- 855-1005/2500-1001
WAGO 855-1005/2500-1001 is a closed current transformer for current measurement. Primary rated current is 2500 A with a 5 A secondary, rated power 10 VA, accuracy class 1, and rated frequency 50 to 60 Hz. Rated continuous thermal current is 1.2 x IN; rated short-time thermal current is 60 x IN for 1 s, maximum 100 kA for 1 s. Overcurrent limiting factor is FS5 or FS10, type dependent, per the type plate. The measurement conductor feedthrough is 70 mm. Dimensions are 130 mm wide, 147.45 mm high, and 52 mm deep; weight is 396 g. Connection technology is CAGE CLAMP, with 9 to 10 mm strip length and 0.08 to 4 mm2 (28 to 12 AWG) conductors. Operation is -5 to +50 °C.
- 855-1700/032-000
The WAGO 855-1700/032-000 is a plug-in current transformer for the WAGO I/O System, intended only for use with WAGO 750 Series 3-Phase Power Measurement Modules. It measures current with a 32 A primary rated current and 0.32 A secondary rated current at 50 to 60 Hz, accuracy class 0.5, and 0.01 VA rated power. The closed current transformer provides a 5.0 mm measurement conductor feedthrough and accepts 0.2 to 1.5 mm2 (24 to 14 AWG) conductors via push-in CAGE CLAMP connection and a picoMAX 3.5, 2091-1122 connector. It measures 17 mm wide, 34 mm high, and 23 mm deep, weighs 11 g, and operates from -10 to +55 °C. Protection is IP20; test voltage is AC 3 kV at 50 Hz for 1 min.
- 855-1851/350-000
WAGO 855-1851/350-000 is a current and voltage tap for 185 mm² conductors, with 350 A primary rated current, 1 A secondary rated current, and accuracy class 0.5. It mounts via the jumper slot of a 2-conductor high-current through terminal block (285-1185; 285-1184) for DIN-rail mounting. Rated voltage is AC 400 V; rated frequency 50 … 60 Hz; rated power 0.2 VA. The voltage path uses a 2 A; 450 V; F; 70 kA; 5 x 25 mm fuse (WAGO 855-8020). Dimensions are 32 mm width, 84 mm height, 60 mm depth; weight 144 g. Operation is -25 … +70 °C at up to 2000 m altitude. Conforms to EN 61869-2.
- 855-2701/035-001
WAGO 855-2701/035-001 plug-in current transformer, closed type, for current measurement. Primary rated current 35 A, secondary rated current 1 A, rated power 0.2 VA, accuracy class 1, rated frequency 50 to 60 Hz. Rated continuous thermal current 100 percent, rated short-time thermal current 60 x IN for 1 s, rated surge current 2.5 x Ith. Highest voltage for equipment Um AC 720 Vrms; test voltage AC 3 kV at 50 Hz for 1 min. Feedthrough for measurement conductor 7.5 mm. Push-in CAGE CLAMP connection, picoMAX 3.5 connector 2091-1122, strip length 8 to 9 mm, solid and fine-stranded conductors 0.2 to 1.5 mm2 (24 to 14 AWG). IP20, insulation class E, PA 66 housing. Dimensions 27 x 46 x 23 mm, weight 48.4 g. Operating temperature -10 to +55 C, storage -20 to +70 C, relative humidity 5 to 85 percent without condensation, altitude up to 2000 m. CE, EN 61869-1.
- 855-2701/064-001
WAGO 855-2701/064-001 plug-in current transformer, 64 A primary, 1 A secondary, rated frequency 50 … 60 Hz, accuracy class 1, rated power 0.2 VA. Closed current transformer with 7.5 mm feedthrough for the measurement conductor. Push-in CAGE CLAMP® connection; WAGO connector picoMAX® 3.5, 2091-1122; strip length 8 … 9 mm; solid and fine-stranded conductors 0.2 … 1.5 mm² (24 … 14 AWG). Dimensions 27 mm W x 46 mm H x 23 mm D; PA 66 housing; weight 44 g. IP20; insulation class E; highest voltage for equipment Um AC 720 Vrms; test voltage AC 3 kV, 50 Hz, 1 min. Ambient temperature -10 … +55 °C operation, -20 … +70 °C storage; relative humidity 5 … 85 % without condensation; operating altitude up to 2000 m. CE; EN 61869-1.
- 855-3001/060-003
WAGO 855-3001/060-003 split-core current transformer, suspended mounting, for current measurement. Primary rated current 60 A; secondary rated current 1 A; rated power Sr 0.2 VA; accuracy class 3. Rated frequency 50 … 60 Hz. Rated continuous thermal current Icth 100 %; rated short-time thermal current Ith 60 x IN/ 1 s; rated surge current Idyn 2.5 x Ith. Highest voltage for equipment Um AC 720 Vrms. Test voltage AC 6 kV, 50 Hz, 1 min. Feedthrough for measurement conductor Ø 18 mm. Cable 2 x 0.5 mm2, fine-stranded, 3 m; brown = S1, blue = S2. Dimensions 48 mm x 50.4 mm x 36 mm; weight 240 g. Ambient temperature -10 … +55 °C operation, -20 … +70 °C storage; relative humidity 5 85 % without condensation; operating altitude max. 2000 m. IP20; CE; EN 61869-1.
- 855-3001/100-003
WAGO 855-3001/100-003 split-core current transformer for current measurement, suspended mounting. Primary rated current 100 A, secondary rated current 1 A, rated power 0.2 VA, accuracy class 3, rated frequency 50 … 60 Hz. Measurement conductor feedthrough Ø 18 mm. Test voltage AC 6 kV; 50 Hz; 1 min. Highest voltage for equipment Um AC 720 Vrms. Rated continuous thermal current Icth 100 %, rated short-time thermal current Ith 60 x IN/ 1 s, rated surge current Idyn 2.5 x Ith. 3 m cable, 2 x 0.5 mm² fine-stranded, brown = S1, blue = S2. IP20, dimensions 48 x 50.4 x 36 mm, 240 g. Ambient temperature -10 … +55 °C operation, -20 … +70 °C storage, 5 85 % relative humidity without condensation, altitude up to 2000 m. Conforms to EN 61869-1, CE marked.
- 855-3001/200-001
WAGO 855-3001/200-001 split-core current transformer for current measurement, with a primary rated current of 200 A and a secondary rated current of 1 A. Rated power Sr is 0.2 VA and accuracy class is 1. Rated frequency is 50 … 60 Hz. The measurement conductor feedthrough is Ø 18 mm. The cable is 3 m, 2 x 0.5 mm2 fine-stranded, with brown = S1 and blue = S2. Dimensions are 48 mm width, 50.4 mm height, and 36 mm depth; weight is 10 g. Operation is -10 … +55 °C, storage -20 … +70 °C, relative humidity 5 85 % without condensation, and maximum operating altitude 2000 m. Protection type is IP20. Test voltage is AC 6 kV; 50 Hz; 1 min. Highest voltage for equipment Um is AC 720 Vrms. Conformity marking is CE; standards/specifications include EN 61869-1.