- 150-F108NBDD
The Rockwell 150-F108NBDD is an SMC Flex soft starter with an integrated display and internal bypass. It operates on 100...240V AC control voltage and is rated 108 A, 20-75 Hp at 460V AC. Line-connected motor current is 27...108 A at 600/Y/690V AC, 3-phase; delta-connected motor current is 47...187 A at 500/575V AC, 3-phase. Power circuit operating frequency is 50/60 Hz, with rated operational voltage 200...480V AC (-15%, +10%) per UL/CSA/NEMA. Trip classes are 10, 15, 20, and 30, with trip current at 117% of motor FLC. It provides four programmable NO/NC auxiliary contacts rated 3A at 120V AC and 1.5A at 240V AC, plus integrated motor overload protection and PTC input ratings.
- 150-F108NBRB
The Rockwell 150-F108NBRB is an SMC Flex soft starter with an integrated display. Its controller rating is 108 A, 20–75 Hp at 460 V AC. Rated operational voltage is 200–480 V AC (-15%, +10%) per UL/CSA/NEMA for the power circuit, with 50/60 Hz operating frequency. Line-connected motor current is 27–108 A at 600/Y/690 V AC, 3-phase; delta-connected motor current is 47–187 A at 500/575 V AC, 3-phase. Control supply voltage is 24 V AC at 50 Hz, 24 V AC at 60 Hz, and 24 V DC. Trip classes are 10, 15, 20, and 30, with trip current at 117% of motor FLC. Integrated motor overload protection is included. The open-type enclosure measures 196.4 mm wide, 212.2 mm deep, and 443.7 mm high.
- 150-F108NBRD
The Rockwell 150-F108NBRD is an SMC Flex smart motor controller and soft starter with an open-type enclosure and integrated bypass. It is rated 108 A, 20 to 75 Hp at 460V AC, with line-connected motor current of 27 to 108 A at 600/Y/690V AC, 3-phase, and delta-connected motor current of 47 to 187 A at 500/575V AC, 3-phase. Control voltage is 24V AC/DC at 50 Hz and 60 Hz, or 24V DC. The controller includes a display, integrated motor overload protection, trip classes 10, 15, 20 and 30, and four programmable NO/NC auxiliary contacts. Steady-state heat dissipation with control and fan power is 91 W. Operating temperature is -5 to 50 degrees C open. Dimensions are 196.4 mm wide, 212.2 mm deep, and 443.7 mm high.
- 150-F108NCD
The Rockwell 150-F108NCD is an SMC Flex soft starter with an integrated display and internal bypass. It operates on 100...240V AC control voltage and is rated 108 A, 20-75 Hp at 460V AC. Line-connected motor current is 27...108 A at 600/Y/690V AC, 3-phase; delta-connected motor current is 47...187 A at 500/575V AC, 3-phase. Maximum line-connected motor power is 90 kW at 690V/Y AC, 50 Hz, 3-phase. The power circuit is rated 200...600V AC (-15%, +10%) per UL/CSA/NEMA, with 50/60 Hz operating frequency and 6000V rated impulse voltage per IEC. Integrated motor overload protection is included, with trip classes 10, 15, 20 and 30 and trip current rating 117% of motor FLC. Enclosure is open type, three poles, single direction.
- 150-F108NCRB
The Rockwell 150-F108NCRB is an SMC Flex soft starter for three-phase motors, rated 108 A and 20-75 Hp at 460 V AC. It operates at 200...600 V AC (-15%, +10%) per UL/CSA/NEMA and 50/60 Hz, with 24 V AC/DC control. Line-connected motor current is 27...108 A at 600/Y/690 V AC, three-phase; delta-connected current is 47...187 A at 500/575 V AC, three-phase. Integrated motor overload protection is included, with trip classes 10, 15, 20 and 30 and trip current at 117% of motor FLC. Control options include pump control, and a display is fitted. The open-type unit has three poles, internal bypass, and dimensions of 196.4 mm width, 212.2 mm depth and 443.7 mm height.
- 150-F108NCRD
The Rockwell 150-F108NCRD is an SMC Flex soft starter with an open-type enclosure, three poles, and a display. It operates on 24 V AC/DC control voltage and a rated operational voltage of 200...600 V AC (-15%, +10%) per UL/CSA/NEMA for the power circuit. Controller rating is 108 A, 20-75 Hp at 460 V AC. Line-connected motor current is 27...108 A at 600/Y/690 V AC, 3-phase; delta-connected motor current is 47...187 A at 500/575 V AC, 3-phase. It provides integrated motor overload protection, internal bypass, and programmable NO/NC auxiliary contacts. Steady-state heat dissipation with control and fan power is 91 W. Operating temperature is -5 to 50 degrees C open. Dimensions are 196.4 mm width, 212.2 mm depth, and 443.7 mm height.
- 150-F108NZDB
The Rockwell 150-F108NZDB is an SMC Flex smart motor controller configured as a soft starter with an integrated display and internal bypass. The controller rating is 108 A, 20–75 Hp at 460V AC, with line-connected motor current of 27...108 A at 600/Y/690V AC, 3-phase, and delta-connected motor current of 47...187 A at 500/575V AC, 3-phase. Control voltage is 100...240V AC. The power circuit is rated 230...690V/Y (-15%, +10%) per IEC, with operating frequency 50/60 Hz and rated impulse voltage 6000V per IEC. It provides integrated motor overload protection, trip classes 10, 15, 20 and 30, and pump control. Dimensions are 196.4 mm wide, 212.2 mm deep, and 443.7 mm high.
- 150-F108NZDD
The Rockwell Allen-Bradley 150-F108NZDD is a soft starter in the Smart Motor Controller category, supplied with a display. Its controller rating is 108 A, 20–75 Hp at 460 V AC. Control voltage is 100...240 V AC, and the rated operating voltage Ue is 230 V. The transformer control module is rated 75 VA at 100...240 V AC (-15%, +10%). Overload current is 27 A for line-connected devices and 47 A for delta-connected devices. Trip classes are 10, 15, 20, and 30, with a trip current rating of 117% of motor FLC. Power-circuit operating frequency is 50/60 Hz. Control options include brake control.