Product Model
DDA204 AC-40/0.3
Material Number
2CSB204001R3400
Manufacturer
ABB
Product ID
69749

Get a Free Quote

Request pricing and availability for DDA204 AC-40/0.3.

More parts to source? Send your whole list in one enquiry

Key specifications

Rated Voltage (Ur)
230/400 V
Rated Operational Voltage
230/400 V
Rated Current (In)
40 A
Rated Frequency (f)
50 … 60 Hz
Degree of Protection
IP2X
Product Net Weight
173 g
See all specifications

Product Highlights

  1. Protection Type: Type AC residual current device for sinusoidal alternating earth fault currents
  2. Rated Current: 40 A
  3. Rated Residual Current: 300 mA
  4. Rated Voltage: 230/400 V, rated insulation voltage 500 V, rated impulse withstand voltage 4 kV
  5. Rated Frequency: 50 to 60 Hz
  6. Standards: IEC/EN 61009 Annex G
  7. Number of Poles: 4
  8. Operating Characteristic: Instantaneous
  9. Ambient Temperature Range: -25 to 55 °C
  10. Degree of Protection: IP2X
  11. Electrical Endurance: 10000 cycles
  12. Connecting Capacity: Rigid 16 mm², flexible 16 mm²
  13. Power Loss: 4.8 W
  14. Compatibility: For assembly with MCBs S200 series and S300P
DDA204 AC-40/0.3

Product Information

Technical Specifications

Specifications for DDA204 AC-40/0.3

ParameterValue
StandardsIEC/EN 61009 Ann. G
Type of Residual CurrentType AC
Rated Voltage (Ur)230/400 V
Rated Operational Voltage230/400 V
Rated Insulation Voltage (Ui)500 V
Rated Impulse Withstand Voltage (Uimp)4 kV
Rated Current (In)40 A
Rated Residual Current300 mA
Leakage Current TypeAC
Rated Frequency (f)50 … 60 Hz
Power Loss4.8 W
Power Supply ConnectionArbitrary
Electrical Endurance10000 cycle
Number of Poles4
Operating CharacteristicInstantaneous
Options Provided-
Connecting CapacityRigid 16 ... 16 mm² Flexible 16 ... 16 mm²
Ambient Temperature-25...55 °C
Ambient Air TemperatureOperation -25...55 °C
Degree of ProtectionIP2X
Resistance to Vibrations20 Cycles with Load 0.8 In: 1g or 1mm 50 … 150 … 5 Hz
ParameterValue
Resistance to Shock acc. to IEC 60068-2-2725g 2 shocks 13 ms
Environmental InformationRefer to RoHS
Short-Circuit Current Rating (SCCR)0.3 ... 0.3 A
Product Net Width105 mm
Product Net Height93 mm
Product Net Depth / Length76 mm
Product Net Weight173 g
Dimension Diagram9AKK106930A3989
ETIM 8EC002297 - Residual current circuit breaker (RCCB) module
ETIM 9EC002297 - Residual current circuit breaker (RCCB) module
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2BBusiness To Consumer
CN885363030
eClassV11.0 : 27142210
Object Classification CodeF
Manufacturer ID2CSB204001R3400

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?