Industrial Automation Parts. Prompt replies from real people.

Schneider LC1K09008L7 TeSys K Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the Schneider LC1K09008L7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1K09008L7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1K09008L7
Material Number
—
Manufacturer
Schneider
Product ID
38638

Get a Free Quote

Request pricing and availability for LC1K09008L7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC <= 400 Hz / Signalling circuit: <= 690 V AC <= 400 Hz
[Ie] rated operational current
20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit
[Uc] control circuit voltage
200...208 V AC 50/60 Hz
IP degree of protection
IP2X conforming to VDE 0106
See all specifications

Product Highlights

  1. Rated Operational Current: 20 A at up to 690 V AC, AC-1, for power circuit
  2. Contact Configuration: 4-pole with 2 NO + 2 NC power pole contact composition
  3. Coil and Control: AC 50/60 Hz control circuit with 200...208 V AC coil voltage
  4. Making and Breaking Capacity: 110 A AC making capacity and 110 A breaking capacity at 220...230 V, 380...400 V, 415 V, and 440 V conforming to IEC 60947
  5. Thermal Current: 20 A at 60 °C for power circuit, 10 A at 50 °C for signalling circuit
  6. Impulse Withstand Voltage: 8 kV, overvoltage category III
  7. Terminal and Mounting: Screw clamp terminals for 0.34...4 mm² conductors, mountable on plate or rail
  8. Durability: 10 million mechanical cycles and 0.16 million electrical cycles at 20 A AC-1 up to 690 V
  9. Environmental Compliance: RoHS and REACh compliant
LC1K09008L7

Product Information

Technical Specifications

Specifications for LC1K09008L7

ParameterValue
Product or component typeContactor
[Ue] rated operational voltagePower circuit: <= 690 V AC <= 400 Hz / Signalling circuit: <= 690 V AC <= 400 Hz
[Ie] rated operational current20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit
[Uc] control circuit voltage200...208 V AC 50/60 Hz
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at <50 °C) / Drop-out: >= 0.20 Uc (at <50 °C)
power pole contact composition2 NO + 2 NC
RangeTeSys
Device applicationControl
ParameterValue
Connections - terminalsScrew clamp terminals 1 cable(s) 1.5…4 mm²solidScrew clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable endScrew clamp terminals 2 cable(s) 1.5…4 mm²solidScrew clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
Height58 mm
Width45 mm
Depth57 mm
IP degree of protectionIP2X conforming to VDE 0106
Ambient air temperature for storage-50…80 °C
Product certificationsCB SchemeCCCULCSAEACCEUKCA

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp