- OS250D12BB
ABB fuse switch disconnector, model OS250D12BB, manufacturer ID 1SCA102202R1001. Three-pole, front-operated, base-mounting unit with back-in/back-out line terminals and lug terminals 25 mm wide. Rated current 250 A in the main circuit; conventional free-air thermal current 250 A at 40 °C and conventional thermal current 250 A fully enclosed. Rated operational voltage 690 V AC; rated insulation voltage 1000 V; rated impulse withstand voltage 12 kV. Rated conditional short-circuit current 80 kA at 690 V; rated short-time withstand current 8 kA rms for 1 s. Power loss 13 W per pole at rated operating conditions. Accepts NH0 and NH1 DIN fuse sizes. Pollution degree 3. Tightening torque 30 to 44 N·m. Standards: IEC 60947-3. Handle and shaft not included. Net dimensions 206 x 193 x 189 mm; net weight 3.03 kg.
- OS250D12K
ABB OS250D12K fuse protector, manufacturer ID 1SCA137659R1001. Three-pole front-operated fuse switch disconnector for DIN fuse systems in NH0 and NH1 sizes, base mounting with lug terminals 25 mm wide. Rated current 250 A; conventional free-air thermal current 250 A at 40 °C; fully enclosed thermal current 250 A. Rated operational voltage 690 V AC; rated insulation voltage 1000 V; rated impulse withstand voltage 12 kV. Rated conditional short-circuit current 80 kA at 690 V; short-time withstand current 8 kA rms for 1 s. Power loss 13 W per pole at rated operating conditions. Direct mounted handle. Pollution degree 3. Dimensions 310 mm wide, 270 mm high, 200 mm deep; net weight 4 kg. Standards: IEC 60947-3.
- OS250D12LR
ABB OS250D12LR fuse switch disconnector, base mounting, front operated, 3 poles, line terminals left in and right out. Rated current 250 A; rated operational voltage 690 V AC; rated insulation voltage 1000 V; rated impulse withstand voltage 12 kV. Conventional free-air thermal current 250 A at 40 °C; conventional thermal current 315 A fully enclosed. Rated conditional short-circuit current 80 kA at 690 V; rated short-time withstand current 8 kA rms for 1 s. Accepts NH0 and NH1 DIN fuse sizes. Lug terminals, 25 mm width, tightening torque 30 to 44 N·m. Power loss 17 W per pole at rated operating conditions. Pollution degree 3. Dimensions 297 mm width, 150 mm height, 218 mm depth; net weight 5.2 kg. Conforms to IEC 60947-3. Handle and shaft not included.
- OS250D12LRP
ABB fuse protector OS250D12LRP, manufacturer ID 1SCA022852R8410, is a three-pole front-operated fuse switch disconnector for base mounting. It accepts NH0 and NH1 DIN fuse sizes and is rated 250 A in the main circuit, with conventional free-air thermal current 250 A at 40 °C and fully enclosed thermal current 250 A. Rated operational voltage is 690 V AC; rated insulation voltage 1000 V; rated impulse withstand voltage 12 kV; rated conditional short-circuit current 80 kA at 690 V; rated short-time withstand current 8 kA rms for 1 s. Line terminals are left in, right out. Lug terminals are 25 mm wide, tightening torque 30 to 44 N·m. Dimensions are 353 mm wide, 150 mm high, 234 mm deep; net weight 6.1 kg. Standards: IEC 60947-3.
- OS250D12M1P
ABB fuse protector, model OS250D12M1P, manufacturer ID 1SCA022746R5530. Three-pole, front-operated fuse switch disconnector for base mounting, rated current 250 A in the main circuit. Rated operational voltage 690 V AC; rated insulation voltage 1000 V; rated impulse withstand voltage 12 kV. Conventional free-air thermal current 250 A at 40 °C; conventional thermal current 250 A fully enclosed. Rated conditional short-circuit current 80 kA at 690 V, and rated short-time withstand current 8 kA rms for 1 s. Accepts NH0 and NH1 DIN fuse sizes. Lug terminals, 25 mm terminal width, tightening torque 30 to 44 N·m. Power loss 13 W per pole at rated operating conditions. Pollution degree 3. Standards: IEC 60947-3. Dimensions 206 mm wide, 199 mm high, 154 mm deep; net weight 3.6 kg.
- OS250D13N2
The ABB OS250D13N2 is a four-pole fuse protector supplied with a front-operated handle and shaft. It accepts NH0 and NH1 fuses in the DIN fuse system and mounts on a base. The main circuit is rated 690 V AC, and power loss is 13 W per pole at rated operating conditions. Terminals are lug type, tightened to 30 to 44 N·m. Dimensions are 154 mm wide, 269 mm high, and 193 mm deep, with a net weight of 4.2 kg. The device is classified under IEC 60947-3. Manufacturer ID: 1SCA123070R1001.
- OS250D13N2P
The ABB OS250D13N2P is a four-pole front-operated fuse switch disconnector for base mounting, with the fourth pole on the right side, switched with a solid link. It accepts NH0 and NH1 fuses in the DIN fuse system and is rated 250 A at 690 V AC. Rated insulation voltage is 1000 V, rated impulse withstand voltage is 12 kV, and rated conditional short-circuit current is 80 kA at 690 V. Rated short-time withstand current is 8 kA rms for 1 s. Power loss is 13 W per pole at rated operating conditions. Terminals are lug type, 25 mm wide, tightened to 30 to 44 N·m. Dimensions are 260 mm width, 199 mm height, and 154 mm depth; net weight is 4.8 kg. It conforms to IEC 60947-3.
- OS250D20
ABB OS250D20 fuse switch disconnector, manufacturer ID 1SCA022760R0250. Two-pole, front-operated, base-mounting unit with lug terminals, 25 mm terminal width, and 30 to 44 N·m tightening torque. Rated current 250 A in the main circuit; conventional free-air thermal current 250 A at 40 °C; conventional thermal current 250 A fully enclosed. Rated operational voltage 690 V AC; rated insulation voltage 1000 V; rated impulse withstand voltage 12 kV; rated conditional short-circuit current 80 kA at 690 V; rated short-time withstand current 8 kA rms for 1 s. Power loss 13 W per pole at rated operating conditions. Accepts NH0 and NH1 DIN fuses. Pollution degree 3. IEC 60947-3. Handle and shaft not included. Dimensions 154 mm wide, 199 mm high, 154 mm deep; net weight 2.6 kg.