Industrial Automation Parts. Prompt replies from real people.

ABB OT800U12C Isolating switch

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/24/2026

Q1Can you supply the ABB OT800U12C?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the ABB OT800U12C cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
OT800U12C
Material Number
1SCA104042R1001
Manufacturer
ABB
Product ID
91086

Get a Free Quote

Request pricing and availability for OT800U12C.

More parts to source? Send your whole list in one enquiry

Key specifications

Mechanical endurance
3000 cycles
Rated impulse withstand voltage
12 kV
Rated insulation voltage
1000 V
Rated operational current AC-21A (up to 690 V)
1600 A
Rated operational current AC-22A (690 V)
1600 A
Rated operational current AC-22A (up to 500 V)
1600 A
See all specifications

Product Highlights

  1. Short-Circuit Rating: 110 kA short-circuit current rating
  2. Mounting: Base mounting with flexible installation orientation
  3. Terminals: Lug terminals for connecting and disconnecting circuits
  4. Standards: Complies with IEC 60947-1 and UL 98
OT800U12C

Product Information

Technical Specifications

Specifications for OT800U12C

ParameterValue
Type designationOT800U12C
Mechanical endurance3000 cycles
Rated impulse withstand voltage12 kV
Rated insulation voltage1000 V
Rated operational current AC-21A (up to 690 V)1600 A
Rated operational current AC-22A (690 V)1600 A
Rated operational current AC-22A (up to 500 V)1600 A
ParameterValue
Rated operational current AC-23A (690 V)1250 A
Rated operational current AC-23A (up to 500 V)1250 A
Rated short-time making capacity Icm (690 V)92 kA
Rated short-time withstand current Icw (690 V, 1 s)50 kA
Rated thermal current Ith (open air)1600 A
UL98 general use rating (600 V)800 A

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp