parts is not a strategy — it buys time, it does not replace a migration plan.

Migrating to PROFINET: how to do it on site

Siemens' route is direct: replace the DP interface modules with the corresponding PN interface modules and move the network from PROFIBUS to PROFINET. In practice, we recommend four steps:

  1. Inventory first. List every ET 200AL, ET 200pro, ET 200SP and ET 200MP station in the plant by model, and check against the table above which are on the phase-out list and which merely use PROFIBUS cabling with interface modules that are not listed. Batenburg's checklist starts with exactly this: know what you have before you talk about risk.
  2. Pilot one station. Take a non-critical ET 200SP or ET 200MP station, swap the IM 155-6 DP HF for an IM 155-6 PN HF (or the IM 155-5 DP ST for an IM 155-5 PN ST), redo the configuration, check the GSD files, verify the 244-byte address space and compatibility with the existing I/O modules, and run it for a full production cycle before rolling out.
  3. Change over in stages, inside planned shutdowns. Do not leave it to a big-bang conversion in September 2027 — spares and shutdown windows will both be tight by then. Use each planned stoppage to convert one or two stations; a DP/PN coupler (6ES7158-3AD01-0XA0) can keep legacy PROFIBUS stations connected to PROFINET during the transition.
  4. Account for spares and migration separately. Spares cover failures before 1 October 2027; migration solves the post-2027 problem. Mix the two budgets and you end up with too many spares and no money left to migrate.

Our judgment: if a line is scheduled for a major overhaul or expansion after 2028, the PN interface modules' models, quantities and budget belong in the plan now. Conversely, if a line is itself due to shut down before 2027, stocking two years of spares may be better value than migrating — but that judgment has to be made line by line, never as one answer for the whole plant.

Your checklist before the window closes

  • Against SIOS 109989704, list every model and quantity in your plant that is on the phase-out list
  • Check each model's PROFINET successor, and confirm the successor is currently available
  • Check SIOS 110002640: confirm whether the 6GK1500-0DA00 bus terminal is in use, and whether its successor 6GK1500-0AA10 is stocked
  • Confirm the announcement status of bus connectors and repeaters; do not assume they sit outside the phase-out programme
  • Plan backwards from 1 October 2027: new-part purchasing, the pilot station, shutdown windows, budget
  • Size spare quantities on two years of failure rates beyond 1 October 2027, not one year
  • Run the pilot station for a full production cycle and confirm configuration, addressing and I/O compatibility before rolling out
  • Archive this article's source links; where a model or date is in doubt, the SIOS original governs