Industrial Automation Parts. Prompt replies from real people.

Schneider GV2L20 TeSys Deca Manual Starter and Protector

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider GV2L20?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider GV2L20 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
GV2L20
Material Number
—
Manufacturer
Schneider
Product ID
30174

Get a Free Quote

Request pricing and availability for GV2L20.

More parts to source? Send your whole list in one enquiry

Key specifications

Product or component type
Motor circuit breaker
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
Motor power kW
7.5 kW at 400/415 V AC 50/60 Hz / 9 kW at 500 V AC 50/60 Hz / 15 kW at 690 V AC 50/60 Hz
Power dissipation per pole
1.8 W
[In] rated current
18 A
IP degree of protection
IP20 conforming to IEC 60529
See all specifications

Product Highlights

  1. Motor Protection: 3-pole motor circuit breaker with magnetic trip unit and rotary handle, rated 18 A and adjustable thermal protection from 13 to 18 A
  2. Motor Power: 7.5 kW at 400/415 V AC, 9 kW at 500 V AC, and 15 kW at 690 V AC, 50/60 Hz
  3. Breaking Capacity: 100 kA Icu at 230/240 V AC, 50 kA at 400/415 V AC, 20 kA at 440 V AC, 10 kA at 500 V AC, and 4 kA at 690 V AC
  4. Electrical Characteristics: Rated operational and insulation voltage 690 V AC, rated impulse withstand voltage 6 kV, magnetic tripping current 341 A, and suitability for isolation
  5. Durability: 100000 mechanical cycles and 100000 electrical cycles at AC-3/AC-3e 415 V In
  6. Mounting and Terminals: 35 mm symmetrical DIN rail or panel mounting with 2 x M4 screws, screw clamp terminals tightened to 1.7 N.m, 45 mm width
  7. Standards and Certifications: EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, IEC/EN 60335-2-40 Annex JJ, with CCC, UL, CSA, EAC, LROS, BV, RINA, DNV-GL, UKCA, and IECEE CB Scheme certifications
  8. Environmental Ratings: IP20 and IK04 protection, operating temperature -20 to 60 °C, storage temperature -40 to 80 °C, and operating altitude up to 2000 m
GV2L20

Product Information

Technical Specifications

Specifications for GV2L20

ParameterValue
Product or component typeMotor circuit breaker
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Motor power kW7.5 kW at 400/415 V AC 50/60 Hz9 kW at 500 V AC 50/60 Hz15 kW at 690 V AC 50/60 Hz
Power dissipation per pole1.8 W
[In] rated current18 A
Magnetic tripping current341 A
RangeTeSys Deca
Product nameTeSys GV2
Connections - terminalsPower circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solidPower circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable endPower circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end
ParameterValue
Height89 mm
Width45 mm
Depth97 mm
IP degree of protectionIP20 conforming to IEC 60529
Ambient air temperature for operation-20…60 °C
Product certificationsCB SchemeCEUKCACCCcULusEACLROS (Lloyds register of shipping)BVRINADNV-GL

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp