Product Model
2022-1804
Material Number
—
Manufacturer
WAGO
Product ID
42097

Get a Free Quote

Request pricing and availability for 2022-1804.

More parts to source? Send your whole list in one enquiry

Key specifications

Weight
11.8g
Rated voltage (III / 3)
690V
Rated impulse voltage (III / 3)
6kV
Rated current
24A
Rated current IN for specified power loss
24A
Frequency
f1= 5 Hz to f2= 150 Hz
See all specifications

Product Highlights

  1. Mounting: DIN-35 rail, horizontal design
  2. Connection: 4 female plug slots, 1 potential, 1 level
  3. Dimensions: 5.2 mm wide, 106 mm high, 32.5 mm deep from upper DIN-rail edge
  4. Electrical ratings: 690 V rated voltage, 6 kV rated impulse voltage, 24 A rated current per IEC/EN 60947-7-1 (III/3)
  5. Housing: blue polyamide PA66, UL94 V0 flammability class, continuous operating temperature -60 to +105 °C
  6. Railway compliance: tested to DIN EN 50155 and DIN EN 61373 for shock and vibration
  7. Safety note: a separator plate (209-191) or 10 mm end stop (249-117) must be placed at the end of a WAGO X-COM SYSTEM terminal strip
2022-1804

Product Information

Technical Specifications

Specifications for 2022-1804

ParameterValue
Safety informationA separator plate (Item No. 209-191) or a 10 mm end stop (Item No. 249-117) must be placed at the end of a WAGO X-COM®-SYSTEM terminal strip.
Female plug slots4
Total number of potentials1
Number of levels1
Width5.2 mm / 0.205 inches
Height106 mm / 4.173 inches
Depth from upper-edge of DIN-rail32.5 mm / 1.28 inches
Designhorizontal type
Mounting typeDIN-35 rail
Marking levelCenter/side marking
Note (material data)Information on material specifications can be found here
Colorblue
Material groupI
Insulation material (main housing)Polyamide (PA66)
Flammability class per UL94V0
Fire load0.242MJ
Weight11.8g
Continuous operating temperature-60 … +105 °C
ETIM 9.0EC000897
ETIM 8.0EC000897
ECCNNO US CLASSIFICATION
PU (SPU)50 pcs
Packaging typeBox
Country of originCN
GTIN4055143926683
Customs tariff number8536904000
RoHS Compliance StatusCompliant,No Exemption
Ratings perIEC/EN 60947-7-1
Rated voltage (III / 3)690V
Rated impulse voltage (III / 3)6kV
Rated current24A
Legend (ratings)(III3) ≙ Overvoltage category IIIPollution degree 3
Approvals perCSA 22.2 No 158
ParameterValue
Rated voltage UL (Use Group B)600V
Rated current UL (Use Group B)20A
Rated voltage UL (Use Group C)600V
Rated current UL (Use Group C)20A
Rated voltage CSA (Use Group C)600V
Rated current CSA (Use Group C)20A
Power loss, per pole (potential)0.766W
Rated current IN for specified power loss24A
Test specification <br/>Railway applications <br/>Rolling stock <br/>Electronic equipmentDIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications <br/>Rolling stock equipment <br/>Shock and vibration testsDIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation locationService life test, Category 1, Class A/B
Function test with noise-like vibrationTest passed according to Section 8 of the standard
Frequencyf1= 5 Hz to f2= 150 Hz
Acceleration5g (highest test level used for all axes)
Test duration per axis5 h
Test directionsX, Y and Z axes
Monitoring for contact faults/interruptionsPassed
Voltage drop measurement before and after each axisPassed
Simulated service life test through increased levels of noise-like vibrationTest passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptionsPassed
Extended test scope: Voltage drop measurement before and after each axisPassed
Shock testTest passed according to Section 10 of the standard
Shock formHalf sine
Shock duration30 ms
Number of shocks per axis3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipmentPassed

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.