Industrial Automation Parts. Prompt replies from real people.

Schneider LC1F115F7 Contactors and Protection Relays

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the Schneider LC1F115F7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1F115F7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1F115F7
Material Number
—
Manufacturer
Schneider
Product ID
33158

Get a Free Quote

Request pricing and availability for LC1F115F7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
<= 690 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current
200 A (at <40 °C) at <= 440 V AC-1 / 115 A (at <55 °C) at <= 440 V AC-3
[Uc] control circuit voltage
110 V AC 40...400 Hz
IP degree of protection
IP2X front face with shrouds conforming to IEC 60529 / IP2X front face with shrouds conforming to VDE 0106
See all specifications

Product Highlights

  1. Contactor Type: TeSys F 3-pole contactor for motor control and resistive loads, utilisation categories AC-1, AC-3 and AC-4
  2. Rated Operational Current: 200 A at 40 °C for AC-1 and 115 A at 55 °C for AC-3, with 200 A conventional free air thermal current at 40 °C
  3. Motor Power Range: 18.5 kW at 400 V AC-4 and 55 kW at 380 to 400 V AC-3, up to 80 kW at 660 to 690 V AC-3
  4. Voltage and Control: Operational voltage up to 690 V AC 50/60 Hz or 460 V DC, 110 V AC control circuit at 40 to 400 Hz, 8 kV impulse withstand and 1000 V rated insulation
  5. Durability and Operating Limits: 10 million mechanical cycles, maximum operating rate 2400 cycles per hour, 35 ms closing and 130 ms opening, ambient operating temperature -40 to 60 °C and operating altitude up to 3000 m without derating
  6. Connections and Mounting: Power circuit bar 20 x 3 mm, lugs or connectors for 95 mm², control circuit screw clamp terminals for 1 to 4 mm², plate mounting, 10 N.m power and 1.2 N.m control tightening torque
  7. Compliance: IEC 60947-1, IEC 60947-4-1, EN 60947-1, EN 60947-4-1 and JIS C8201-4-1, with CCC, CB, RM, RoHS, LR, DNV, ABS, RINA, UL, BV, UKCA certifications and IP2X front face with shrouds
LC1F115F7

Product Information

Technical Specifications

Specifications for LC1F115F7
ParameterValue
Product or component typeContactor
Range of productTeSys F
[Ue] rated operational voltage<= 690 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current200 A (at <40 °C) at <= 440 V AC-1 / 115 A (at <55 °C) at <= 440 V AC-3
[Uc] control circuit voltage110 V AC 40...400 Hz
Control circuit voltage limitsOperational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) / Drop-out: 0.2...0.55 Uc 40...400 Hz (at 55 °C)
Power dissipation per pole15 W AC-1 / 5 W AC-3
RangeTeSys
Connections - terminalsPower circuit: bar 2 cable(s) - busbar cross section: 20 x 3 mmPower circuit: lugs-ring terminals 1 cable(s) 95 mm²Power circuit: connector 1 cable(s) 95 mm²Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable endControl circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable endControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable endControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable endControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable endControl circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable endPower circuit: bolted connection
Height162 mm
Width163.3 mm
Depth171 mm
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529 / IP2X front face with shrouds conforming to VDE 0106
Ambient air temperature for operation-40…60 °C
Product certificationsCCCCBRMRoSLROS (Lloyds register of shipping)DNVABSRINAULBVUKCA

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp