Industrial Automation Parts. Prompt replies from real people.

ABB OS1250D03N3 High-Voltage Switchgear

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/24/2026

Q1Can you supply the ABB OS1250D03N3?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the ABB OS1250D03N3 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
OS1250D03N3
Material Number
1SCA114761R1001
Manufacturer
ABB
Product ID
75931

Get a Free Quote

Request pricing and availability for OS1250D03N3.

More parts to source? Send your whole list in one enquiry

Key specifications

Product Net Weight
28.2 kg
Number of Poles
3+N
Rated Conditional Short-Circuit Current (Inc)
(690 V) 80 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 315 kW (400 V) 560 kW (415 V) 560 kW (500 V) 710 kW (690 V) 1000 kW
See all specifications

Product Highlights

  1. Electrical Ratings: 1250 A rated current in the main circuit, 1000 V rated insulation voltage, 12 kV rated impulse withstand voltage, and 690 V AC rated operational voltage
  2. Switching and Short-Circuit Performance: Rated conditional short-circuit current of 80 kA at 690 V, 40 kA rms short-time withstand current for 1 s, and AC-21A/AC-21B operational current of 1250 A at 380 to 690 V
  3. Fuse and Pole Configuration: NH4 DIN fuse system, 3+N poles with a detachable neutral link integrated into the mechanism, and front-operated mechanism on the left side
  4. Terminations and Mounting: Lug terminals 50 mm wide with 50 to 75 N·m tightening torque, cable cross-section 2.5 to 25 mm², and base mounting
  5. Physical and Environmental Data: 294 mm width, 429 mm height, 356 mm depth, 28.2 kg net weight, pollution degree 3, and 75 W power loss per pole at rated operating conditions
  6. Compliance: IEC 60947-3
OS1250D03N3

Product Information

Technical Specifications

Specifications for OS1250D03N3

ParameterValue
Pollution Degree3
Product Net Width294 mm
Product Net Height429 mm
Product Net Depth / Length356 mm
Product Net Weight28.2 kg
Cable Cross-Section2.5 ... 25 mm²
Conventional Free-air Thermal Current (Ith)Θ = 40 °C 1250 A
Conventional Thermal Current (Ithe)Fully Enclosed 1000 A
Fourth Pole TypeDetachable Neutral Link Integrated Into the Mechanism
Fuse SizeNH4
Fuse SystemDIN
Handle TypeHandle and shaft not included
Mounting TypeBase mounting
Number of Poles3+N
Operating ModeFront Operated
Pollution Degree3
Position of Line TerminalsTop In - Bottom Out Bottom In - Top Out
Power Lossat Rated Operating Conditions per Pole 75 W
Rated Conditional Short-Circuit Current (Inc)(690 V) 80 kA
Rated Current (In)Main Circuit 1250 A
Rated Impulse Withstand Voltage (Uimp)12 kV
Rated Insulation Voltage (Ui)1000 V
Rated Operational Current AC-21A (Ie)(380 ... 415 V) 1250 A (500 V) 1250 A (690 V) 1250 A
Rated Operational Current AC-21B (Ie)(500 V) 1250 A (690 V) 1250 A
ParameterValue
Rated Operational Current AC-22A (Ie)(380 ... 415 V) 1250 A
Rated Operational Current AC-22B (Ie)(500 V) 1250 A (690 V) 1250 A
Rated Operational Current AC-23A (Ie)(380 ... 415 V) 1000 A
Rated Operational Current AC-23B (Ie)(500 V) 1000 A (690 V) 1000 A
Rated Operational Power AC-23A (Pe)(220 ... 240 V) 315 kW (400 V) 560 kW (415 V) 560 kW (500 V) 710 kW (690 V) 1000 kW
Rated Operational VoltageMain Circuit 690 V AC
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 40 kiloampere rms
Special FunctionsDetachable Neutral
StandardsIEC 60947-3
Switches Operating Mechanism03 (Left Side)
Terminal TypeLug terminals
Terminal Width50 mm
Tightening Torque50 ... 75 N·m
Tightening Torque50 ... 75 N·m
Object Classification CodeQ
ETIM 8EC001040 - Fuse switch disconnector
ETIM 9EC001040 - Fuse switch disconnector
UNSPSC39122233
IDEA Granular Category Code (IGCC)5291 >> Fuse switch disconnector
eClassV11.1 : 27371401
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID1SCA114761R1001

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.