Industrial Automation Parts. Prompt replies from real people.

Schneider LC1D400086F7 TeSys Deca Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D400086F7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D400086F7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D400086F7
Material Number
—
Manufacturer
Schneider
Product ID
31930

Get a Free Quote

Request pricing and availability for LC1D400086F7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current
60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
110 V AC 50/60 Hz
IP degree of protection
IP20 front face conforming to IEC 60529
See all specifications

Product Highlights

  1. Product Type: TeSys Deca LC1D contactor for resistive load applications
  2. Utilisation Category: AC-1
  3. Pole Configuration: 4P with 2 NO + 2 NC pole contact composition
  4. Rated Operational Voltage: Power circuit <= 690 V AC 25...400 Hz and <= 300 V DC
  5. Rated Operational Current: 60 A at <= 440 V AC, AC-1, at <= 140 °F (60 °C) for power circuit
  6. Control Circuit Voltage: 110 V AC 50/60 Hz
  7. Conventional Free Air Thermal Current: 60 A at 140 °F (60 °C) for power circuit
  8. Rated Making Capacity: 800 A at 440 V for power circuit conforming to IEC 60947
  9. Rated Breaking Capacity: 800 A at 440 V for power circuit conforming to IEC 60947
  10. Short-Time Withstand Current: 320 A at 104 °F (40 °C) for 10 s, 720 A at 104 °F (40 °C) for 1 s, 72 A at 104 °F (40 °C) for 10 min, and 165 A at 104 °F (40 °C) for 1 min for power circuit
  11. Terminals: Lugs-ring terminals with an external diameter of 8 mm
  12. Protective Cover: Without
LC1D400086F7

Product Information

Technical Specifications

Specifications for LC1D400086F7

ParameterValue
Product or component typeContactor
Range of productTeSys Deca
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage110 V AC 50/60 Hz
Control circuit voltage limits0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Power dissipation per pole5.4 W AC-1
RangeTeSys
ParameterValue
Connections - terminalsControl circuit: lugs-ring terminals - external diameter: 8 mm / Power circuit: lugs-ring terminals - external diameter: 16.5 mm
Height127 mm
Width85 mm
Depth125 mm
IP degree of protectionIP20 front face conforming to IEC 60529
Permissible ambient air temperature around the device-40…60 °C / 60…70 °C with derating