Industrial Automation Parts. Prompt replies from real people.

ROCKWELL 140G-KC0H3-D40 Motor protection circuit breaker

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the ROCKWELL 140G-KC0H3-D40?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the ROCKWELL 140G-KC0H3-D40 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
140G-KC0H3-D40
Material Number
—
Manufacturer
ROCKWELL
Product ID
105261

Get a Free Quote

Request pricing and availability for 140G-KC0H3-D40.

More parts to source? Send your whole list in one enquiry

Key specifications

With integrated under voltage release
False
Integrated earth fault protection
False
Rated permanent current Iu
400 A
Rated impulse withstand voltage (Uimp)
8 kV
Weight
0.999
Ambient temperature without derating
104 °F
See all specifications

Product Highlights

  1. Short-Circuit Breaking Capacity: 120 kA at 400 V 50 Hz and 85 kA at 500 V AC per IEC 60947-2, with 100% Ics at 690 V AC and 65 kA at 600 V per UL 489/CSA C22.2 No. 5
  2. Electronic LSI Protection: Adjustable long-time I1 = 0.4 to 1 x In (160 to 400 A) with t1 = 3, 6, 12, 18 s, short-time I2 = 1 to 10 x In (240 to 4000 A) with t2 = 0.05, 0.1, 0.25, 0.5 s, and instantaneous I3 = 1 to 10 x In (600 to 4800 A)
  3. Current and Voltage Ratings: 400 A rated permanent current, 3-pole, 1000 V rated insulation voltage per IEC, and 8 kV rated impulse withstand voltage
  4. Connection and Mounting: Front-side main circuit connection with screw terminals, toggle control element, built-in fixed construction, and optional DIN rail mounting
  5. Physical and Environmental Data: IP40 degree of protection, 205 mm height, 140 mm width, 108.5 mm depth, 0.999 kg weight, and 104 °F ambient temperature without derating
140G-KC0H3-D40

Product Information

Technical Specifications

Specifications for 140G-KC0H3-D40

ParameterValue
Number of poles3
With integrated under voltage releaseFalse
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz120 kA
Integrated earth fault protectionFalse
Complete device with protection unitTrue
Rated permanent current Iu400 A
Type of control elementToggle
Rated impulse withstand voltage (Uimp)8 kV
Frame size400 A
Protection type—Electronic I (instantaneous trip units)I3 = 1...10 x In (600...4800)
Electrical life cycle7000 (400 A)/5000 (600 A) ops @ 415V AC
Protection type—Electronic L (long time trip units)I1 = 0.4...1 x In (160...400), t1 = 3, 6, 12, 18 s
Intermediate point (Irms)30 kA @ rated current up to 400 A, rated voltage 480V AC
Threshold current (Irms)10 ka @ rated current up to 400 A, rated voltage 600V AC
Interrupting rating (Irms)65 kA @ rated current up to 400 A, rated voltage 480V AC
Intermediate point (Ip)35 kA @ rated current up to 400 A, rated voltage 480V AC
Interrupting rating (Ip)43.9 @ rated current up to 400 A, rated voltage 480V AC
Threshold current (Ip)21 kA @ rated current up to 400 A, rated voltage 600V AC
Threshold current (I2t)1.5x103 @ rated current up to 400 A, rated voltage 600V AC
Intermediate point (I2t)2.4x103 @ rated current up to 400 A, rated voltage 480V AC
Interrupting rating (I2t)2.8x103 @ rated current up to 400 A, rated voltage 600V AC
Protection type—Electronic S (short time trip units)I2 = 1...10 x In (240...4000), t2 = 0.05, 0.1, 0.25, 0.5 s
Rated service short-circuit breaking capacity (Ics(% Icu)) per IEC 60947-2 rating100% @ 690V AC, 50/60 Hz
Interrupting rating per UL 489/CSA C22.2, No. 565kA @ 600V, 50/60 Hz
ParameterValue
Rated ultimate short-circuit breaking capacity (Icu) per IEC 60947-2 rating85kA @ 500V AC, 50/60 Hz
Protection typeElectronic LSI-long and short time, high instantaneous
Motor drive integratedFalse
With switched-off indicatorFalse
Motor drive optionalTrue
Position of connection for main current circuitFront side
Type of electrical connection of main circuitScrew connection
Insulation voltageRated 1000V per IEC
Suitable for DIN rail (top hat rail) mountingFalse
DIN rail (top hat rail) mounting optionalTrue
Degree of protection (IP)IP40
Weight0.999
Mechanical life operations240 /h
Factory optionNone
Height205 mm
Device constructionBuilt-in device fixed built-in technique
Width140 mm
Depth108.5 mm
Storage temperature-40 °F
Wire temperature ratingAl or Cu 75 °C
Operational voltage (Ue)90% @ 3000 metre (9840 ft) altitude
Rated uninterrupted current (Iu)98% @ 3000 metre (9840 ft) altitude
Ambient temperature without derating104 °F
RepairableNOT_REPAIRABLE
Preferred Availabilityfalse
Quick Turnaroundfalse
Dimension Height0.0
Lead Time15
Dimension Width0.0
Dimension Length0.0
Stock StatusNON_STOCKED
Weight UnitKG

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp