- 857-403
WAGO 857-403 signal conditioner with voltage (DC) input and current output. Input signal ±60 mV or ±0.3 mA; output ±5 V or ±10 mA. Input resistance is 10 Ω (≤ 5 mA) and 100 Ω (≤ 5 mA) for current input, 1 MΩ for voltage input. Load impedance is ≤ 2 kΩ for voltage output and ≤ 600 Ω for current output. Limit frequency is 100 Hz or 5 kHz, configurable via DIP switch. Step response is 3.5 ms (100 Hz) or 100 µs (5 kHz). Transmission error is ≤ 0.08 % of upper-range value; temperature coefficient ≤ 0.01 %/K. Supply is DC 24 V with ±30 % range; current consumption ≤ 40 mA. Push-in CAGE CLAMP® connection, 6 mm wide, DIN-35 rail mounting, IP20, ambient operation -25 … +70 °C.
- 857-411
WAGO 857-411 signal conditioner for current signals, pre-configured. Input 0–20 mA with input resistance ≤ 50 Ω; output 0–20 mA into load impedance ≤ 600 Ω. Limit frequency 100 Hz; typical step response 3.5 ms; transmission error ≤ 0.1 % of upper-range value; temperature coefficient ≤ 0.01 %/K. Supply: 24 VDC (SELV), range ±30 %, current consumption ≤ 40 mA. Test voltage input/output/supply AC 3 kV, 50 Hz, 1 min. Rated voltage 300 V; overvoltage category II; pollution degree 2. Push-in CAGE CLAMP® connection, solid conductor 0.08–2.5 mm² (28–14 AWG), strip length 9–10 mm. 6 mm wide, DIN-35 rail mounting, IP20. Ambient operation -25 to +70 °C. EMC: EN 61000-6-2, EN 61000-6-4; EN 61010-1. CE marked.
- 857-412
WAGO 857-412 JUMPFLEX signal conditioner, pre-configured, for analog standard voltage signals. Input 0–10 V, input resistance ≤ 100 kΩ, maximum input voltage 30 V. Output 0–10 V into load impedance ≤ 2 kΩ. Limit frequency 100 Hz; typical step response 3.5 ms; typical transmission error ≤ 0.1 % of upper-range value; temperature coefficient ≤ 0.01 %/K. Supply 24 VDC (SELV), range ±30 %, current consumption ≤ 25 mA. Test voltage input/output/supply AC 3 kV, 50 Hz, 1 min. Push-in CAGE CLAMP connection, solid 0.08–2.5 mm2 (28–14 AWG), fine-stranded 0.34–2.5 mm2 (22–14 AWG), strip length 9–10 mm. DIN-35 rail mounting, IP20, 6 mm wide. Ambient operation -25 to +70 °C.
- 857-413
WAGO 857-413 signal conditioner, an isolation amplifier with voltage input and current output. Input signal is 0–10 V with input resistance ≤ 100 kΩ and maximum input voltage 30 V. Output signal is 0–20 mA into load impedance ≤ 600 Ω. Limit frequency is 100 Hz and typical step response is 3.5 ms. Typical transmission error is ≤ 0.1 % of upper-range value, with temperature coefficient ≤ 0.01 %/K. Supply is 24 VDC (SELV), nominal DC 24 V, range ±30 %, current consumption ≤ 30 mA at nominal supply voltage. Test voltage input/output/supply is AC 3 kV; 50 Hz; 1 min. Rated voltage 300 V, overvoltage category II, pollution degree 2. Push-in CAGE CLAMP® connection, 6 mm wide, DIN-35 rail mounting, IP20, operating ambient -25 … +70 °C.
- 857-414
WAGO 857-414 signal conditioner converts a 0–10 V voltage input to a 4–20 mA current output. Input resistance is ≤ 100 kΩ and maximum input voltage is 30 V; the current output supports load impedance ≤ 600 Ω. Typical transmission error is ≤ 0.1 % of upper-range value, temperature coefficient ≤ 0.01 %/K, limit frequency 100 Hz, and typical step response 3.5 ms. The module is pre-configured and provides 3-way electrical isolation with a test voltage of AC 3 kV, 50 Hz, 1 min. Supply is 24 VDC (SELV) with ±30 % range and current consumption ≤ 40 mA. It mounts on DIN-35 rail, measures 6 mm wide, and uses Push-in CAGE CLAMP® connections for 0.08–2.5 mm² (28–14 AWG) solid or 0.34–2.5 mm² (22–14 AWG) fine-stranded conductors, 9–10 mm strip length. Rated voltage 300 V, IP20, operating temperature -25 to +70 °C.
- 857-415
WAGO 857-415 JUMPFLEX isolation amplifier for converting a 0–20 mA current input to a 0–10 V voltage output. Input resistance is ≤ 50 Ω; maximum input current 50 mA and maximum input voltage 30 V. Voltage output load impedance is ≤ 2 kΩ, limit frequency 100 Hz, typical step response 3.5 ms, typical transmission error ≤ 0.1 % of upper-range value, temperature coefficient ≤ 0.01 %/K. Supply is 24 VDC (SELV), nominal US DC 24 V, range ±30 %, current consumption ≤ 20 mA at nominal supply voltage. Test voltage input/output/supply AC 3 kV, 50 Hz, 1 min. 6 mm wide, DIN-35 rail mounting, Push-in CAGE CLAMP connection, IP20, ambient operation -25 … +70 °C.
- 857-416
WAGO 857-416 signal conditioner, a pre-configured isolation amplifier for converting a 4–20 mA current input to a 0–10 V voltage output. It operates from a 24 VDC (SELV) supply with a ±30 % supply voltage range and consumes ≤ 25 mA. Input resistance is ≤ 50 Ω; voltage output load impedance is ≤ 2 kΩ. Typical transmission error is ≤ 0.1 % of upper-range value, temperature coefficient ≤ 0.01 %/K, limit frequency 100 Hz, and typical step response 3.5 ms. The 6 mm wide module mounts on a DIN-35 rail and uses Push-in CAGE CLAMP® connections for solid conductors 0.08–2.5 mm² (28–14 AWG) and fine-stranded conductors 0.34–2.5 mm² (22–14 AWG), with 9–10 mm strip length. Rated voltage 300 V; test voltage AC 3 kV, 50 Hz, 1 min. Operating ambient temperature −25 to +70 °C; IP20; CE marking.
- 857-420
WAGO 857-420 signal conditioner with DIP-switch configuration. Input is current, 0–20 mA, with input resistance ≤ 50 Ω and maximum input current 50 mA. Sensor supply is Uv = 18 V; 30 mA. Outputs are current 0–20 mA and voltage 0–5 V, with load impedance ≤ 600 Ω for current output and ≤ 2 kΩ for voltage output. Offset is ≤ 20 µA, residual ripple ≤ 10 mV (rms), limit frequency 100 Hz, typical step response 3.5 ms, typical transmission error ≤ 0.1 % of upper-range value, and temperature coefficient ≤ 0.01 %/K. Supply is DC 24 V nominal with ±30 % range and current consumption ≤ 45 mA. Test voltage input/output/supply is AC 2.5 kV; 50 Hz; 1 min. DIN-35 rail mounting, 6 mm wide, IP20, push-in CAGE CLAMP connection.