Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D40004T6?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D40004T6 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D40004T6
Material Number
—
Manufacturer
Schneider
Product ID
31926

Get a Free Quote

Request pricing and availability for LC1D40004T6.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: 690 V AC 25...400 Hz
[Ie] rated operational current
60 A (at <60 °C) at 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
480 V AC 60 Hz
IP degree of protection
IP2X conforming to VDE 0106
See all specifications

Product Highlights

  1. Range and Type: TeSys D / TeSys Deca contactor, device short name LC1D
  2. Contact Configuration: 4-pole, 4 NO contact composition with protective cover
  3. Load Rating: AC-1 resistive load, 60 A at 440 V AC for power circuit at up to 140 °F (60 °C)
  4. Power Circuit Voltage: 690 V AC, 25...400 Hz rated operational voltage
  5. Control Circuit: 480 V AC 60 Hz coil, AC 60 Hz standard control circuit type
  6. Thermal Current: 40 A power circuit and 10 A control circuit conventional free air thermal current at 140 °F (60 °C)
  7. Durability: 15,000,000 mechanical cycles, B10d 1,369,863 cycles with nominal load and 20,000,000 cycles with mechanical load per EN/ISO 13849-1
  8. Terminations: Screw clamp terminals for control circuit 1...4 mm² and power circuit 2.5...16 mm², tightening torque 1.7 N.m control and 5 N.m power
  9. Standards and Certifications: EN/IEC 60947-4-1, EN/IEC 60947-5-1, CSA C22.2 No 14, UL 508, with UL, CSA, GL, CCC, LRoS, DNV, BV, RINA certifications
  10. Ambient Range: -40...140 °F (-40...60 °C) operation, 140...158 °F (60...70 °C) with derating, storage -76...176 °F (-60...80 °C)
LC1D40004T6

Product Information

Technical Specifications

Specifications for LC1D40004T6

ParameterValue
Product or component typeContactor
Range of productTeSys D / TeSys Deca
[Ue] rated operational voltagePower circuit: 690 V AC 25...400 Hz
[Ie] rated operational current60 A (at <60 °C) at 440 V AC AC-1 for power circuit
[Uc] control circuit voltage480 V AC 60 Hz
Control circuit voltage limits0.3...0.6 Uc (60 °C):drop-out AC 50/60 Hz / 0.85...1.1 Uc (60 °C):operational AC 60 Hz
Power dissipation per pole5.4 W AC-1 / 2.4 W AC-3
Device short nameLC1D
Contactor applicationResistive load
Utilisation categoryAC-1
ParameterValue
Connections - terminalsControl circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminal 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminal 2 1…4 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminal 1 2.5…16 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminal 2 2.5…16 mm² - cable stiffness: solid without cable end
Mounting supportRail / Plate
IP degree of protectionIP2X conforming to VDE 0106
Permissible ambient air temperature around the device-60…80 °C storage-40…60 °C operation60…70 °C with derating
Product certificationsGLCCCLROS (Lloyds register of shipping)DNVCSABVRINAUL

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.