Product Model
LC1K1210N7
Material Number
—
Manufacturer
Schneider
Product ID
38493

Get a Free Quote

Request pricing and availability for LC1K1210N7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC <= 400 Hz / Signalling circuit: <= 690 V AC <= 400 Hz
[Ie] rated operational current
12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 12 A (at <60 °C) at <= 440 V AC AC-3e for power circuit / 20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit
[Uc] control circuit voltage
400...415 V AC 50/60 Hz
IP degree of protection
IP2X conforming to VDE 0106
See all specifications

Product Highlights

  1. Product Type: TeSys LC1K control contactor for resistive loads and motor control
  2. Utilisation Category: AC-3, AC-3e, AC-1, and AC-4
  3. Poles: 3P with 3 NO power poles and 1 NO auxiliary contact
  4. Rated Operational Voltage: Power and signalling circuits up to 690 V AC at up to 400 Hz
  5. Rated Operational Current: 12 A at up to 60 °C at up to 440 V AC for AC-3 and AC-3e, 20 A at up to 60 °C at up to 690 V AC for AC-1
  6. Motor Power: 3 kW at 220 to 230 V AC, 5.5 kW at 380 to 415 V AC, 5.5 kW at 440 V AC, and 4 kW at 690 V AC for AC-3, AC-3e, and AC-4
  7. Control Circuit: AC 50/60 Hz with 400 to 415 V AC control circuit voltage
LC1K1210N7

Product Information

Technical Specifications

Specifications for LC1K1210N7

ParameterValue
Product or component typeContactor
[Ue] rated operational voltagePower circuit: <= 690 V AC <= 400 Hz / Signalling circuit: <= 690 V AC <= 400 Hz
[Ie] rated operational current12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit12 A (at <60 °C) at <= 440 V AC AC-3e for power circuit20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit
[Uc] control circuit voltage400...415 V AC 50/60 Hz
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at <50 °C) / Drop-out: >= 0.20 Uc (at <50 °C)
power pole contact composition3 NO
RangeTeSys
Device short nameLC1K
ParameterValue
Connections - terminalsScrew clamp terminals 1 cable(s) 1.5…4 mm²solidScrew clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable endScrew clamp terminals 2 cable(s) 1.5…4 mm²solidScrew clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
Height58 mm
Width45 mm
Depth57 mm
IP degree of protectionIP2X conforming to VDE 0106
Ambient air temperature for storage-50…80 °C
Product certificationsCB SchemeCCCULCSAEACCEUKCA