Industrial Automation Parts. Prompt replies from real people.

Schneider LC1D40004G6 IEC Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D40004G6?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D40004G6 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D40004G6
Material Number
—
Manufacturer
Schneider
Product ID
32116

Get a Free Quote

Request pricing and availability for LC1D40004G6.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: 690 V AC 25...400 Hz
[Ie] rated operational current
60 A (at <60 °C) at 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
120 V AC 60 Hz
IP degree of protection
IP2X conforming to VDE 0106
See all specifications

Product Highlights

  1. Contactor Configuration: 4-pole contactor with 4 NO pole contact composition and mechanically linked 1 NO + 1 NC auxiliary contacts
  2. Coil and Control: 120 V AC 60 Hz control circuit voltage with AC standard control circuit type and screw clamp terminals
  3. Power Circuit Ratings: 60 A at 440 V AC AC-1 at 60 °C, 690 V AC operational voltage at 25 to 400 Hz, and 40 A conventional free air thermal current at 60 °C
  4. Making and Breaking Capacity: 800 A at 440 V AC making capacity and 800 kA at 440 V breaking capacity for power circuit conforming to IEC 60947
  5. Mounting and Standards: Plate or rail mounting, IP2X protection, and compliance with IEC 60947-4-1, IEC 60947-5-1, UL 508, and CSA C22.2 No 14
LC1D40004G6

Product Information

Technical Specifications

Specifications for LC1D40004G6

ParameterValue
Product or component typeContactor
Range of productTeSys Deca Advanced
[Ue] rated operational voltagePower circuit: 690 V AC 25...400 Hz
[Ie] rated operational current60 A (at <60 °C) at 440 V AC AC-1 for power circuit
[Uc] control circuit voltage120 V AC 60 Hz
Control circuit voltage limits0.3...0.6 Uc (60 °C):drop-out AC 50/60 Hz / 0.85...1.1 Uc (60 °C):operational AC 60 Hz
Power dissipation per pole5.4 W AC-1 / 2.4 W AC-3
Device short nameLC1D
Contactor applicationResistive load
Utilisation categoryAC-3AC-3eAC-1AC-4
ParameterValue
Connections - terminalsControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 1 2.5…16 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: solid without cable end
Mounting supportPlate / Rail
IP degree of protectionIP2X conforming to VDE 0106
Permissible ambient air temperature around the device-5…60 °C / -40…70 °C at Uc
Product certificationsCSADNVGLBVULCCCRINALROS (Lloyds register of shipping)UKCA