- CA5-04U
ABB auxiliary contact block, model CA5-04U, manufacturer ID 1SBN010040R1304. It provides four normally closed (NC) auxiliary contacts and no normally open (NO) contacts. Auxiliary circuit ratings: 690 V operational voltage at 50/60 Hz; AC-15 rated operational current 6 A at 24/127 V, 4 A at 220/240 V, 3 A at 380/400 V, and 2 A at 500 V and 690 V; DC-13 ratings include 6 A / 144 W at 24 V and 0.3 A / 75 W at 250 V. Rated short-time withstand current is 140 A for 0.1 s and 100 A for 1 s. Rated insulation voltage is 690 V per IEC 60947-5-1 and 600 V per UL/CSA. Auxiliary terminals are IP20 per IEC 60529, IEC 60947-1, and EN 60529. Screw terminals. Dimensions: 43 mm width, 39 mm depth, 47 mm height; 0.06 kg.
- CA5-10
ABB CA5-10 auxiliary contact block, manufacturer ID 1SBN010010W1010. It provides one normally open (NO) auxiliary contact and no normally closed (NC) contacts, with screw terminals and IP20 protection on the auxiliary terminals according to IEC 60529, IEC 60947-1, and EN 60529. Rated operational voltage for the auxiliary circuit is 690 V at 50/60 Hz. Rated operational current AC-15 is 6 A at 24/127 V, 4 A at 220/240 V, 3 A at 380/400 V, and 2 A at 500 V and 690 V. DC-13 ratings include 6 A / 144 W at 24 V and 0.30 A / 66 W at 220 V. Dimensions are 11 mm wide, 32.5 mm deep, and 47 mm high; net weight 0.014 kg.
- CA5-10-AU FASTON
The ABB CA5-10-AU FASTON is a 1-pole front-mounted auxiliary contact block with one normally open (NO) auxiliary contact and no normally closed (NC) contacts. It uses flat-pin (FASTON) connections. Dimensions are 11 mm wide, 32.5 mm deep, and 47 mm high, with a net weight of 0.02 kg. The auxiliary circuit is rated 690 V at 50/60 Hz. Rated insulation voltage is 690 V according to IEC 60947-5-1 and 600 V according to UL/CSA. Rated short-time withstand current is 140 A for 0.1 s and 100 A for 1 s. It is suitable for contactors A9, A12, A16, A26, A30, A40, A45, A50, A63, A75, A95, A110, AL9, AL12, AL16, AL26, AL30, AL40, AE45, AE50, AE63, AE75, TAL9, TAL12, TAL16, TAL26, TAL30, TAL40, TAE45, TAE50, and TAE75. Manufacturer ID: 1SBN010014R9001.
- CA5-11/11E
ABB auxiliary contact block CA5-11/11E, manufacturer ID 1SBN010040R1018. It provides two normally open and two normally closed auxiliary contacts with screw terminals. Rated operational voltage for the auxiliary circuit is 690 V at 50/60 Hz. Rated operational current AC-15 is 6 A at 24/127 V, 4 A at 220/240 V, 3 A at 380/400 V, and 2 A at 500 V and 690 V. DC-13 ratings include 6 A / 144 W at 24 V and 0.30 A / 66 W at 220 V. Rated insulation voltage is 690 V according to IEC 60947-5-1 and 600 V according to UL/CSA. Short-circuit protection uses gG type fuses rated 10 A. Dimensions are 43 mm width, 39 mm depth, 47 mm height, and 0.06 kg net weight. Auxiliary terminals have IP20 protection according to IEC 60529, IEC 60947-1, and EN 60529.
- CA5-11/11M
ABB CA5-11/11M auxiliary contact block, manufacturer ID 1SBN010040R1118. It provides 2 normally open and 2 normally closed auxiliary contacts with screw terminals. Rated operational voltage for the auxiliary circuit is 690 V at 50/60 Hz. Rated operational current AC-15 is 6 A at 24/127 V, 4 A at 220/240 V, 3 A at 380/400 V, and 2 A at 500 V and 690 V. DC-13 ratings include 6 A / 144 W at 24 V and 0.3 A / 75 W at 250 V. Rated insulation voltage is 690 V per IEC 60947-5-1 and 600 V per UL/CSA. Dimensions are 43 mm width, 39 mm depth, 47 mm height, 0.06 kg. Mechanical durability is 10 million operations.
- CA5-13M
The ABB CA5-13M is a front-mounted auxiliary contact block with screw terminals. It provides 1 normally open (NO) and 3 normally closed (NC) auxiliary contacts. Rated operational voltage for the auxiliary circuit is 690 V at 50/60 Hz. Rated operational current AC-15 is 6 A at 24/127 V, 4 A at 220/240 V, 3 A at 380/400 V, and 2 A at 500 V and 690 V. Rated operational current DC-13 is 6 A / 144 W at 24 V and 0.3 A / 75 W at 250 V. Rated insulation voltage is 690 V according to IEC 60947-5-1 and 600 V according to UL/CSA. Auxiliary terminals offer IP20 protection according to IEC 60529, IEC 60947-1, and EN 60529. Net dimensions are 43 mm width, 39 mm depth, and 47 mm height; net weight is 0.06 kg.
- CA5-13N
ABB CA5-13N auxiliary contact block, manufacturer ID 1SBN010040R1213. It provides 1 normally open and 3 normally closed auxiliary contacts with screw terminals. Rated operational voltage for the auxiliary circuit is 690 V at 50/60 Hz. Rated operational current AC-15 is 6 A at 24/127 V, 4 A at 220/240 V, 3 A at 380/400 V, and 2 A at 500 V and 690 V. DC-13 ratings include 6 A / 144 W at 24 V and 0.30 A / 66 W at 220 V. Rated insulation voltage is 690 V according to IEC 60947-5-1 and 600 V according to UL/CSA. Dimensions are 43 mm width, 39 mm depth, 47 mm height, and 0.06 kg net weight. Auxiliary terminals have IP20 protection according to IEC 60529, IEC 60947-1, and EN 60529. Suitable for N22E, N31E, N40E, NL22E, NL31E, NL40E, TNL22E, TNL31E, and TNL40E.
- CA5-22E
ABB CA5-22E auxiliary contact block, manufacturer ID 1SBN010040R1022. It provides 2 normally open and 2 normally closed auxiliary contacts with screw terminals. Dimensions are 44 mm width, 39 mm depth, and 47 mm height; net weight 0.06 kg. The auxiliary circuit is rated 690 V at 50/60 Hz. Rated operational current AC-15 is 6 A at 24/127 V, 4 A at 220/240 V, 3 A at 380/400 V, and 2 A at 500 V and 690 V. DC-13 ratings include 6 A / 144 W at 24 V and 0.30 A / 66 W at 220 V. Rated insulation voltage is 690 V per IEC 60947-5-1 and 600 V per UL/CSA. Auxiliary terminals are IP20 per IEC 60529, IEC 60947-1, and EN 60529. Maximum electrical switching frequency is 1200 cycles per hour; maximum mechanical switching frequency is 3600 cycles per hour.