Q1Can you supply the ABB CMS-120LA?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the ABB CMS-120LA cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
CMS-120LA
Material Number
2CCA880225R0001
Manufacturer
ABB
Product ID
70412

Get a Free Quote

Request pricing and availability for CMS-120LA.

More parts to source? Send your whole list in one enquiry

Key specifications

Sensor type
Open-core sensor, 18 mm
Mounting
For retrofit of MCBs (S200, SMISSLINE) and RCBOs (SMISSLINE)
Measurement range
80 A
Measurement method
TRMS, AC 50/60 Hz, DC
Insulation voltage
690 V AC / 1500 V DC
Operating temperature
-25 ... +70 °C
See all specifications

Product Highlights

  1. Compatibility: Compatible with ABB Circuit Monitoring Systems CMS-600 and CMS-700 control units
  2. Supported Protocols: RS485 (Modbus RTU) and LAN (TCP/IP and Modbus TCP)
  3. Measurement Accuracy: AC accuracy ≤ ± 1.0% and DC temperature coefficient ≤ ± 0.14%
  4. Installation: No special tools required and can be mounted anywhere
CMS-120LA

Product Information

Technical Specifications

Specifications for CMS-120LA

ParameterValue
Type designationCMS-120LA
Sensor typeOpen-core sensor, 18 mm
MountingFor retrofit of MCBs (S200, SMISSLINE) and RCBOs (SMISSLINE)
Measurement range80 A
Measurement methodTRMS, AC 50/60 Hz, DC
Crest factor of distorted wave forms≤ 1.5
AC accuracy (at 25 °C, of full scale)≤ ±1 %
AC temperature coefficient≤ ±0.04 %/K
ParameterValue
DC accuracy (at 25 °C, of full scale)≤ ±1.2 %
DC temperature coefficient≤ ±0.14 %/K
Resolution0.01 A
Internal sampling rate5000 Hz
Response time (±1 %)typ. 0.34 s
Max. cable diameter9.6 mm
Insulation voltage690 V AC / 1500 V DC
Operating temperature-25 ... +70 °C
Storage temperature-40 ... +85 °C
Dimensions17.4 x 41.0 x 38.9 mm
Reference standardsIEC 61010-1, UL508 / CSA C22.2 No. 14

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?