Industrial Automation Parts. Prompt replies from real people.

Schneider RMPT10BD Universal Pt100 Probe Converter

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the Schneider RMPT10BD?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider RMPT10BD cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
RMPT10BD
Material Number
—
Manufacturer
Schneider
Product ID
33759

Get a Free Quote

Request pricing and availability for RMPT10BD.

More parts to source? Send your whole list in one enquiry

Key specifications

abnormal analogue output current
-30…0 mA when no input or input wire broken / 22…30 mA when no input or input wire broken
abnormal analogue output voltage
-15...-11 V when no input or input wire broken / 11...15 V when no input or input wire broken
Net weight
0.12 kg
IP degree of protection
IP20 (terminal block) / IP50 (housing)
See all specifications

Product Highlights

  1. Input Type: Converter for universal Pt100 temperature probes, -40...40 °C (-40...104 °F), 2, 3 or 4 wires
  2. Analogue Output: Current 0...20 mA and 4...20 mA into <= 500 Ohm, voltage 0...10 V into >= 100 kOhm
  3. Measurement Accuracy: +/- 0.5 % of full scale for 3 or 4 wires and +/- 1 % of full scale for 2 wires at 20 °C, repeat accuracy +/- 0.2 % full scale at 20 °C and +/- 0.6 % full scale at 60 °C, temperature coefficient 150 ppm/°C
  4. Protection: Overvoltage (+/- 30 V), reverse polarity and short-circuit protection on output, reverse polarity protection on power supply
  5. Supply and Consumption: 24 V DC non isolated +/- 20 %, <= 40 mA for voltage output and <= 60 mA for current output, green LED for power ON
  6. Abnormal Output: Voltage -15...-11 V or 11...15 V and current -30...0 mA or 22...30 mA when no input or input wire broken
  7. Mounting and Connection: Screw fixing on mounting plate or clip-on 35 mm symmetrical DIN rail, clamping capacity 1 x 2.5 mm² or 2 x 1.5 mm², tightening torque 0.6...1.1 N.m
  8. Environmental and Compliance: IP20 terminal block and IP50 housing, operation 0...50 °C side by side or 0...60 °C with 2 cm spacing, CE, UL, GL and CSA certifications, IEC 61000-4-2, IEC 61000-4-4, IEC 61000-4-5 and CISPR 11/22 class B
RMPT10BD

Product Information

Technical Specifications

Specifications for RMPT10BD

ParameterValue
Product or component typeConverter for Universal Pt100 probes
Range of productHarmony Analog
abnormal analogue output current-30…0 mA when no input or input wire broken / 22…30 mA when no input or input wire broken
Current consumption<= 40 mA for voltage output / <= 60 mA for current output
MarkingCE
Analogue input typeRTD - 40...40 °C/- 40...104 °F Pt 100 2, 3 or 4 wires
Analogue output typeCurrent 0...20 mACurrent 4...20 mAVoltage 0...10 V
abnormal analogue output voltage-15...-11 V when no input or input wire broken / 11...15 V when no input or input wire broken
ParameterValue
Local signallingLED (green) for power ON
Clamping connection capacity1 x 2.5 mm² / 2 x 1.5 mm²
Net weight0.12 kg
IP degree of protectionIP20 (terminal block) / IP50 (housing)
Ambient air temperature for operation0…50 °C mounting side by side / 0…60 °C 2 cm spacing
Protection typeOvervoltage protection on output (+/- 30 V)Reverse polarity protection on outputShort-circuit protection on outputReverse polarity protection on power supply
Product certificationsULGLCSA

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp