Industrial Automation Parts. Prompt replies from real people.

Schneider LC1D40004M5 Contactors and Protection Relays

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D40004M5?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D40004M5 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D40004M5
Material Number
—
Manufacturer
Schneider
Product ID
32119

Get a Free Quote

Request pricing and availability for LC1D40004M5.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current
60 A (at <60 °C) AC AC-1 for power circuit
[Uc] control circuit voltage
220 V AC 50 Hz
IP degree of protection
IP2X conforming to IEC 60529 / IP2X conforming to VDE 0106
See all specifications

Product Highlights

  1. Product Type: TeSys Deca LC1D contactor for resistive load
  2. Utilisation Category: AC-1, AC-3, AC-3e, AC-4
  3. Poles Description: 4P with 4 NO pole contact composition
  4. Rated Operational Voltage: Power circuit up to 690 V AC, 25 to 400 Hz
  5. Rated Operational Current: 60 A at 60 °C, AC-1 for power circuit
  6. Control Circuit Voltage: 220 V AC, 50 Hz
  7. Conventional Free Air Thermal Current: 60 A at 60 °C for power circuit, 10 A at 60 °C for control circuit
  8. Rated Making Capacity: 800 A at 440 V for power circuit per IEC 60947, 140 A AC for control circuit per IEC 60947-5-1
  9. Rated Breaking Capacity: 800 A at 440 V for power circuit per IEC 60947
  10. Associated Fuse Rating: 80 A gG at up to 690 V, coordination type 1 and type 2 for power circuit, 10 A gG for control circuit per IEC 60947-5-1
  11. Protective Cover: With
LC1D40004M5

Product Information

Technical Specifications

Specifications for LC1D40004M5

ParameterValue
Product or component typeContactor
Range of productTeSys Deca
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current60 A (at <60 °C) AC AC-1 for power circuit
[Uc] control circuit voltage220 V AC 50 Hz
Control circuit voltage limits0.3...0.6 Uc (60 °C):drop-out AC 50 Hz / 0.85...1.1 Uc (55 °C):operational AC 50 Hz
Power dissipation per pole5.4 W AC-1
Device short nameLC1D
Connections - terminalsControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 2 1…35 mm² - cable stiffness: solid without cable end
ParameterValue
Height127 mm
Width85 mm
Depth125 mm
IP degree of protectionIP2X conforming to IEC 60529 / IP2X conforming to VDE 0106
Permissible ambient air temperature around the device-5…60 °C / -40…70 °C at Uc
Product certificationsLROS (Lloyds register of shipping)DNVGLRINABVCSAGOSTULCCCUKCA

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp