Schneider GV2LE08 TeSys GV2 Manual Starter and Protector

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider GV2LE08?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider GV2LE08 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
GV2LE08
Material Number
—
Manufacturer
Schneider
Product ID
30182

Get a Free Quote

Request pricing and availability for GV2LE08.

More parts to source? Send your whole list in one enquiry

Key specifications

Product or component type
Motor circuit breaker
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
Motor power kW
1.5 kW at 400/415 V AC 50/60 Hz / 1.5 kW at 500 V AC 50/60 Hz / 2.2 kW at 500 V AC 50/60 Hz / 3 kW at 690 V AC 50/60 Hz
Power dissipation per pole
1.8 W
[In] rated current
4 A
IP degree of protection
IP20 conforming to IEC 60529
See all specifications

Product Highlights

  1. Trip Unit: Magnetic trip unit for motor protection
  2. Control Type: Toggle control
  3. Motor Power: 1.5 kW at 400/415 V and 500 V AC 50/60 Hz, 2.2 kW at 500 V AC 50/60 Hz, 3 kW at 690 V AC 50/60 Hz
  4. Breaking Capacity: 100 kA Icu at 230/240 V, 400/415 V, 440 V, and 500 V AC 50/60 Hz, 3 kA Icu at 690 V AC 50/60 Hz per IEC 60947-2
  5. Thermal Protection Adjustment Range: 1.6...2.5 A per IEC 60947-4-1
  6. Magnetic Tripping Current: 74 A
  7. Rated Operational Voltage: 690 V AC 50/60 Hz per IEC 60947-2
  8. Utilisation Category: Category A per IEC 60947-2, AC-3 and AC-3e per IEC 60947-4-1
  9. Terminals: Screw clamp terminals with 1.7 N.m tightening torque
  10. Enclosure Rating: IP20 per IEC 60529
GV2LE08

Product Information

Technical Specifications

Specifications for GV2LE08

ParameterValue
Product or component typeMotor circuit breaker
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Motor power kW1.5 kW at 400/415 V AC 50/60 Hz1.5 kW at 500 V AC 50/60 Hz2.2 kW at 500 V AC 50/60 Hz3 kW at 690 V AC 50/60 Hz
Power dissipation per pole1.8 W
[In] rated current4 A
Magnetic tripping current74 A
RangeTeSys Deca
Product nameTeSys GV2
Connections - terminalsPower circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solidPower circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable endPower circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end
ParameterValue
Height89 mm
Width45 mm
Depth78.5 mm
IP degree of protectionIP20 conforming to IEC 60529
Ambient air temperature for operation-20…60 °C
Product certificationsCB SchemeCEUKCACCCcULusEACLROS (Lloyds register of shipping)BVRINADNV-GL

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.