Industrial Automation Parts. Prompt replies from real people.

ABB AF400-30-00-70 3-Pole Non-Reversing Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the ABB AF400-30-00-70?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the ABB AF400-30-00-70 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
AF400-30-00-70
Material Number
1SFL577001R7000
Manufacturer
ABB
Product ID
88193

Get a Free Quote

Request pricing and availability for AF400-30-00-70.

More parts to source? Send your whole list in one enquiry

Key specifications

Product Net Weight
10.6 kg
Rated Operational Voltage
Main Circuit 1000 V
Rated Operational Current AC-1 (Ie)
(1000 V) 40 °C 600 A (1000 V) 55 °C 500 A (1000 V) 70 °C 400 A (690 V) 40 °C 600 A (690 V) 55 °C 500 A (690 V) 60 °C 500 A (690 V) 70 °C 400 A
Rated Operational Power AC-3 (Pe)
(415 V) 220 kW (440 V) 220 kW (500 V) 250 kW (690 V) 315 kW (1000 V) 220 kW (380 / 400 V) 200 kW (220 / 230 / 240 V) 110 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 4400 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 840 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 2500 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 4600 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 3100 A
Maximum Electrical Switching Frequency
300 cycles per hour
See all specifications

Product Highlights

  1. Control Voltage: Rated control circuit voltage is 100 to 250 V at 50 Hz
  2. Main Contacts: 3 normally open main contacts with no normally open or normally closed auxiliary contacts
  3. Current Ratings: AC-1 rated operational current is 600 A at 40 °C and 400 A at 70 °C, while AC-3 rated operational current is 400 A at 415 V and 155 A at 1000 V
  4. Power Ratings: AC-3 rated operational power is 200 kW at 380/400 V, 220 kW at 415 V, 250 kW at 500 V, and 315 kW at 690 V
  5. Short-time Withstand: Rated short-time withstand current at 40 °C in free air from a cold state is 4600 A for 1 s, 4400 A for 10 s, 3100 A for 30 s, 2500 A for 1 min, and 840 A for 15 min
AF400-30-00-70

Product Information

Technical Specifications

Specifications for AF400-30-00-70

ParameterValue
Product Net Width186 mm
Product Net Depth / Length216 mm
Product Net Height278 mm
Product Net Weight10.6 kg
Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC0
Rated Operational VoltageMain Circuit 1000 V
Rated Operational Current AC-1 (Ie)(1000 V) 40 °C 600 A (1000 V) 55 °C 500 A (1000 V) 70 °C 400 A (690 V) 40 °C 600 A (690 V) 55 °C 500 A (690 V) 60 °C 500 A (690 V) 70 °C 400 A
Rated Operational Current AC-3 (Ie)(415 V) 55 °C 400 A (440 V) 55 °C 400 A (500 V) 55 °C 400 A (690 V) 55 °C 350 A (1000 V) 55 °C 155 A (380400 V) 55 °C 400 A (220230240 V) 55 °C 400 A
Rated Operational Power AC-3 (Pe)(415 V) 220 kW (440 V) 220 kW (500 V) 250 kW (690 V) 315 kW (1000 V) 220 kW (380400 V) 200 kW (220230240 V) 110 kW
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 4400 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 840 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 2500 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 4600 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 3100 A
ParameterValue
Maximum Electrical Switching Frequency300 cycles per hour
Mechanical Durability3 million
Maximum Mechanical Switching Frequency300 cycles per hour
Rated Control Circuit Voltage (Uc)50 Hz 100 ... 250 V
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A Pull-in at Max. Rated Control Circuit Voltage 50 Hz 955 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 955 V·A Pull-in at Max. Rated Control Circuit Voltage DC 895 V·A
Terminal TypeMain Circuit: Bars
Maximum Operating Voltage UL/CSAMain Circuit 1000 V
Horsepower Rating UL/CSA(200 ... 208 V AC) Three Phase 125 Hp (220 ... 240 V AC) Three Phase 150 Hp (440 ... 480 V AC) Three Phase 350 Hp (550 ... 600 V AC) Three Phase 400 Hp
Object Classification CodeQ
ETIM 7EC000066 - Power contactor, AC switching
ETIM 8EC000066 - Power contactor, AC switching
ETIM 9EC000066 - Power contactor, AC switching
eClassV11.0 : 27371003
UNSPSC39121529
IDEA Granular Category Code (IGCC)4755 >> Contactors
Manufacturer ID1SFL577001R7000

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp
ABB AF400-30-00-70 3-Pole Non-Reversing Contactor | 100-250VAC/DC