Industrial Automation Parts. Prompt replies from real people.

ABB NFC44E-86 Efficient and Reliable Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the ABB NFC44E-86?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the ABB NFC44E-86 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
NFC44E-86
Material Number
1SBH131001R8644
Manufacturer
ABB
Product ID
89254

Get a Free Quote

Request pricing and availability for NFC44E-86.

More parts to source? Send your whole list in one enquiry

Key specifications

Product Net Weight
0.351 kg
Rated Operational Voltage
Auxiliary Circuit 690 V Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz
Rated Operational Current AC-15 (Ie)
(500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (400 / 440 V) 3 A
Rated Short-time Withstand Current Low Voltage (Icw)
for 0.1 s 140 A for 1 s 100 A
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
See all specifications

Product Highlights

  1. Contact Configuration: 4 NO and 4 NC auxiliary contacts with no main contacts
  2. Coil and Switching Ratings: 400 to 415 V at 50 Hz or 415 to 440 V at 60 Hz coil, 2.3 W coil consumption, up to 6000 mechanical cycles per hour and 1200 AC-15 electrical cycles per hour
  3. Current Ratings: 16 A conventional free-air thermal current at 40 °C, AC-15 ratings from 2 A at 690 V to 6 A at 24 or 127 V, and DC-13 ratings from 6 A at 24 V to 0.1 A at 600 V
  4. Termination and Mounting: Screw terminals with 10 mm stripping length, 0.75 to 2.5 mm² connecting capacity, 11 in·lb tightening torque, and DIN rail or diagonal M4 screw mounting
  5. Operating Conditions and Standards: -40 to 70 °C ambient operation, 3000 m maximum altitude without derating, and compliance with IEC/EN 60947-1, IEC/EN 60947-5-1, UL 60947-1, UL 60947-5-1, CSA C22.2 No. 60947-1-13, and CSA C22.2 No. 60947-5-1-14
NFC44E-86

Product Information

Technical Specifications

Specifications for NFC44E-86

ParameterValue
Product Net Width45 mm
Product Net Depth / Length110.5 mm
Product Net Height86 mm
Product Net Weight0.351 kg
Number of Main Contacts NO0
Number of Main Contacts NC0
Number of Auxiliary Contacts NO4
Number of Auxiliary Contacts NC4
StandardsIEC/EN 60947-1, IEC/EN 60947-5-1, UL 60947-1, UL 60947-5-1, CSA C22.2 No. 60947-1-13, CSA C22.2 No. 60947-5-1-14
Rated Operational VoltageAuxiliary Circuit 690 V Main Circuit 690 V
Rated Frequency (f)Auxiliary Circuit 5060 Hz Main Circuit 5060 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-15 (Ie)(500 V) 2 A (690 V) 2 A (24127 V) 6 A (220240 V) 4 A (400440 V) 3 A
Rated Short-time Withstand Current Low Voltage (Icw)for 0.1 s 140 A for 1 s 100 A
Maximum Electrical Switching Frequency(AC-1) 0 cycles per hour (AC-15) 1200 cycles per hour (AC-2 / AC-4) 0 cycles per hour (AC-3) 0 cycles per hour (DC-13) 900 cycles per hour
Rated Operational Current DC-13 (Ie)(24 V) 6 A144 W (48 V) 2.8 A134 W (72 V) 1 A72 W (110 V) 0.55 A60 W (125 V) 0.55 A69 W (220 V) 0.27 A60 W (250 V) 0.27 A68 W (400 V) 0.15 A60 W (500 V) 0.13 A65 W (600 V) 0.1 A60 W
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)6 kV Auxiliary Circuit 6 kV
Maximum Mechanical Switching Frequency6000 cycles per hour
Rated Control Circuit Voltage (Uc)50 Hz 400 ... 415 V 60 Hz 415 ... 440 V
ParameterValue
Coil Consumption2.3 W
Operate TimeBetween Coil De-energization and NC Contact Closing 9 ... 20 ms Between Coil De-energization and NO Contact Opening 4 ... 18 ms Between Coil Energization and NC Contact Opening 7 ... 21 ms Between Coil Energization and NO Contact Closing 10 ... 26 ms
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)2 x M4 screws placed diagonally
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping LengthAuxiliary Circuit 10 mm Control Circuit 10 mm
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Terminal TypeScrew Terminals
Tightening Torque UL/CSAAuxiliary Circuit 11 in·lb Control Circuit 11 in·lb
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C Close to Contactor without Thermal O/L Relay -40 ... 70 °C Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air -40 ... 70 °C Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +60 °C Near Contactor for Operation in Free Air (Uc) -40 ... 70 °C
Climatic WithstandCategory B according to IEC 60947-1 Annex Q
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27Closed, Shock Direction: B1 25 g Open, Shock Direction: B1 5 g Shock Direction: A 30 g Shock Direction: B2 15 g Shock Direction: C1 25 g Shock Direction: C2 25 g
Resistance to Vibrations4g Closed Position & 2g Open position 5 ... 300 Hz
Object Classification CodeK
ETIM 7EC000196 - Contactor relay
ETIM 8EC000196 - Contactor relay
ETIM 9EC000196 - Contactor relay
eClassV11.0 : 27371001
UNSPSC39121500
IDEA Granular Category Code (IGCC)4755 >> Contactors
Manufacturer ID1SBH131001R8644

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp