Product Model
OT40F3
Material Number
1SCA104902R1001
Manufacturer
ABB
Product ID
85405

Get a Free Quote

Request pricing and availability for OT40F3.

More parts to source? Send your whole list in one enquiry

Key specifications

Degree of Protection
Front IP20
Product Net Weight
0.09 kg
Rated Conditional Short-Circuit Current (Inc)
(40 A fuse, ≤415V) 50 kA (25 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 750 V
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 5.5 kW (400 ... 415 V) 11 kW (500 V) 11 kW (690 V) 11 kW
See all specifications

Product Highlights

  1. Electrical Ratings: 3-pole switch-disconnector rated 40 A, 750 V insulation voltage, 8 kV impulse withstand, and 50 kA conditional short-circuit current with a 40 A fuse at up to 415 V
  2. Operating Capability: AC-21A and AC-22A ratings of 40 A at 380 to 690 V, AC-23A ratings of 23 A at 380 to 500 V and 12 A at 690 V, and AC-23A power ratings up to 11 kW
  3. Connection and Mounting: Screw terminals accept Cu conductors from 0.75 to 10 mm², require 9 to 10 mm stripping length and 0.8 N·m tightening torque, and the switch is base mounted with top or bottom line terminals
  4. Construction and Durability: Front-operated mechanism with knob handle and shaft not included, 20,000 mechanical operations, 1.6 W power loss per pole at rated conditions, and front IP20 protection
  5. Dimensions and Standards: 35 mm wide, 68 mm high, 56 mm deep, 0.09 kg, compliant with IEC 60947-3, UL 508, and CSA C22.2 No. 14, with UL/CSA ratings up to 600 V and 40 A
OT40F3

Product Information

Technical Specifications

Specifications for OT40F3

ParameterValue
Degree of ProtectionFront IP20
Environmental Information1SCC301262D0201
Pollution Degree3
Product Net Width35 mm
Product Net Height68 mm
Product Net Depth / Length56 mm
Product Net Weight0.09 kg
Cable Cross-SectionCu 0.75 ... 10 mm²
Connecting Capacity Main CircuitFlexible with Ferrule 1x Cu 0.75…4 mm² Solid 1x Cu 0.75…6 mm² Flexible 1x Cu 0.75…10 mm² Stranded 1x Cu 0.75…10 mm²
Conventional Free-air Thermal Current (Ith)Θ = 40 °C 40 A
Conventional Thermal Current (Ithe)Fully Enclosed 40 A
Degree of ProtectionFront IP20
Distance Between PhasesStandard
Handle TypeKnob Handle and shaft not included
Lock TypeNo
Mechanical Durability20000
Mounting TypeBase mounting
Number of Poles3P
Operating ModeFront operated
Pollution Degree3
Position of Line TerminalsTop In - Bottom Out Bottom In - Top Out
Power Lossat Rated Operating Conditions per Pole 1.6 W
Rated Conditional Short-Circuit Current (Inc)(40 A fuse, ≤415V) 50 kA (25 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-21A (Ie)(380 ... 415 V) 40 A (500 V) 40 A (690 V) 40 A
Rated Operational Current AC-22A (Ie)(380 ... 415 V) 40 A (500 V) 40 A (690 V) 40 A
Rated Operational Current AC-23A (Ie)(380 ... 415 V) 23 A (500 V) 23 A (690 V) 12 A
Rated Operational Power AC-23A (Pe)(220 ... 240 V) 5.5 kW (400 ... 415 V) 11 kW (500 V) 11 kW (690 V) 11 kW
ParameterValue
Rated Operational VoltageMain Circuit 750 V
Rated Short-Circuit Making Capacity (Icm)(690 V) 0.71 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 0.5 kA
Recommended Screw DriverMain Circuit Pozidriv 2
Special FunctionsNo
StandardsIEC 60947-3UL 508CSA C22.2 No. 14
Switches Operating MechanismMechanism on Top of the Switch
Terminal TypeScrew Terminals
Tightening Torqueacc. IEC 60947-1 0.8 N·m
Wire Stripping LengthMain Circuit 9-10 mm
Maximum Operating Voltage UL/CSA600 V
Ampere Rating40 A
Horsepower Rating UL/CSA(110 ... 120 V AC) Single Phase 2 Hp (240 V AC) Single Phase 5 Hp (440 ... 480 V AC) Single Phase 10 Hp (550 ... 600 V AC) Single Phase 15 Hp (220 ... 240 V AC) Three Phase 10 Hp (440 ... 480 V AC) Three Phase 20 Hp (550 ... 600 V AC) Three Phase 25 Hp
Wire Stripping LengthMain Circuit 9-10 mm
Recommended Screw DriverMain Circuit Pozidriv 2
Tightening Torqueacc. IEC 60947-1 0.8 N·m
Tightening Torque UL/CSA7 in·lb
Object Classification CodeQ
ETIM 8EC000216 - Switch disconnector
ETIM 9EC000216 - Switch disconnector (low voltage)
UNSPSC39122233
IDEA Granular Category Code (IGCC)5290 >> Disconnect switch
eClassV11.1 : 27371403
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)3601438
E-Number (Norway)4363524
E-Number (Sweden)3170939
Manufacturer ID1SCA104902R1001

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.