Schneider GV2RT07 TeSys GV2 Manual Starter and Protector

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider GV2RT07?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider GV2RT07 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
GV2RT07
Material Number
—
Manufacturer
Schneider
Product ID
30335

Get a Free Quote

Request pricing and availability for GV2RT07.

More parts to source? Send your whole list in one enquiry

Key specifications

Product or component type
Motor circuit breaker
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
Motor power kW
0.37 kW at 220/230 V AC 50/60 Hz motor protection high peak current / 0.75 kW at 400/415 V AC 50/60 Hz motor protection high peak current / 0.75 kW at 440 V AC 50/60 Hz motor protection high peak current / 1.1 kW at 440 V AC 50/60 Hz motor protection high peak current / 1.1 kW at 500 V AC 50/60 Hz motor protection high peak current / 1.5 kW at 690 V AC 50/60 Hz motor protection high peak current / 0.63 kW at 230/240 V AC 50/60 Hz transformer protection / 1 kW at 400/415 V AC 50/60 Hz transformer protection / 1.6 kW at 500 V AC 50/60 Hz transformer protection / 1.6 kW at 690 V AC 50/60 Hz transformer protection / 2 kW at 690 V AC 50/60 Hz transformer protection
Power dissipation per pole
2.5 W
[In] rated current
2.5 A
IP degree of protection
IP20 conforming to IEC 60529
See all specifications

Product Highlights

  1. Device Type: TeSys GV2RT motor circuit breaker with thermal-magnetic trip unit and toggle control
  2. Motor Protection: 0.37 kW at 220/230 V AC, 0.75 kW at 400/415 V AC and 440 V AC, 1.1 kW at 440 V AC and 500 V AC, 1.5 kW at 690 V AC, all 50/60 Hz for high peak current motor protection
  3. Transformer Protection: 0.63 kW at 230/240 V AC, 1 kW at 400/415 V AC, 1.6 kW at 500 V AC and 690 V AC, 2 kW at 690 V AC, all 50/60 Hz
  4. Current Settings: 2.5 A rated current, 1.6 to 2.5 A thermal protection adjustment range, 51 A magnetic tripping current
  5. Breaking Capacity: 100 kA Icu at 220/230 V, 400/415 V, 440 V and 500 V AC, 3 kA Icu at 690 V AC, IEC 60947-2
  6. Electrical Characteristics: 690 V AC rated operational and insulation voltage, 6 kV impulse withstand voltage, 3P, AC network, 50/60 Hz, utilisation categories A, AC-3 and AC-3e
  7. Durability: 100000 mechanical cycles and 100000 electrical cycles at AC-3 and AC-3e 415 V In, continuous duty
  8. Mounting and Protection: 35 mm symmetrical DIN rail or panel mounting, IP20 and IK04 protection, 45 mm width, 89 mm height, 78.5 mm depth
  9. Environmental Range: -20 to 60 °C operating temperature, -40 to 80 °C storage temperature, 2000 m maximum operating altitude
GV2RT07

Product Information

Technical Specifications

Specifications for GV2RT07
ParameterValue
Product or component typeMotor circuit breaker
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Motor power kW0.37 kW at 220/230 V AC 50/60 Hz motor protection high peak current0.75 kW at 400/415 V AC 50/60 Hz motor protection high peak current0.75 kW at 440 V AC 50/60 Hz motor protection high peak current1.1 kW at 440 V AC 50/60 Hz motor protection high peak current1.1 kW at 500 V AC 50/60 Hz motor protection high peak current1.5 kW at 690 V AC 50/60 Hz motor protection high peak current0.63 kW at 230/240 V AC 50/60 Hz transformer protection1 kW at 400/415 V AC 50/60 Hz transformer protection1.6 kW at 500 V AC 50/60 Hz transformer protection1.6 kW at 690 V AC 50/60 Hz transformer protection2 kW at 690 V AC 50/60 Hz transformer protection
Power dissipation per pole2.5 W
[In] rated current2.5 A
Magnetic tripping current51 A
RangeTeSys Deca
Product nameTeSys GV2
Connections - terminalsPower circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solidPower circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable endPower circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end
Height89 mm
Width45 mm
Depth78.5 mm
IP degree of protectionIP20 conforming to IEC 60529
Ambient air temperature for operation-20…60 °C
Product certificationsCB SchemeCEUKCACCCcULusEACLROS (Lloyds register of shipping)BV

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.