Q1Can you supply the ROCKWELL 150-SD1NBD?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the ROCKWELL 150-SD1NBD cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
150-SD1NBD
Material Number
—
Manufacturer
ROCKWELL
Product ID
107575

Get a Free Quote

Request pricing and availability for 150-SD1NBD.

More parts to source? Send your whole list in one enquiry

Key specifications

Control Voltage
100...240V AC
Rated operating voltage Ue
200
DV/DT protection
RC snubber network
Operating frequency
47...63 Hz or DC for control power
Output current, max
300mA @ 24V DC supply (terminals 8 and 12) for control power
Weight
71.0
See all specifications

Product Highlights

  1. Voltage and Control Supply: Rated operating voltage 200V with 100...240V AC control supply, 47...63 Hz or DC control power
  2. Current Ratings: Controller rating 361 A, line-connected motor current 120...361 A and delta-connected motor current 210...625 A at 400/415/460V AC, 3-phase
  3. Motor Protection: Integrated electronic I2t overload protection with trip classes 5...30 and trip current rating 118% of motor FLC
  4. Power Circuit Protection: RC snubber network DV/DT protection, metal oxide varistor transient protection at 220 J, 1400V repetitive peak inverse voltage, 6000V rated impulse voltage and 2500V dielectric withstand per IEC
  5. Operating Conditions: -20 to 65 °C ambient without derating, 5...95% noncondensing humidity, 2000 m altitude without derating, IP00 open-type enclosure with IP20 control terminals, vertical mounting
150-SD1NBD

Product Information

Technical Specifications

Specifications for 150-SD1NBD

ParameterValue
Control Voltage100...240V AC
Controller RatingsD1
With displayNo
Voltage type for actuatingAC
Rated operating voltage Ue200
Rated control supply voltage at AC 50 Hz100
Rated control supply voltage at AC 60 Hz100
Controller rating361 A
Continuous duty power structure heat dissipation1083 W
Overload current for line connected devices120 A
Overload current for delta connected devices210 A
Controller typeSMC-50
Trip classes5...30
Trip current rating118% of motor FLC
Base power draw from control module with heat sink fan300VA @ 100...240V AC
DV/DT protectionRC snubber network
Repetitive peak inverse voltage rating1400V per UL/CSA/NEMA for power circuit
Operating frequency47...63 Hz or DC for control power
Rated impulse voltage6000V per IEC for power circuit
Dielectric withstand2500V per IEC for power circuit
Line connected motor currentNormal/standard duty: 120...361A @ 400/415/460V AC, 3-phase
Delta connected motor currentNormal/standard duty: 210...625A @ 400/415/460V AC, 3-phase
Transient protectionMetal oxide varistors: 220 J
Insulation voltageRated 500V per IEC for power circuit
Line connected motor powerNormal/standard duty: 75...200 kW @ 400/415V AC @ 50Hz, 3-phase
Delta connected motor powerNormal/standard duty: 75...200 kW @ 230V AC @ 50Hz, 3-phase
High capacity available fault current, max65kA @ 600V, typical current 1000 A time delay Class J or Class L fuse for inside delta connected motors
Utilization categoryMG 1 per UL/CSA/NEMA for normal duty
Option power adder5VA @ 100...240V AC, 150-SM6 (for each option installed, add to base power to obtain total power requirement)
Standard controller featureTorque control
Standard available fault current, max42kA @ 600V, typical current 1600 A non-time delay fuse for inside delta connected motors
Optional controller featureParam configuration/progming tools
Integrated motor overload protectionYes
Short circuit protection device performance (SCPD) typeType 1
ParameterValue
Control power ride through22 ms for control power
Control module battery typeCR 2032 for control power
Overload typeElectronic - using I2t algorithm
Output current, max300mA @ 24V DC supply (terminals 8 and 12) for control power
Degree of protection (IP)IP00
ShockOpsal: 15 G
Width914.4 mm
Depth355.6 mm
Height1295.4 mm
Power terminal lugsTwo 13.5 mm (0.53 in) diam holes per power pole
VibrationOpsal: 1.0 G peak, 0.15 mm (0.006 in) displacement
FunctionSingle direction
Power terminal markingsNEMA, CENELEC EN50 012
Control terminalsClAing yoke connection, M3 screw clA
Storage and transportation temperature-25 °C
Rated surrounding temperature range without derating-20 °C
Humidity5...95% (noncondensing)
Protection against electrical shockIP00 (IP20 - control terminals only) per IEC
EMC emission levelsRadiated emissions: Class A (per EN 60947-4-2)
EMC immunity levelsSurge transient per EN 60947-4-2
Altitude2000 m (6560 ft) without derating, for ops above 2000...7000 m (6560...22965 ft) maximum, refer to Thermal Wizard
Pollution degree2
Mounting orientationVertical
Atmospheric protectionANSI/ISA - 71.04-2013, class G3 environment
Operating ambient temperature40 to 65 °C (104 to 149 °F) (refer to thermal wizard)
Number of poles3
Horizontal clearance, min0 cm
Vertical clearance, min15 cm
EnclosureOpen type
Metal partsPlated brass, copper or steel
Control modulesThermoset and thermoplastic moldings
Power polesHeatsink hockey puck thyristor modular design
RepairableREPAIRABLE
Preferred Availabilityfalse
Quick Turnaroundfalse
Dimension Height56.01
Lead Time19
Dimension Width62.0
Dimension Length81.0
Stock StatusNON_STOCKED
Weight71.0
Weight UnitKG
Dimension UnitCM