Product Model
CMS-122FH
Material Number
2CCA880217R0001
Manufacturer
ABB
Product ID
70306

Get a Free Quote

Request pricing and availability for CMS-122FH.

More parts to source? Send your whole list in one enquiry

Key specifications

Sensor type
Open-core sensor, 18 mm
Mounting
For retrofit of E90 fuseholders 1000 V DC
Measurement range
20 A
Measurement method
TRMS, AC 50/60 Hz, DC
Insulation voltage
690 V AC / 1500 V DC
Operating temperature
-25 ... +70 °C
See all specifications

Product Highlights

  1. Current Measurement Accuracy: AC accuracy is ≤ ±1.0%
  2. Width: Overall width is 18mm
  3. Connection to Control Unit: Connects to the CMS-700 control unit via a flexible flat cable and insulation piercing connectors
  4. Current Measurement Range: Measures direct, alternating, and mixed current up to 20A
  5. Data Transmission: Transmits measurement data digitally to the control unit via the CMS bus interface
CMS-122FH

Product Information

Technical Specifications

Specifications for CMS-122FH

ParameterValue
Type designationCMS-122FH
Sensor typeOpen-core sensor, 18 mm
MountingFor retrofit of E90 fuseholders 1000 V DC
Measurement range20 A
Measurement methodTRMS, AC 50/60 Hz, DC
Crest factor of distorted wave forms≤ 6
AC accuracy (at 25 °C, of full scale)≤ ±1 %
AC temperature coefficient≤ ±0.04 %/K
ParameterValue
DC accuracy (at 25 °C, of full scale)≤ ±1.8 %
DC temperature coefficient≤ ±0.44 %/K
Resolution0.01 A
Internal sampling rate5000 Hz
Response time (±1 %)typ. 0.34 s
Max. cable diameter9.6 mm
Insulation voltage690 V AC / 1500 V DC
Operating temperature-25 ... +70 °C
Storage temperature-40 ... +85 °C
Dimensions17.4 x 41.0 x 38.9 mm
Reference standardsIEC 61010-1, UL508 / CSA C22.2 No. 14

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.