- OS630D13N2K
The ABB OS630D13N2K is a 4-pole front-operated fuse switch disconnector for base mounting, with a direct-mounted handle and a switched fourth pole on the right side using a solid link. It accepts NH3 DIN fuses and lug terminals 39 mm wide, tightened to 50 ... 75 N·m. Rated values include 630 A main circuit, 690 V AC, 1000 V insulation, 12 kV impulse withstand, and 80 kA conditional short-circuit current at 690 V. Conventional free-air thermal current is 630 A at 40 °C; enclosed thermal current is 570 A. Power loss is 46 W per pole at rated operating conditions. It conforms to IEC 60947-3. Dimensions are 279 mm wide, 429 mm high, and 306 mm deep; weight is 19.4 kg.
- OS630D13N2P
The ABB OS630D13N2P is a fuse protector with a DIN NH3 fuse system and a switched fourth pole on the right side using a solid link. It measures 429 mm wide, 306 mm high, and 233 mm deep, weighing 15.9 kg. Conventional free-air thermal current is 630 A at 40 °C; fully enclosed conventional thermal current is 570 A. Pollution degree 3. A pistol handle and shaft are included.
- OS630D21
ABB OS630D21 fuse switch disconnector, 3-pole, front-operated, base mounting. Main circuit rated 690 V AC, 630 A, with rated insulation voltage 1000 V and rated impulse withstand voltage 12 kV. Conventional free-air thermal current 630 A at 40 °C; fully enclosed thermal current 570 A. Rated conditional short-circuit current 80 kA at 690 V, and rated short-time withstand current 18 kA rms for 1 s. Accepts NH3 DIN fuse system fuses. Lug terminals, 39 mm terminal width, tightening torque 50 to 75 N·m. Power loss 46 W per pole at rated operating conditions. Pollution degree 3. Dimensions 341 mm wide, 306 mm high, 233 mm deep; net weight 14.39 kg. Conforms to IEC 60947-3. Handle and shaft not included.
- OS630D21P
ABB fuse protector, model OS630D21P, manufacturer ID 1SCA022835R7930. Three-pole, front-operated fuse switch disconnector for NH3 DIN fuses, base mounting, with pistol handle and shaft included. Rated current 630 A in the main circuit; conventional free-air thermal current 630 A at 40 °C, 570 A fully enclosed. Rated operational voltage 690 V AC; rated insulation voltage 1000 V; rated impulse withstand voltage 12 kV. Rated conditional short-circuit current 80 kA at 690 V; rated short-time withstand current 18 kA rms for 1 s. Power loss 46 W per pole at rated operating conditions. Lug terminals, 39 mm wide, tightening torque 50 to 75 N·m. Dimensions 341 mm wide, 306 mm high, 233 mm deep; net weight 14.89 kg. Pollution degree 3. Conforms to IEC 60947-3.
- OS630D22F
ABB OS630D22F fuse switch disconnector, 4-pole, base mounting, front operated. Rated current 630 A at 690 V AC; conventional free-air thermal current 630 A at 40 °C, fully enclosed 570 A. Rated insulation voltage 1000 V, rated impulse withstand voltage 12 kV, rated conditional short-circuit current 80 kA at 690 V. Rated short-time withstand current 18 kA rms for 1 s. Fuse size NH3, DIN fuse system; fourth pole switched-fusible. Power loss 46 W per pole at rated operating conditions. Lug terminals, 39 mm terminal width, tightening torque 50 to 75 N·m. Pollution degree 3. Dimensions 429 x 306 x 233 mm; net weight 19.154 kg. Handle and shaft not included. Conforms to IEC 60947-3.
- OS630D22F-60
ABB OS630D22F-60 fuse protector, manufacturer ID 1SCA124535R1001. Four-pole, front-operated fuse switch disconnector for base mounting, accepting NH2 and NH3 fuses in the DIN fuse system. Rated operational voltage is 690 V AC for the main circuit. Power loss is 46 W per pole at rated operating conditions. Lug terminals accept a tightening torque of 50 to 75 N·m. The unit weighs 17.16 kg and conforms to IEC 60947-3. ETIM 8 and ETIM 9 classify it as EC001040, fuse switch disconnector. WEEE Category 5, small equipment with no external dimension more than 50 cm.
- OS630D22N1
ABB OS630D22N1 fuse protector, a four-pole front-operated fuse switch disconnector for base mounting. Main circuit rated 690 V AC and 630 A; conventional free-air thermal current 630 A at 40 °C, fully enclosed thermal current 570 A. Rated insulation voltage 1000 V, rated impulse withstand voltage 12 kV, rated conditional short-circuit current 80 kA at 690 V, and short-time withstand current 18 kA rms for 1 s. Fuse system DIN, fuse size NH3. Fourth pole is switched with solid link, left side. Power loss 46 W per pole at rated operating conditions. Lug terminals, 39 mm wide, tightening torque 50 to 75 N·m. Pollution degree 3. Standards: IEC 60947-3. Handle and shaft not included. Net dimensions 429 x 306 x 233 mm; net weight 18.54 kg.
- OS630D22N1P
The ABB OS630D22N1P is a four-pole, front-operated fuse switch disconnector for base mounting. It uses NH3 fuses in the DIN system and accepts lug terminals 39 mm wide, tightened to 50 to 75 N·m. The fourth pole, on the left side, is switched with a solid link. Rated current of the main circuit is 630 A, with conventional thermal current of 630 A at 40 °C free air and 570 A fully enclosed. Rated operational voltage is 690 V AC; rated insulation voltage is 1000 V and rated impulse withstand voltage is 12 kV. Rated conditional short-circuit current is 80 kA at 690 V, and short-time withstand current is 18 kA rms for 1 s. Pollution degree 3. It conforms to IEC 60947-3. Dimensions are 429 mm wide, 306 mm high, and 233 mm deep; net weight is 19.04 kg. A pistol handle and shaft are included.