Product Model
GV2RT04
Material Number
—
Manufacturer
Schneider
Product ID
30332

Get a Free Quote

Request pricing and availability for GV2RT04.

More parts to source? Send your whole list in one enquiry

Key specifications

Product or component type
Motor circuit breaker
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
Motor power kW
0.12 kW at 400/415 V AC 50/60 Hz motor protection high peak current / 0.18 kW at 400/415 V AC 50/60 Hz motor protection high peak current / 0.18 kW at 440 V AC 50/60 Hz motor protection high peak current / 0.37 kW at 690 V AC 50/60 Hz motor protection high peak current
Power dissipation per pole
2.5 W
[In] rated current
0.63 A
IP degree of protection
IP20 conforming to IEC 60529
See all specifications

Product Highlights

  1. Product Type: Motor circuit breaker with thermal-magnetic trip unit
  2. System Integration: Motor protection and transformer protection
  3. Breaking Capacity: 100 kA Icu at 220/230 V AC, 400/415 V AC, 440 V AC, 500 V AC, and 690 V AC, 50/60 Hz, IEC 60947-2
  4. Protection Settings: Thermal adjustment range 0.4...0.63 A, magnetic tripping current 13 A, line rated current 0.63 A
  5. Electrical Ratings: 690 V AC 50/60 Hz rated operational voltage, 6 kV rated impulse withstand voltage, 3P, AC network, 50/60 Hz, IEC 60947-2
  6. Motor Power: 0.12 kW at 400/415 V AC, 0.18 kW at 440 V AC, 0.37 kW at 690 V AC, 50/60 Hz
  7. Physical and Compliance: 45 mm W x 78.5 mm D x 89 mm H, IP20 per IEC 60529, IK04, 35 mm DIN rail or panel mounting, EN/IEC 60947-2 and EN/IEC 60947-4-1
GV2RT04

Product Information

Technical Specifications

Specifications for GV2RT04

ParameterValue
Product or component typeMotor circuit breaker
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Motor power kW0.12 kW at 400/415 V AC 50/60 Hz motor protection high peak current0.18 kW at 400/415 V AC 50/60 Hz motor protection high peak current0.18 kW at 440 V AC 50/60 Hz motor protection high peak current0.37 kW at 690 V AC 50/60 Hz motor protection high peak current
Power dissipation per pole2.5 W
[In] rated current0.63 A
Magnetic tripping current13 A
RangeTeSys Deca
Product nameTeSys GV2
ParameterValue
Connections - terminalsPower circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solidPower circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable endPower circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end
Height89 mm
Width45 mm
Depth78.5 mm
IP degree of protectionIP20 conforming to IEC 60529
Ambient air temperature for operation-20…60 °C
Product certificationsCB SchemeCEUKCACCCcULusEACLROS (Lloyds register of shipping)BV