Industrial Automation Parts. Prompt replies from real people.

ABB PST44-690-70 Softstarter

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the ABB PST44-690-70?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the ABB PST44-690-70 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
PST44-690-70
Material Number
1SFA895004R7000
Manufacturer
ABB
Product ID
90194

Get a Free Quote

Request pricing and availability for PST44-690-70.

More parts to source? Send your whole list in one enquiry

Key specifications

Product Net Weight
4.8 kg
Rated Operational Voltage
Main Circuit 400 ... 690 V AC
Rated Control Circuit Voltage (Uc)
DC Operation 24 V
Rated Frequency (f)
50/60 Hz Main Circuit 50 / 60 Hz
Rated Operational Power - In-Line Connection (Pe)
(400 V) 22 kW (500 V) 25 kW (690 V) 37 kW
Rated Operational Current - In-Line Connection (Ie)
44 A
See all specifications

Product Highlights

  1. Rated Operational Voltage: Main circuit 400 to 690 V AC at 50/60 Hz
  2. Rated Operational Current: 44 A in-line connection and 76 A inside delta connection
  3. Rated Operational Power: In-line 22 kW at 400 V, 25 kW at 500 V, 37 kW at 690 V, inside delta 37 kW at 400 V, 45 kW at 500 V, 59 kW at 690 V
  4. Starting and Overload Protection: Built-in electronic overload protection with adjustable rated motor current 30 to 115 percent, starting capacity 3xIe for 15 s, ramp time 1 to 120 s, initial voltage 30 to 70 percent, and current limit 1.5 to 7xIe
  5. Control and Monitoring: 24 V DC control circuit, fieldbus plug, run, bypass, fault, and overload signal relays, analog outputs 0 to 10 V, 0 to 20 mA, and 4 to 20 mA, and green, yellow, and red status LEDs
  6. Terminals and Protection: Screw terminals with main circuit capacity 1 x 10 to 95 mm² or 2 x 6 to 35 mm², control and supply circuit capacity 1 x 2.5 mm² or 2 x 1.5 mm², tightening torque 6 N·m main and 0.5 N·m control and supply, and IP10 main terminals
  7. Dimensions and Operating Conditions: 160 mm width, 260 mm height, 196 mm depth, 4.8 kg weight, and ambient air temperature 0 to +50 °C operation and -25 to +70 °C storage
PST44-690-70

Product Information

Technical Specifications

Specifications for PST44-690-70

ParameterValue
Product Net Width160 mm
Product Net Height260 mm
Product Net Depth / Length196 mm
Product Net Weight4.8 kg
Rated Operational VoltageMain Circuit 400 ... 690 V AC
Rated Control Circuit Voltage (Uc)DC Operation 24 V
Rated Frequency (f)50/60 Hz Main Circuit 50 / 60 Hz
Rated Operational Power - In-Line Connection (Pe)(400 V) 22 kW (500 V) 25 kW (690 V) 37 kW
Rated Operational Current - In-Line Connection (Ie)44 A
Rated Operational Power - Inside Delta Connectionat 400 V 37 kW at 500 V 45 kW at 690 V 59 kW
Rated Operational Current - Inside Delta Connection76 A
Service Factor Percentage115 %
Overload ProtectionBuild-in electronic overload protection
Integrated Electronic OverloadYes
Adjustable Rated Motor Current Ie30 ... 115 %
Starting Capacity at Maximum Rated Current Ie3xIe for 15s
Ramp Time0 ... 120 second [unit of time] 1 ... 120 second [unit of time]
Initial Voltage During Start30 ... 70 %
Step Down Voltage Special Ramp100 ... 30 %
Current Limit Function1.5 ... 7xIe
Switch for Inside Delta ConnectionYes
ParameterValue
Run Signal RelayYes
By-pass Signal RelayYes
Fault Signal RelayYes
Overload Signal RelayYes
Analog Outputs0…10 volts 0…20 mA 4…20 mA
Signal Indication Ready to Start/Standby ON (LED)Green
Signal Indication Protection (LED)Yellow
Signal Indication Fault (LED)Red
Number of Starts Per Hour at 3.5*Ie for 7 sec. 50% ON Time 50% OFF Time30
CommunicationFiledBusPlug(Standard)
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Terminal TypeScrew Terminals
Connecting Capacity Main CircuitRigid 1 x 10 ... 95 mm² Rigid 2 x 6 ... 35 mm²
Connecting Capacity Control CircuitRigid 1 x 2.5 mm² Rigid 2 x 1.5 mm²
Connecting Capacity Supply CircuitRigid 1 x 2.5 mm²
Tightening TorqueControl Circuit 0.5 N·m Main Circuit 6 N·m Supply Circuit 0.5 N·m
Product Main TypePST44
Ambient Air TemperatureOperation 0 ... +50 °C Storage -25 ... +70 °C
Object Classification CodeQ
ETIM 7EC000640 - Soft starter
ETIM 8EC000640 - Soft starter
ETIM 9EC000640 - Soft starter
eClassV11.0 : 27370907
UNSPSC39121521
Manufacturer ID1SFA895004R7000

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp