Q1Can you supply the Schneider LC1F4002Q7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1F4002Q7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1F4002Q7
Material Number
—
Manufacturer
Schneider
Product ID
33431

Get a Free Quote

Request pricing and availability for LC1F4002Q7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current
500 A (at <40 °C) at <= 440 V AC AC-1
[Uc] control circuit voltage
380 V AC 40...400 Hz
IP degree of protection
IP20 front face with shrouds conforming to IEC 60529 / IP20 front face with shrouds conforming to VDE 0106
See all specifications

Product Highlights

  1. Range: TeSys F contactor, device short name LC1F
  2. Contactor Application: Resistive load, utilisation category AC-1, 2 NO power poles
  3. Rated Operational Voltage: <= 1000 V AC 50/60 Hz, <= 460 V DC
  4. Control Circuit: 380 V AC 40...400 Hz, operational limits 0.85...1.1 Uc and drop-out 0.3...0.5 Uc at 55 °C
  5. Rated Operational Current: 500 A at <= 440 V AC AC-1 and 40 °C, conventional free air thermal current 500 A at 40 °C
  6. Rated Breaking Capacity: 3200 A conforming to IEC 60947-4-1
  7. Rated Short-Time Withstand Current: 3600 A for 10 s, 2400 A for 30 s, 1700 A for 1 min, 1200 A for 3 min, 1000 A for 10 min at 40 °C
  8. Associated Fuse Rating: 400 A aM at <= 440 V, 500 A gG at <= 440 V
  9. Rated Insulation Voltage: 1000 V IEC 60947-4-1, 1500 V VDE 0110 group C
  10. Rated Impulse Withstand Voltage: 8 kV, overvoltage category III
  11. Mechanical Durability: 10 Mcycles, maximum operating rate 2400 cyc/h at 55 °C
  12. Operating Time: 40...65 ms closing, 100...170 ms opening
  13. Power Dissipation: 65 W per pole AC-1, 14 W heat dissipation
  14. Connections: control circuit screw clamp terminals 1...4 mm², power circuit bar 30 x 5 mm or lugs-ring terminals 150 mm², tightening torque 1.2 N.m control and 35 N.m power
  15. Mounting and Protection: plate mounting, IP20 front face with shrouds, TH protective treatment
  16. Ambient Air Temperature for Operation: -5...55 °C, storage -60...80 °C, permissible around device -40...70 °C
  17. Operating Altitude: 3000 m without derating
  18. Standards and Certifications: IEC 60947-4-1, IEC 60947-1, EN 60947-4-1, EN 60947-1, JIS C8201-4-1, DNV, CBL, ROS, RM, RoS, RINA, ABS, CCC, UL, BV
  19. Dimensions and Weight: 206 mm height, 213 mm width, 219 mm depth, 8 kg
LC1F4002Q7

Product Information

Technical Specifications

Specifications for LC1F4002Q7

ParameterValue
Product or component typeContactor
Range of productTeSys F
[Ue] rated operational voltage<= 1000 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current500 A (at <40 °C) at <= 440 V AC AC-1
[Uc] control circuit voltage380 V AC 40...400 Hz
Control circuit voltage limitsOperational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) / Drop-out: 0.3...0.5 Uc 40...400 Hz (at 55 °C)
Power dissipation per pole65 W AC-1
RangeTeSys
Connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable endControl circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable endControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable endControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable endControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable endControl circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable endPower circuit: bar 2 cable(s) - busbar cross section: 30 x 5 mmPower circuit: lugs-ring terminals 2 cable(s) 150 mm²Power circuit: bolted connection
ParameterValue
Height206 mm
Width213 mm
Depth219 mm
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 / IP20 front face with shrouds conforming to VDE 0106
Ambient air temperature for operation-5…55 °C
Product certificationsDNVCBLROS (Lloyds register of shipping)RMRoSRINAABSCCCULBV

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp