Industrial Automation Parts. Prompt replies from real people.

Schneider LC1D25GD TeSys D IEC Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D25GD?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D25GD cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D25GD
Material Number
—
Manufacturer
Schneider
Product ID
31789

Get a Free Quote

Request pricing and availability for LC1D25GD.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current
25 A (at <60 °C) at <= 440 V AC AC-3 for power circuit / 40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit / 25 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage
125 V DC
IP degree of protection
IP20 front face conforming to IEC 60529
See all specifications

Product Highlights

  1. Product Range: TeSys Deca contactor, device short name LC1D
  2. Contactor Application: Resistive load and motor control
  3. Utilisation Category: AC-1, AC-3, AC-3e, AC-4
  4. Poles Description: 3P with 3 NO pole contact composition
  5. Rated Operational Voltage: Power circuit up to 690 V AC at 25 to 400 Hz or up to 300 V DC
  6. Rated Operational Current: 25 A AC-3 and AC-3e, 40 A AC-1, all at up to 440 V AC and 60 °C
  7. Control Circuit: 125 V DC standard coil with built-in bidirectional peak limiting diode suppressor
  8. Motor Power: 5.5 kW at 220 to 230 V AC, 11 kW at 380 to 440 V AC, 15 kW at 500 to 690 V AC in AC-3 and AC-3e, 5.5 kW at 400 V AC in AC-4
  9. Maximum Horse Power Rating: 2 hp at 115 V AC 1 phase, 3 hp at 230 to 240 V AC 1 phase, 7.5 hp at 200 to 240 V AC 3 phase, 15 hp at 460 to 480 V AC 3 phase, 20 hp at 575 to 600 V AC 3 phase
  10. Auxiliary Contacts: 1 NO + 1 NC mechanically linked and mirror contact
  11. Mechanical Durability: 30 Mcycles
  12. Electrical Durability: 1.65 Mcycles at 25 A AC-3 or AC-3e up to 440 V, 1.4 Mcycles at 40 A AC-1 up to 440 V
  13. Operating Time: 63 ms closing, 20 ms opening
  14. Maximum Operating Rate: 3600 cycles per hour at 60 °C
  15. Connections: Screw clamp terminals for control and power circuits
  16. Mounting Support: Plate or rail
  17. Standards and Certifications: IEC 60947-4-1, IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 14, UL, CCC, CSA, Marine, UKCA, EAC, CB Scheme
  18. IP Degree of Protection: IP20 front face
  19. Permissible Ambient Air Temperature: -40 to 60 °C, with derating up to 70 °C
  20. Operating Altitude: 0 to 3000 m
  21. Dimensions: 85 mm height, 45 mm width, 101 mm depth
  22. Net Weight: 0.53 kg
LC1D25GD

Product Information

Technical Specifications

Specifications for LC1D25GD
ParameterValue
Product or component typeContactor
Range of productTeSys Deca Advanced
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current25 A (at <60 °C) at <= 440 V AC AC-3 for power circuit40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit25 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage125 V DC
Control circuit voltage limits0.1...0.25 Uc (-40…70 °C):drop-out DC0.7...1.25 Uc (-40…60 °C):operational DC1...1.25 Uc (60…70 °C):operational DC
Motor power kW5.5 kW at 220/230 V AC 50/60 Hz (AC-3)11 kW at 380/400 V AC 50/60 Hz (AC-3)11 kW at 415/440 V AC 50/60 Hz (AC-3)15 kW at 500 V AC 50/60 Hz (AC-3)15 kW at 660/690 V AC 50/60 Hz (AC-3)5.5 kW at 220/230 V AC 50/60 Hz (AC-3e)11 kW at 380/400 V AC 50/60 Hz (AC-3e)11 kW at 415/440 V AC 50/60 Hz (AC-3e)15 kW at 500 V AC 50/60 Hz (AC-3e)15 kW at 660/690 V AC 50/60 Hz (AC-3e)5.5 kW at 400 V AC 50/60 Hz (AC-4)
Device short nameLC1D
Connections - terminalsControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 1 2.5…10 mm² - cable stiffness: flexible without cable endPower circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible without cable endPower circuit: screw clamp terminals 1 1…10 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 1 1.5…10 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: solid without cable end
Height85 mm
Width45 mm
Depth101 mm
IP degree of protectionIP20 front face conforming to IEC 60529
Permissible ambient air temperature around the device-40…60 °C / 60…70 °C with derating
Product certificationsULCCCCSAMarineUKCAEACCB Scheme