Industrial Automation Parts. Prompt replies from real people.

WAGO 750-651 Serial TTY Interface

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/24/2026

Q1Can you supply the WAGO 750-651?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the WAGO 750-651 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
750-651
Material Number
—
Manufacturer
WAGO
Product ID
39546

Get a Free Quote

Request pricing and availability for 750-651.

More parts to source? Send your whole list in one enquiry

Key specifications

Supply voltage (system)
5 VDC; Via data contacts
Weight
45.9g
Ambient temperature (operation)
0 … +55 °C
Protection type
IP20
See all specifications

Product Highlights

  1. TTY 20 mA serial interface: 1 TxD / 1 RxD full-duplex, 2 x 20 mA bit transfer, 1 x 24-bit input/output (3-byte user data) plus 1 x 8-bit control/status
  2. Transmission rate: 1.2 kBd to 19.2 kBd, 9600 baud default, 8 data bits, 1 stop bit, no parity, 128-byte input and 16-byte output buffer
  3. Line length: max. 1000 m over twisted pair, load impedance up to 500 Ω
  4. Connection and indicators: 4 x CAGE CLAMP inputs/outputs for 0.08 to 2.5 mm2 (28 to 14 AWG) solid or fine-stranded conductors, 8 to 9 mm strip length, green LEDs for function, TxD and RxD
  5. Supply and isolation: 5 VDC system supply via data contacts, 55 mA current consumption, 500 V system/field isolation
  6. Dimensions and mounting: 12 mm wide, 100 mm high, 69.8 mm deep (62.6 mm from DIN-rail upper edge), 45.9 g, DIN-35 rail mounting, light gray polycarbonate/polyamide 6.6 housing
  7. Operating conditions: 0 to +55 °C operation, -40 to +85 °C storage, 95% relative humidity without condensation, IP20, pollution degree 2, 0 to 2000 m altitude, 4g vibration and 15g shock resistance
  8. EMC and environmental compliance: EN 61000-6-2 immunity and EN 61000-6-4 emission for marine applications, pollutant exposure per IEC 60068-2-42 and IEC 60068-2-43, CE marking, RoHS compliant
750-651

Product Information

Technical Specifications

Specifications for 750-651

ParameterValue
Signal typeTTY, 20 mA
Transmission rate1.2 kBd 19.2 kBd ( (9600 baud (default setting)))
Bit transfer2 x 20 mA
Transmission channels1 TxD / 1 RxD, full-duplex
Line lengthmax. 1000 m twisted pair
Data width1 x 24-bit input/output (3-byte user data); 1 x 8-bit control/status
Load impedance (current output)≤ 500 Ω
ParityNone
Number of data bits8
Number of stop bits1
Buffer128-byte input / 16-byte output
Supply voltage (system)5 VDC; Via data contacts
Current consumption (5 V system supply)55mA
Isolation500 V system/field
IndicatorsLED (A, B, D) green: Function, TxD, RxD
Connection technology: inputs / outputs4 x CAGE CLAMP®
Connection type 1Inputs/Outputs
Solid conductor0.08 … 2.5 mm2 / 28 14 AWG
Fine-stranded conductor0.08 … 2.5 mm2 / 28 14 AWG
Strip length8 9 mm / 0.31 0.35 inches
Width12 mm / 0.472 inches
Height100 mm / 3.937 inches
Depth69.8 mm / 2.748 inches
Depth from upper-edge of DIN-rail62.6 mm / 2.465 inches
Mounting typeDIN-35 rail
Colorlight gray
Housing materialPolycarbonate; polyamide 6.6
Fire load0.087MJ
Weight45.9g
Conformity markingCE
Ambient temperature (operation)0 … +55 °C
ParameterValue
Ambient temperature (storage)-40 … 85 °C
Protection typeIP20
Pollution degree2 per IEC 61131-2
Operating altitude0 2000 m / 0 6562 ft
Mounting positionHorizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Relative humidity (without condensation)95%
Vibration resistance4g per IEC 60068-2-6
Shock resistance15g per IEC 60068-2-27
EMC immunity to interferenceper EN 61000-6-2, marine applications
EMC emission of interferenceper EN 61000-6-4, marine applications
Exposure to pollutantsPer IEC 60068-2-42 and IEC 60068-2-43
Permissible pollutant concentration H2S at a relative humidity < 75%10ppm
Permissible pollutant concentration SO 2 at a relative humidity < 75%25ppm
Product Group15 (I/O System)
eCl@ss 10.027-24-26-08
eCl@ss 9.027-24-26-08
ETIM 9.0EC001604
ETIM 8.0EC001604
ECCNNO US CLASSIFICATION
PU (SPU)1 pcs
Packaging typebox
Country of originDE
GTIN4045454853006
Customs tariff number8538901000
End of Sale2023-12-31
End of Production2024-03-31
End of Delivery2024-04-01
End of Service and Repair2026-04-01
RoHS Compliance StatusCompliant,No Exemption

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp
WAGO 750-651 Serial TTY Interface