Q1Can you supply the Schneider LC1K1610P7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1K1610P7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1K1610P7
Material Number
—
Manufacturer
Schneider
Product ID
38499

Get a Free Quote

Request pricing and availability for LC1K1610P7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC <= 400 Hz / Signalling circuit: <= 690 V AC <= 400 Hz
[Ie] rated operational current
16 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 16 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage
230 V AC 50/60 Hz
IP degree of protection
IP2X conforming to VDE 0106
See all specifications

Product Highlights

  1. Utilisation Category: AC-3 and AC-3e for motor control
  2. Rated Operational Current: 16 A at up to 440 V AC at 60 °C for power circuit
  3. Motor Power: 4 kW at 220...230 V AC, 7.5 kW at 380...415 V AC, 5.5 kW at 440 V AC, and 4 kW at 690 V AC for AC-3 and AC-3e
  4. Control Circuit: 230 V AC at 50/60 Hz with 1 NO auxiliary contact
  5. Rated Operational Voltage: Power and signalling circuits up to 690 V AC at up to 400 Hz
  6. Rated Impulse Withstand Voltage: 8 kV with overvoltage category III
  7. Conventional Free Air Thermal Current: 20 A at 60 °C for power circuit and 10 A at 50 °C for signalling circuit
  8. Standards: EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and IEC 60335-1 Clause 30.2
LC1K1610P7

Product Information

Technical Specifications

Specifications for LC1K1610P7

ParameterValue
Product or component typeContactor
[Ue] rated operational voltagePower circuit: <= 690 V AC <= 400 Hz / Signalling circuit: <= 690 V AC <= 400 Hz
[Ie] rated operational current16 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 16 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage230 V AC 50/60 Hz
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at <50 °C) / Drop-out: >= 0.20 Uc (at <50 °C)
power pole contact composition3 NO
RangeTeSys
Device short nameLC1K
ParameterValue
Connections - terminalsScrew clamp terminals 1 cable(s) 1.5…4 mm²solidScrew clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable endScrew clamp terminals 2 cable(s) 1.5…4 mm²solidScrew clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
Height58 mm
Width45 mm
Depth57 mm
IP degree of protectionIP2X conforming to VDE 0106
Ambient air temperature for operation-25…50 °C
Product certificationsCB SchemeCCCULCSAEACCEUKCA