Product Model
OVR T2 40-320 C U
Material Number
2CTB802348R3700
Manufacturer
ABB
Product ID
77148

Get a Free Quote

Request pricing and availability for OVR T2 40-320 C U.

More parts to source? Send your whole list in one enquiry

Key specifications

Rated Voltage (Ur)
277 V AC
Nominal AC Voltage of the System (Uo)
277 V
Voltage Protection Level ( Up)
1.2 kV (L-N) 1.2 kV
Number of Protected Poles
1
Product Net Weight
50 g
See all specifications

Product Highlights

  1. Standards and Class: Complies with UL 1449 Ed3 and is a Class II arrester
  2. Electrical Ratings: 277 V AC rated voltage, 320 V maximum continuous operating voltage (L-PE), and 1.2 kV voltage protection level (L-N)
  3. Surge Current Capacity: 20 kA nominal and 40 kA maximum discharge current (8/20 µs), with 100 kA rated short-circuit breaking capacity and 200 kA short-circuit withstand
  4. Configuration and Mounting: Single-pole, single-conductor plug-in design with replacement cartridge, DIN-rail mounting, and 1 modular spacing (17.6 mm wide)
  5. Physical and Environmental: IP20 degree of protection and maximum operating altitude of 5000 m without derating
OVR T2 40-320 C U

Product Information

Technical Specifications

Specifications for OVR T2 40-320 C U

ParameterValue
StandardsUL 1449 Ed3
Suitable ForTo protect the systems against the transient overvoltage (lightning)
Rated Voltage (Ur)277 V AC
Nominal AC Voltage of the System (Uo)277 V
Voltage Protection Level ( Up)1.2 kV (L-N) 1.2 kV
Maximum Continuous Operating Voltage (Uc)(L-PE) 320 V
Rated Service Short-Circuit Breaking Capacity (Ics)100 kA
Discharge CurrentNominal (820 µs) 20 kA I (max, 820 µs) 40 kA
Short Circuit Withstand Icc200 kA
Arrester ClassII
Number of Protected Poles1
Number of Poles1
Number of Conductors1
Transmission StandardOptic
VersionPlug-in
Mounting TypeDIN-Rail
Options ProvidedReplacement Cartridge
Preventive Maintenance FeatureNo
Status IndicatorYes
Fuse Size4 modular spacing
ParameterValue
Degree of ProtectionIP20
Maximum Operating Altitude PermissibleWithout Derating 5000
Maximum Continuous Operating Voltage UL/CSA (MCOV)(L-PE) 350 V (L-L) 350 V (L-N) 350 V (N-PE) - V
Maximum Operating Voltage UL/CSA320 V
Type of Low Voltage Distribution System UL/CSASingle Phase
Width in Number of Modular Spacings1
Product Net Width17.6 mm
Product Net Height57 mm
Product Net Depth / Length55.6 mm
Product Net Weight50 g
ETIM 8EC000941 - Surge protection device for power supply systems
ETIM 9EC000941 - Surge protection device for power supply systems
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2BBusiness To Business
CN885363090
UNSPSC39121610
eClassV11.0 : 27130805
IDEA Granular Category Code (IGCC)4906 >> Surge suppressers
Object Classification Code141DDC
Manufacturer ID2CTB802348R3700

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp