| [Ui] rated insulation voltage | Power circuit 600 V UL 508Power circuit 690 V IEC 60947-4-1Signalling circuit 690 V IEC 60947-4-1Signalling circuit 690 V IEC 60947-5-1Signalling circuit 600 V UL 508Power circuit 600 V CSA C22.2 No 14Signalling circuit 600 V CSA C22.2 No 14 |
|---|
| Insulation resistance | > 10 MOhm for signalling circuit |
|---|
| Inrush power in VA | 30 VA (at 68 °F (20 °C)) |
|---|
| Hold-in power consumption in VA | 4.5 VA (at 68 °F (20 °C)) |
|---|
| Heat dissipation | 1.3 W |
|---|
| Control circuit voltage limits | Operational: 0.8...1.15 Uc (at <122 °F (50 °C))Drop-out: >= 0.20 Uc (at <122 °F (50 °C)) |
|---|
| Connections - terminals | solder pins 0.001 in (0.035 mm)) |
|---|
| Maximum operating rate | 3600 cyc/h |
|---|
| Auxiliary contacts type | Instantaneous 1 NC |
|---|
| Signalling circuit frequency | <= 400 Hz |
|---|
| Minimum switching current | 5 mA for signalling circuit |
|---|
| Minimum switching voltage | 17 V for signalling circuit |
|---|
| Mounting Support | Printed circuit boards |
|---|
| Operating time | 10...20 ms coil de-energisation and NO opening10...20 ms coil energisation and NO closing |
|---|
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
|---|
| Non overlap distance | 0.02 in (0.5 mm) |
|---|
| Mechanical durability | 10 Mcycles |
|---|
| Electrical durability | 1.3 Mcycles 9 A AC-3 <= 440 V1.3 Mcycles 9 A AC-3e <= 440 V0.16 Mcycles 20 A AC-1 <= 690 V0.02 Mcycles 54 A AC-4 <= 440 V |
|---|
| Mechanical robustness | Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6 |
|---|
| Height | 2.3 in (58 mm) |
|---|
| Width | 1.8 in (45 mm) |
|---|
| Depth | 2.2 in (57 mm) |
|---|
| Net Weight | 0.40 lb(US) (0.18 kg) |
|---|
| Standards | EN/IEC 60947-4-1GB/T 14048.4UL 60947-4-1CSA C22.2 No 60947-4-1JIS C8201-4-1IEC 60335-1:Clause 30.2IEC 60335-2-40:Annex JJUL 60335-2-40:Annex JJ |
|---|
| Product Certifications | CB SchemeCCCULCSAEACCEUKCA |
|---|
| IP degree of protection | IP2X VDE 0106 |
|---|
| Protective treatment | TC IEC 60068TC DIN 50016 |
|---|
| Ambient Air Temperature for Storage | -58...176 °F (-50...80 °C) |
|---|
| Operating altitude | 6561.68 ft (2000 m) without derating |
|---|
| Flame retardance | V1 conforming to UL 94Requirement 2 conforming to NF F 16-101Requirement 2 conforming to NF F 16-102 |
|---|